Instructional Booklet 

IB022010EN

Effective July 2019
Revision #4

Instructions for installation, operation,  

and maintenance of medium voltage 

VC-W MR2 (integral racking) 

EATON

 www.eaton.com

Notices and warnings

m

 NOTICE

ALL USERS OF THIS PRODUCT SHOULD READ AND FOLLOW THE  

INSTRUCTIONS PROVIDED HEREIN; HOWEVER, THIS INSTRUCTION BOOK 

SHOULD NOT BE CONSIDERED ALL INCLUSIVE REGARDING INSTALLATION 

OR MAINTENANCE PROCEDURES.  IF FURTHER INFORMATION IS 

REQUIRED, YOU SHOULD CONSULT EATON’S ELECTRICAL SERVICES & 

SYSTEMS. 

 

READ AND UNDERSTAND THIS AND OTHER SUPPLIED INSTRUCTIONS 

AND DRAWINGS IN THEIR ENTIRETY BEFORE INSTALLING OR OPERATING 

THIS DEVICE.  ADJUSTMENT, REPAIR OR MAINTENANCE, OTHER THAN 

THOSE DESCRIBED HEREIN, MUST BE PERFORMED BY QUALIFIED  

PERSONNEL.  A QUALIFIED PERSON IS ONE WHO IS FAMILIAR WITH  

THE CONSTRUCTION AND OPERATION OF THIS EQUIPMENT AND THE  

HAZARDS INVOLVED.

m

 WARNING

IMPROPER USE OR MAINTENANCE OF THIS PRODUCT, OR OPERATING 

IT IN A MANNER FOR WHICH IT WAS NOT INTENDED, MAY RESULT IN 

DEATH, SERIOUS PERSONAL INJURY, OR PROPERTY DAMAGE. 

 

READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE ATTEMPTING 

ANY OPERATION OR MAINTENANCE OF THE CIRCUIT BREAKERS OR 

AUXILIARIES TO BE OPERATED BY THIS DEVICE. 

 

ALL SAFETY CODES, SAFETY STANDARDS, AND/OR REGULATIONS AS 

THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY 

ADHERED TO.

m

 NOTICE

THE DANGER, WARNING, AND CAUTION MESSAGES INCLUDED AS A 

PART OF THE PROCEDURAL STEPS IN THIS MANUAL ARE FOR PERSONNEL 

SAFETY AND PROTECTION OF EQUIPMENT FROM DAMAGE.  AN 

EXAMPLE OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE 

THIS PARAGRAPH TO FAMILIARIZE PERSONNEL WITH THIS TYPE OF 

PRESENTATION.  THIS WILL HELP ASSURE THAT PERSONNEL ARE ALERT 

TO THESE TYPES OF MESSAGES.  IN ADDITION, THESE MESSAGES ARE 

ALL UPPERCASE AND BOLDFACE.

This product is manufactured by Eaton at the Greenwood Assemblies 

Plant: 2210 Hwy 72/221, Greenwood, SC 29649 .
All possible contingencies which may arise during installation,  

operation, or maintenance, and all details and variations of this  

equipment are not encompassed by these instructions .  If further 

information is desired by purchaser regarding particular installation, 

operation, or maintenance of particular equipment, contact an Eaton 

sales or service representative .

Introduction

Switchgear with the VC-W MR2 integral racking option allows an 

operator to remotely rack a VCP-W breaker or auxiliary drawer 

from a distance of 30 ft . (9 .14 m) or greater depending on the 

communication option installed .  The integral racking assembly 

consists of a controller and a motor mounted in the rear of the 

breaker or auxiliary pan assembly, as well as safety and component 

position sensing devices located on the racking mechanism of the 

breaker and auxiliary pan assembly .  The controller accepts 120 Vac 

and supplies power to the motor based on user input .  The position 

of the VCP-W breaker or auxiliary drawer is detected by two limit 

switches located on the side of the racking mechanism .

m

 DANGER

WHEN SWITCHGEAR IS CERTIFIED TO BE ARC-RESISTANT PER  

ANSI/IEEE

®

 STD.  C37.20.7, THE ARC-RESISTANT RATING IS ONLY VALID 

WHEN ALL DOORS ARE CLOSED AND PROPERLY LATCHED OR BOLTED, 

AND ALL COMPONENTS ARE INSTALLED AND WORKING PROPERLY. 

IN ADDITION, REMOVAL OF ANY BREAKER FROM ITS CELL WITHOUT 

REINSTALLING A BREAKER OR ARC-RESISTANT PROVISION COVER WILL 

VOID THE ARC-RESISTANT RATING.

Eaton contact information

For additional information about Eaton products please call 1-800-

525-2000 or log onto www .eaton .com .  Additional Medium Voltage 

Switchgear information regarding Pricing/Aftermarket, Customer 

Service, Engineering/Technical Information, or Warranty, can be 

found by calling 1-800-345-4072 .
Eaton Electrical Services and Systems (EESS) can be reached at 

1-800-498-2678 .
If further information is desired regarding this particular installation 

or application information, contact the local Eaton sales office, 

reference Eaton’s Consulting Application Guide, or the appropriate 

industry standards .

Summary of Contents for VC-W MR2

Page 1: ...Open permissive 9 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking Description Page E6 Communication error 9 E7 No MV device 9 E8 Firmware compatibi...

Page 2: ...2 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Page 3: ...source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PA...

Page 4: ...SC 29649 All possible contingencies which may arise during installation operation or maintenance and all details and variations of this equipment are not encompassed by these instructions If further i...

Page 5: ...ive interlocks wired for every breaker cell with integrated racking and one for every auxiliary cell with integrated racking Breaker cell specific interlocks 1 Normally closed mechanism operated compa...

Page 6: ...pass E5 error circuit CAUTION by jumpering terminals 51 to 54 you have defeated the inter lock circuit For troubleshooting move the black mo tor lead on terminal 47 to terminal 44 to bypass E2 error c...

Page 7: ...the auxiliary pan assembly This lock prohibits an operator from manually inserting a crank into the Lev in assembly and manually racking the breaker or auxiliary device as specified in the switchgear...

Page 8: ...hen motor current is in excess of allowed value Multiple causes could create this condition E1 error codes may occur if system is operated on temporary generator power Operator should shut off power t...

Page 9: ...ibility error This state results from the pendant and controller card not having compatible firmware Contact your Eaton representative to have the firmware updated E9 No test MR2 open close only This...

Page 10: ...Disconnect buttons can be used to scroll up and down 01 to 99 until the desired address number is reached While scrolling the Connect LED will continue to flash to let the user know that the address...

Page 11: ...device from a distance of up to 30 ft 9 14 m from the equipment with a Cat 5 cable typically there will be an RJ 45 jack located on the front panel of the switchgear see Figure 14 The MV device can b...

Page 12: ...cking device via a SCADA system or multiple Modbus interface communication systems These systems can be wired to a central control room or to a remote panel located a safe distance away from the equip...

Page 13: ...ontrol power to breaker a At this time the breaker open and close operations can be tested electrically b To proceed further and rack the breaker to the connected position the breaker must be open 1 A...

Page 14: ...ator should then open the breaker c After the breaker is open the error can be cleared by pressing the disconnect button 8 Once the error is cleared the operator can rack the breaker to the test or di...

Page 15: ...15 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com Notes...

Page 16: ...16 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Page 17: ...17 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Page 18: ...n USA Publication No IB022010EN TBG001320 July 2019 Eaton is a registered trademark All other trademarks are property of their respective owners Instructions for installation operation and maintenance...