background image

1

Introduction

Instruction manual—single-phase power conditioners

   IM01002005E   September 2015  Eaton.com

Introduction

1.0:   Scope

This section is a general description of the Power-Sure 

T800R/T800P/T800F power conditioners . It includes  

receiving, electrical, environmental, mechanical  

specifications, and cabinet standard dimensions .

1.1:   Section descriptions

This manual is divided into three sections:

Section 1: Introduction

This section is a general description of the Power-Sure 

T800R/T800P/T800F power conditioners . It includes  

receiving, electrical, and mechanical specifications  

and cabinet measurements .

Section 2: Installation

This section guides the user through installation  

requirements, wire and circuit diagrams, hardwire  

connections, and factory configuration ratings for the  

Power-Sure T800R/T800P/T800F .

Section 3: Maintenance

This section contains preventive maintenance for the  

Power-Sure T800R/T800P/T800F and a troubleshooting 

guide to assist the user with any communication and  

configuration connections .

1.2:   Receiving

Before accepting shipment from the freight carrier, inspect 

the exterior surfaces of all shipping containers or packaging  

used and the equipment for damage that may have 

occurred during transit . If the shipping containers or  

equipment shows evidence of damage, note the damage  

on the receiving document (bill of lading) prior to signing  

for receipt of equipment .

All claims for shipping damage must be filed directly 

with the carrier.

 Replacements for damaged components 

should be ordered through Eaton .
Check by thorough inspection if any electrical connections 

have become loose because of vibration during shipment . 

Check the nameplate to be sure that the voltage and  

frequency match the available power supply . Under no  

circumstance should the unit be connected to a power 

source that does not conform to the nameplate rating .

1.3:   Location and storage

The unit has been completely inspected and extensively 

tested under various load conditions prior to shipment .  

Installing it at a proper location will ensure long trouble-free 

operation . T800R models are forced-air cooled with the air 

intake on the sides of the enclosure . Air exhausts are at the 

rear of the enclosure . Therefore, it should be installed in a 

clean, dry place with enough clearance to allow a free flow 

of air . Allow at least four inches of space between the unit  

and the wall or other equipment for portable units . Allow 

enough space for maintenance on all four sides on larger 

units, and unrestricted air exhaust from the fan . Never 

mount T800P models one unit over the other or near  

a heat source . Heat rising into or blowing into the unit  

may cause premature failure .
If the equipment is to be stored prior to installation, it 

should be stored in a cool, dry, well-ventilated location that 

is protected from rain, splashing water, chemical agents, 

etc . The equipment should be covered with a tarpaulin or 

plastic wrapper to protect it against dust, dirt, paint, or other 

foreign materials .

1.4:   Prerequisites to installation

An efficient installation depends on careful planning and site 

preparation . Installation of the equipment must be handled 

by skilled technicians and electricians familiar with the 

special requirements of high-voltage electrical equipment . 

The installation must comply with the requirements of the 

National Electrical Code (ANSI/NFPA 70, latest issue) and 

local codes as applicable .
Startup service is offered by Eaton . Do not allow  

unqualified personnel to handle, install, or operate  

Power-Sure 800 power conditioners .

1.5:   General description

The Power-Sure 800 is a state-of-the-art ferroresonant  

isolation transformer . Its all-passive electronic design  

provides unsurpassed reliability and power conditioning  

performance . The overall function of the Power-Sure 800  

is to receive raw, extremely polluted electrical power and  

purify it for use by sensitive electronic equipment . This 

highly reliable product is ideal for heavy industrial  

applications where high power equipment constantly  

interferes with a building‘s electrical system . Use the  

Power-Sure 800 where isolated, regulated, transient,  

and noise-free sinusoidal power is required .

Ferroresonant, copper coils, dry type, convection cooled, 

600 V class, 200 ºC system .

Core uses M-6 grade, grain-oriented, stress-relieved 

transformer steel .

Transformers are vacuum impregnated with epoxy resin .

NEMA Type 1, general purpose, indoor enclosure .

Heavy gauge steel . Base substructure adequate  

for fork lifting .

Summary of Contents for T800R-00500

Page 1: ...Instruction manual single phase power conditioners Power Sure 800...

Page 2: ...ing 1 1 3 Location and storage 1 1 4 Prerequisites to installation 1 1 5 General description 1 1 6 Electrical specifications 2 1 7 Power Sure T800R T800P T800F cabinet dimensions 3 SECTION 2 INSTALLAT...

Page 3: ...VA T800R 120 Vac input and output 60 Hz 12 2 2 Wiring diagram for 1 2 5 kVA T800R 120 Vac input and output 60 Hz 12 2 3 Wiring diagram for 3 5 kVA T800R 120 Vac input and output 60 Hz 13 2 4 Wiring di...

Page 4: ...nergy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to caus...

Page 5: ...policies The sole source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton selling policy No warranties express or implied including warranties of fitness for...

Page 6: ...________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________...

Page 7: ...e sides of the enclosure Air exhausts are at the rear of the enclosure Therefore it should be installed in a clean dry place with enough clearance to allow a free flow of air Allow at least four inche...

Page 8: ...hing unity with load power factor as poor as 0 6 Meets FAA G 201e power factor specifications Harmonic attenuation 23 dB for load reflected harmonics Galvanic isolation NEC 250 5d 001pf Surge protecti...

Page 9: ...6 x 355 6 x 254 0 52 24 T800P 00750 750 750 Range 1 ac Range 3 d Hardwired Hardwired 9 00 x 14 00 x 10 00 228 6 x 355 6 x 254 0 60 27 T800P 01000 1000 1000 Range 1 ac Range 3 d Hardwired Hardwired 9...

Page 10: ...1 5 1 5 30R 120 30 S 1 1 L5 30R 120 30 F 1 1 6 15R 208 240 15 T 1 1 L6 15R 208 240 15 G 1 2 6 15R 208 240 15 U 1 2 L6 15R 208 240 15 H 1 1 6 20R 208 240 20 V 1 1 L6 20R 208 240 20 I 1 2 6 20R 208 240...

Page 11: ...anual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 3 Cabinet standard dimensions for 1 3 5 kVA Power Sure T800R models Figure 1 4 Cabinet standard dimensions for 5 15...

Page 12: ...6 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 5 Cabinet dimensions T800P wall panel mounted unit 500 1000 VA...

Page 13: ...7 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 6 Cabinet dimensions T800P wall panel mounted unit 1500 3000 VA...

Page 14: ...8 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 7 Cabinet dimensions T800P wall panel mounted unit 5000 10 000 VA...

Page 15: ...9 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 8 Cabinet dimensions T800F floor mounted unit 5000 10 000 VA...

Page 16: ...10 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 9 Cabinet dimensions T800F floor mounted unit 15 000 25 000 VA...

Page 17: ...nd output field wiring connections are made to the correct terminal blocks as shown for the specific model being installed See Figures 2 5 page 14 2 6 page 15 2 7 page 16 or 2 8 page 17 depending on t...

Page 18: ...le phase power conditioners IM01002005E September 2015 Eaton com 2 3 Wiring diagrams Figure 2 1 Wiring diagram for 500 850 VA T800R 120 Vac input and output 60 Hz Figure 2 2 Wiring diagram for 1 2 5 k...

Page 19: ...Vac load currents X1 N or X2 N should not exceed 50 of the unit s rated power 120 Vac Neither duplex receptacle should be loaded more than 14 5 A Figure 2 4 Wiring diagram for 3 5 kVA T800R 208 240 Va...

Page 20: ...14 Installation Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 2 5 Wiring diagram for 5 7 5 kVA T800R 208 240 Vac input and 120 208 240 Vac output 60 Hz...

Page 21: ...15 Installation Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 2 6 Wiring diagram 10 15 kVA T800R models...

Page 22: ...2015 Eaton com Figure 2 7 Wiring diagram 500 VA 5 kVA T800P T800F models Terminals 500 2500 VA 8 stud Maximum wire size 10 AWG Recommended torque 15 lb in 3000 VA 10 stud Maximum wire size 6 AWG Recom...

Page 23: ...IM01002005E September 2015 Eaton com Figure 2 8 Wiring diagram 8 25 kVA T800P T800F models Terminals Wire size range 12 1 0 AWG Recommended torque 45 50 lb in Note Full kVA ratings may be used at 120...

Page 24: ...7 A 1 kVA T800P 01000 9 2 A 5 3 A 4 6 A 2 3 A 1 5 kVA T800P 01500 13 7 A 7 9 A 6 8 A 3 4 A 2 kVA T800P 02000 18 3 A 10 5 A 9 2 A 4 6 A 3 kVA T800P 03000 27 5 A 15 8 A 13 7 A 6 9 A 5 kVA T800a 05000 45...

Page 25: ...Input volts and amps specifications 8 25 kVA Power rating Model 208 V 240 V 480 V 8 kVA T800 a 08000 42 A 37 A 18 A 10 kVA T800 a 10000 53 A 46 A 23 A 15 kVA T800F 15000 80 A 70 A 34 A 20 kVA T800F 2...

Page 26: ...three main component types in the Power Sure T800R T800P T800F power conditioners transformer capacitors and cooling fans 1 Transformers The transformer is designed with a considerable safety margin N...

Page 27: ...___________________________________________ _____________________________________________________ _____________________________________________________ ________________________________________________...

Page 28: ...g a world that demands more With over 100 years experience in electrical power management we have the expertise to see beyond today From ground breaking products to turnkey design and engineering serv...

Reviews: