The Buzzer definition as below

 

UPS condition 

Buzzer status 

Fault active 

Continuous 

Over Load                           
Warning active 

2 Beep every second 

Other Warning active   

Beep every second 

Battery output 

Beep every 4 seconds, if battery low, buzzer Beep every second 

Bypass output 

Beep every 2 minutes 

 

5.2 LCD description 

The  LCD  backlight automatically dims after  2  minutes of  inactivity (except UPS  is 

fault). Press any button to wake up the screen. 

 

 
 
 
 
 
 
 
 
 
 

 

 

The following table describes the information of ups status. 

Note:  If  other  indicator  appears,  see  troubleshooting  on  chapter  7.2  for  more 

information. 

Operation status 

Cause 

Description 

Standby mode 

 

The UPS is Off. 

UPS is operating without output. 

Summary of Contents for Tower 10K

Page 1: ...Eaton 9E IN User Manual Tower 6 10K...

Page 2: ...vel 3 IEC 61000 4 8 Conducted magnetic field level 4 Performance IEC EN 62040 3 Special symbols The following are examples of symbols used on the UPS or accessories to alert you to important informati...

Page 3: ...e batteries may explode Batteries constitute a danger electrical shock burns The short circuit current may be very high Precautions must be taken for all handling Wear rubber gloves and boots Do not l...

Page 4: ...r to installation storage must be in a dry place The admissible storage temperature range is 25 C to 60 C with battery 15 C to 40 C without battery Special precautions The unit is heavy wear safety sh...

Page 5: ...4 INSTALL THE UNIT 8 4 POWER CABLES CONNECTION 10 4 1 ACCESS TO TERMINAL BLOCKS AC SOURCE TO UPS 11 4 3 PARALLEL INSTALLATION AND OPERATION OPTIONAL 12 5 OPERATION 16 5 1 CONTROL PANEL 16 5 2 LCD DESC...

Page 6: ...UPS 34 7 3 STORING THE EQUIPMENT 34 7 4 REPLACING BATTERIES 35 7 5RECYCLING THE USED EQUIPMENT 36 8 TROUBLESHOOTING 37 8 1 TYPICAL ALARMS AND FAULTS 37 8 2 SILENCING THE ALARM 41 9 SPECIFICATIONS 42...

Page 7: ...ording to an eco design approach Substances This product does not contain CFCs HCFCs or asbestos Packing To improve waste treatment and facilitate recycling separate the various packing components The...

Page 8: ...ltage spikes frequency variations switching transients and harmonic distortion Power outages may occur unexpected and the power quality will be erratic These power problems have the potential to corru...

Page 9: ...3 2 Presentation 2 1 Front panel Tower model Tower UPS 6KS 10KS Tower UPS 6K 10K Tower EBM...

Page 10: ...lel card optional 7 Dry IN OUT 8 Input Output terminal Standard model 5pole IPL IPN PE OPL OPN long backup model has 2 version one is 5 Pole Another is 7pole 7pole add bat bat and no external battery...

Page 11: ...5 2 3 Circuit diagram...

Page 12: ...ed during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for co...

Page 13: ...the unit s front panel and rear panel Discard or recycle the packaging in a responsible manner or store it for future use Packing materials must be disposed in compliance with all local regulations co...

Page 14: ...Stabilizer bracket Ear bracket Rail kit User manual V V V V standard configuration assembled to unit O optional configuration If you ordered other accessories please contact with local sale center 3 4...

Page 15: ...e 2 Connect EBM to UPS with Battery power cable Note This Battery power cable may have different plug according to the number of battery inside of this unit please check the Voltage parameter on rear...

Page 16: ...2 8AWG 10mm 2 6AWG Input fuse 80A 100A Output L N Min conductor cross section 6mm 2 8AWG 10mm 2 6AWG Battery cable 6mm 2 8AWG 10mm 2 6AWG Note It suggests to use standard battery cable in package whe...

Page 17: ...ualified electrical personnel Before carrying out any connection check that the upstream protection devices Normal AC source and Bypass AC source are open O Off Always connect the ground wire first 1...

Page 18: ...ndant output power How to install a new parallel UPS system 1 Before installing a new parallel UPS system please prepare the input output wires breakers and a main maintenance mechanical switch or sta...

Page 19: ...13 4 Install cable locker to protect the parallel cable for each UPS 5 Connect the input and output wires and make sure all the breakers are turned off Tower model...

Page 20: ...nput and output cable of the UPSs is required to be less than 20 2 If the distance between the UPS and breaker panel is more than 20 meters in parallel system the length difference between input and o...

Page 21: ...d disconnect cables wires 6 Switch on the mains breaker and input breaker of the reserved UPS make sure the UPS work in bypass mode 7 Switch on the O P breaker and main O P breaker 8 Transfer the main...

Page 22: ...s and settings The following table shows the indicator status and description Indicator Status Description Normal Green On The UPS is operating normally on Online or on High Efficiency mode Battery Or...

Page 23: ...100ms 1s to scroll down the menu option Enter next menu tree Press this button for 100ms 1s to select the present menu option or enter next menu but do not change any setting Select one menu option Pr...

Page 24: ...ery second Bypass output Beep every 2 minutes 5 2 LCD description The LCD backlight automatically dims after 2 minutes of inactivity except UPS is fault Press any button to wake up the screen The foll...

Page 25: ...and number of Extended Battery Modules EBMs the Battery Low warning may occur before the battery reaches 20 capacity High Efficiency mode The UPS is operating on High Efficiency mode Once the mains ar...

Page 26: ...he problems are not fatal The UPS continues working but please pay attention to the warning or the UPS may fail Fault Some fatal problems happened The UPS will cut off the output or transfer to bypass...

Page 27: ...nual battery test for single UPS Parallel UPS battery test Starts a manual battery test for parallel UPS Single UPS turn off Turn off one UPS in parallel UPS system Reset fault status Clears active fa...

Page 28: ...4 0 4A for standard model 0 12 0 12A for long backup model 1 4A for 6K 2A for 10K 4A for 6KS 10KS Site wiring fault alarm disabled enabled disabled LCD contrast 5 5 0 5 5 UPS startup and shutdown Plea...

Page 29: ...more than 1 second the buzzer will beep for300ms UPS starts to turn on A few seconds later the UPS turns into Battery mode If the utility power comes back the UPS will transfer to Line mode without ou...

Page 30: ...the user own requirements optimize the function of UPS The main menu In the default UPS status summary screen when pressing or 300ms the detailed information about alarm battery the system status wou...

Page 31: ...on the menu of UPS status the display would enter the next UPS status menu tree The content of UPS status menu tree is same as the default UPS status summary menu By pressing ESC 300ms the display wo...

Page 32: ...d enter the next measurement menu tree A lot of detailed useful information could be checked here Ex the output voltage and frequency the output current the load capacity the input voltage and frequen...

Page 33: ...300ms the display would return the last main menu tree The control menu By pressing on the menu of Control the display would enter the next control menu tree Start Battery Test this is one command tha...

Page 34: ...28...

Page 35: ...The setting menu Please contact your local distributor for further information before using the settings Some settings would be changed the specification and some settings would enable or disable some...

Page 36: ...30...

Page 37: ...31 Example set rated output voltage value...

Page 38: ...ction When the EPO function is enabled default setting once the EPO port is pulled out the UPS would shut off the output and enter into EPO mode and the UPS would not respond anything ON OFF request u...

Page 39: ...ntact your local distributor for details 6 3 UPS Management Software WinPower is a new software for UPS monitoring which provides user friendly interface to monitor and control your UPS This unique so...

Page 40: ...f usage and ambient temperature Batteries used beyond expected service life will often have severely reduced runtimes Replace batteries at least every 4 years to keep units running at peak efficiency...

Page 41: ...ired Refer to your local codes for disposal requirements Never dispose of batteries in a fire Batteries may explode when exposed to flame Do not open or mutilate the battery or batteries Released elec...

Page 42: ...of Control 3 Select Control then Single battery test The UPS can starts battery test only in line mode without active alarms During the battery test the UPS transfers to Battery mode and discharges th...

Page 43: ...t Use the following troubleshooting chart to determine the UPS alarm condition 8 1 Typical alarms and faults To check the Event log 1 By pressing on the menu of Event log 2 Scroll through the listed e...

Page 44: ...es to operate but may switch to Bypass mode or shut down if the load increases The alarm resets when the condition becomes inactive UPS over temperature Fault Red LED is On Beep continuous Code F081 T...

Page 45: ...Transfer to maintenance bypass and call service Inv Overload Fault Fault Red LED is On Beep continuous Code F042 UPS has transferred to bypass or fault mode because of overload in inverter mode The U...

Page 46: ...ntative BUS Softstart Fail Fault Red LED is On Beep continuous Code F025 Indicates that the BUS could not soft start successfully Contact your service representative Inv Over Voltage Fault Red LED is...

Page 47: ...D is flash 1 beep every 1 second Code A0E7 Parallel system UPS1 line ok UPS2 line loss Check the line input Power strategy different Fault Red LED is flash 1 beep every 1 second Code A0E9 Parallel sys...

Page 48: ...ltage For power ratings Tower EBM Tower 192Vdc 6000 10000VA Tower EBM Tower 240Vdc 6000 10000VA Table 3 Weights and dimensions Description Weights kg Dimensions mm W x H x D Tower 6K UPS 16PCS BAT 53...

Page 49: ...76 276Vac Tower 10K 16PCS BAT 230V 49 9A 208 220 230 240V 176 276Vac Tower 10K 20PCS BAT 230V 50 9A 208 220 230 240V 176 276Vac Tower 10KS 16PCS BAT 230V 57 6A 208 220 230 240V 176 276Vac Tower 10KS 2...

Page 50: ...3 to 1 for 208V output the load level will be derating to 90 Table 7 Electrical output connections Model Output connection Output cable Tower 6K 6KS Hardwired Not provided Tower 10K 10KS Table 8 Envi...

Page 51: ...l for 6kVA models 55 dBA at 1 meter typical for 10kVA models Table 9 Battery EBMs Tower configuration 240Vdc 20 x 12V 7Ah 240Vdc 20 x 12V 9Ah 192Vdc 16 x 12V 7Ah 192Vdc 16 x 12V 9Ah Fuses 100A for 10k...

Page 52: ...ication bay for connectivity cards Compatible connectivity cards MODBUS card NMC card AS400 card Communication ports RS 232 DB9 2400 bps USB 2 0 full speed Dry out 2 pins jumper normally closed Dry in...

Page 53: ...evices or equipment connected to the UPS output HE mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user This mode reduces the...

Reviews: