•  Average temperature over 24 hours must not 30°C and the temperature of the room 
    should not 40°C.
•  Care should be taken to prevent restriction of air circulation.
•  Adequate space must be maintained between transformers / between transformers and 
    nearby equipment or walls.
•  Separation is especially important near the transformer radiators, with a recommended 
    minimum spacing equal to the radiator panel depth.
•  In case the height of the place of installation higher than 1000m and/or the ambient 
    temperature values are higher than the ones specified above, it is necessary to specify it 
    at the ordering stage since a particular dimensioning of the transformer depends upon 
    these values.
•  Do not energize the transformer which do not provide storage control procedures.

6.2 CONNECTION

6.2.1 Electrical and Mechanical Connections

•  Decide and choose the cable cross-section according to the system current and voltage.
•  Be sure that the surfaces are clean. Dirty surfaces may cause isolation and contact 
    problems.

6. INSTALLATION AND CONNECTION

  

6.1 INSTALLATION

The installation location of a transformer must be carefully considered. Transformers, as is the 
case with most electrical equipment, generate a substantial amount of heat during operation. 
This heat must be removed in order to allow the transformer to maintain its designed 
maximum temperature limits.

If a transformer is located outdoors, the heat will be removed by natural convection cooling 
unless the radiator (or corrugated walls) air flow is restricted by surrounding objects. Indoor 
installations require adequate ventilation to remove the heat of transformer operation. Inlet 
ventilation openings should be as low as possible and outlet ventilation openings as high as 
possible.

Ulusoy Distribution Transformers Maintenance, Operation, Installation and Instruction Manual

Summary of Contents for Ulusoy

Page 1: ...Ulusoy Distribution Transformers Maintenance Operation Installation and Instruction Manual www eaton com...

Page 2: ...ary assistance to the maintenance personnel to facilitate a periodic inspection of the transformer and to indicate the steps that they should follow to effect a more detailed examination of the active...

Page 3: ...n imminently hazardous situation which if not avoided will result in death serious personnel injury and property damage WARNING indicates a potentially hazardous situation which if not avoided could r...

Page 4: ...an be used to lift the entire equipment Under no circumstances may moisture be allowed to penetrate into the transformer For hermetically sealed transformers both those with gas cushions and those wit...

Page 5: ...HV or low voltage LV insulators to guide the transformer when moving it During the transport or the handling it is recommended to use only the special lifting eyes and tow attachments Angle between t...

Page 6: ...of individual pieces WARNING Unless indicated otherwise storage temperature must be between 25C and 50C Monitoring and checking the transformers during storage Preferably only fully assembled liquid f...

Page 7: ...nical Connections Decide and choose the cable cross section according to the system current and voltage Be sure that the surfaces are clean Dirty surfaces may cause isolation and contact problems 6 IN...

Page 8: ...and nut in 8 8 steel C Cover frame Bolt and nut in stainless steel pitch 60mm cork gasket pitch 90mm nbr gasket D Busbar bushings Fixing on cover Top piece onto bottom piece 5 4 6Nm 20 25Nm 20 25Nm 8...

Page 9: ...2 Table 2 Outdoor Electrical Clearance Un H V side voltage of rated level All clearances are in mm Electrical clearances are given for 1000m After 1000m till 3000m each 100m distance must be increase...

Page 10: ...pecifications should be added Oil leakage must be prevented with proper procedure If transformer is hermetically sealed the manufacturer should be informed as soon as possible Dehydrating breather sho...

Page 11: ...3 5 Years Conservation Tank Oil Leakage Every 2 Years Annually Oil Oil Dielectric Test All periodical controls are listed as a table below Table 3 Periodical Check Pressure relief device T 10 must ne...

Page 12: ...w Oil Sample Desired Value New Oil Filling Transformer Oil Sample Desired Value Oil Sample From Operating Transformer Proper Must Be Removed Pcb Analysis ASTM D 4059 ppm NA NA 50 50 Test Name Method U...

Page 13: ...sformers Current transformer Winding temperature indicator With and without contact thermometer 8 ACCESSORIES 8 1 STANDARD COMPONENTS AND ACCESSORIES Rating plate HV porcelain bushing LV porcelain bus...

Page 14: ...sampling of gases and of oil from oil filled electrical equipment and for the analysis of free and dissolved gases IEC 60599 Mineral oil impregnated electrical equipment in service Guide to the inter...

Page 15: ...about the surface protection quality paint of the transformer 7 Is there any oil leakage on the transformer Invalid for dry type distribution transformers 8 Is there any conspicuous point at which you...

Page 16: ...90 312 502 06 63 Eaton s mission is to improve the quality of life and the environment through the use of power management technologies and services We provide sustainable solutions that help our cust...

Reviews: