Instruction Book    IB182312EN   June 2016   www.eaton.com

50/75/150 VCP-W

Selectable Ground and Test Device

SECTION 4:  DESCRIPTION AND OPERATION

The SG&T is a draw out device that can be inserted into a circuit 

breaker cubicle in the same manner as the 150 VCP-W Circuit 

Breaker. It can be ordered as a single terminal device or a double 

terminal selectable ground and test device. Each terminal is isolated 

from each other and the ground bus connections by insulating 

barriers. The upper and lower terminals are accessible upon opening 

the respective front hinged door. The ground connection is easily 

accessible on the lower front section of the device (Figure 3.3.a). 

Interchangeable primary disconnects allow the SG&T device to be 

converted between the available amperes for this device. (1200A / 

2000A and 3000A)

 WARNING

IT IS MOST IMPORTANT THAT THE LOAD OR LINE TERMINALS BE 

CORRECTLY IDENTIFIED FOR EACH COMPARTMENT BEFORE USING THIS 

DEVICE.

Type 150 VCP-W Selectable Ground & Test devices are also available 

with either the upper or lower terminals only.

4.1 INSULATING BARRIERS

Insulating barriers are GPO-3 glastic material used to isolate the 

primary terminals from each other and the ground connections.

4.2 BUSHINGS AND DISCONNECTING CONTACT 

ASSEMBLIES

The upper and lower bushings, which are the primary circuit 

terminals of the selectable ground and test device, consist of 

silver plated insulated conductors. Multiple finger type primary 

disconnecting contacts at the ends of the conductors provides 

means for connecting and disconnecting the SG&T device to the bus 

terminals in the switchgear compartment. (Figure 3.5)

4.3 GROUNDING CONTACTS

The grounding contact is an assembly of spring-loaded fingers, 

which ground the device by engaging the switchgear cell grounding 

bus when the SG&T device is levered into the “connect” position. 

The ground contact is located at the lower section of the device, on 

the truck, and visible from the front of the device. (Figure 3.3.a)

4.4 BREAKER-CELL CODING PLATES

 NOTICE

CODE PLATES WILL BE SUPPLIED PER SWITCHGEAR REQUIREMENTS AND 

THEREFORE AMPERAGE/RATED SHORT-TIME CURRENT ARRANGEMENTS 

WILL NOT BE COVERED IN THIS MANUAL. DETAILED INFORMATION 

ON THE SPECIFIC CODE PLATE OPTIONS WILL BE PROVIDED WITH THE 

CUSTOMER ORDER. 

This is a combination of a notched plate in the cell and interference 

bars on the breaker, so that only appropriately rated breakers can be 

put into the cell (Figure 3.3.a).

 WARNING

FOR 1200A/2000A/3000A UNIVERSAL SELECTABLE GROUND & TEST 

DEVICES A CODE PLATE HAS BEEN FACTORY INSTALLED TO MATCH THE 

RATING OF THE FACTORY-INSTALLED PRIMARY DISCONNECTS. ENSURE 

THAT THE CORRECT PRIMARY DISCONNECTS AND CODE PLATES HAVE 

BEEN INSTALLED FOR THE CORRECT APPLICATION. 

4.5 CELL POSITION DESCRIPTION

Position A: This is the withdrawn position. In the withdrawn position, 

the selectable ground and test device is out of the cell. The racking 

handle is not required for this position.
Position B: As the SG&T device is pushed into the cell, it will reach a 

mechanical stop. This is the “disconnect” position.
Position C: Continue rotating the racking handle until the rotating 

handle turns freely, and the SG&T device stops moving. The device 

will have reached the “connect” position. (Figure 5.11) Remove the 

racking handle.

Figure 4.1. Installed Code Plate (1200A/50kA Unit Shown)

Figure 4.2. Primary Disconnect Installed (3000A)

Summary of Contents for VCP-W Series

Page 1: ...Instruction Book IB182312EN 50 75 150 VCP W Selectable Ground and Test Device 150 VCP W SGT June 2016 Supersedes October 2015 Effective...

Page 2: ...an Eaton sales office should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agree...

Page 3: ...4 2 BUSHINGS AND DISCONNECTING CONTACT ASSEMBLIES 11 4 3 GROUNDING CONTACTS 11 4 4 BREAKER CELL CODING PLATES 11 4 5 CELL POSITION DESCRIPTION 11 4 6 DEVICE AMPERAGE CONVERSION PROCEDURE 13 SECTION 5...

Page 4: ...N AND VAST VARIETY OF SYSTEM USER REQUIREMENTS SPECIFIC SAFE OPERATING PROCEDURES FOR THE USE OF THIS DEVICE MUST BE DEVELOPED BY THE USER WARNING SATISFACTORY PERFORMANCE OF SELECTABLE GROUND AND TES...

Page 5: ...able Ground and Test Device Dimensions Breaker Type Sized For Circuit Breaker Compartment Amps A B C D E F G H I J K 150 VCP W 500 Dual 1200 2000 28 50 26 76 10 00 27 81 12 00 14 13 20 88 24 63 2 25 2...

Page 6: ...n the device Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not leave the selectable ground and test device in an intermediate positio...

Page 7: ...Services System office Tools and Accessories Racking Handle The racking handle is used to drive the racking mechanism which moves the SG T device into and out of the cell This racking handle is the s...

Page 8: ...g objects excessive moisture etc must be provided Container should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation Moisture can...

Page 9: ...ront External View of 150 VCP W SG T Device 3 2 1 8 5 4 7 6 Front External View 150 VCP W SG T Shown 1 Lock out Tag out Ring 4 KirkTM Key Interlock 7 Lift Pull Handle 2 Friction Hinge 5 Spring Loaded...

Page 10: ...une 2016 www eaton com 50 75 150 VCP W Selectable Ground and Test Device Figure 3 3 b Rear External View of 150 VCP W SG T Device Back External View 150 VCP W SG T Shown 1 Lifting Point 2 Primary Disc...

Page 11: ...als in the switchgear compartment Figure 3 5 4 3 GROUNDING CONTACTS The grounding contact is an assembly of spring loaded fingers which ground the device by engaging the switchgear cell grounding bus...

Page 12: ...4 5 Primary Disconnect Shim Removal 3000A Figure 4 8 Primary Disconnect Installed 1200A 2000A Figure 4 6 Primary Disconnect Installation 1200A 2000A Figure 4 4 Primary Disconnect Removal 3000A Figure...

Page 13: ...roperly stored to avoid potential damage Figure 4 4 Note N Ensure shims are installed as shown in Figure 4 5 for the 3000A configuration c THE GROUND AND TEST CODE PLATE MUST BE CHANGED AT THIS TIME T...

Page 14: ...IN THE NEUTRAL POSITION b For SG T devices equipped with Kirk Locks on the terminal access doors use the Kirk key provided to release the special bolt that is held by the Kirk locking system Slide th...

Page 15: ...5 3 Selector Blade Figure 5 6 Utilizing Hot Stick To Engage Selector Blade Figure 5 5 Selector Blade Disengaged Shown in Upper Position Figure 5 7 Selector Blade Engaged Shown in Upper Position Figure...

Page 16: ...IER WHEN PUSHING A SG T INTO A CELL FAILURE TO DO SO COULD RESULT IN BODILY INJURY IF FINGERS BECOME WEDGED BETWEEN THE SG T AND THE CELL USE BOTH FULLY OPENED HANDS FLAT ON THE FRONT OF THE SG T TO A...

Page 17: ...e In Connect Position Figure 5 12 Removing SG T using Lift Pull Handle To remove the SG T from the cell install the extension guide rails Pull up on the Lift Pull Handle as shown in Figure 5 12 then p...

Page 18: ...uired to cut dirt used Stoddard s Solvent Eaton part number 55812CA or commercial equivalent Hardware Visually inspect all hardware Replace any damaged or missing hardware with parts equivalent to tho...

Page 19: ...ating experience 7 1 1 ORDERING INSTRUCTIONS 1 Always specify the selectable ground and test device rating information and general order number from the nameplate 2 Describe the item give the style nu...