background image

GND terminals 3, 7 and 13 are internally connected.

Terminal

Signal

Description

1

+10V

ref

Reference Output

Potentiometer Voltage, etc.

V

in

+

I

in

+

I

out

+

I

out

–

Analog Input Current

(range 0-20mA)

Analog Input Voltage

(range = 0-10V DC)

Frequency reference activated when

terminals 14

&

15 are open and

parameter 1.17 = 0 (default value)

3

4

I

in

–

5

GND

I/O Ground

Reference and Control GND
Frequency reference activated when

terminals 14

&

15 are closed – or –

If parameter 1.17 = 1, when terminals

14

&

15 are open.

6

+24V

Control Voltage Output¿

Switch Voltage, etc. (0.1A max.)

7

GND

I/O Ground

Reference and Control Ground

8

DIA1

Start Forward

(programmable in STANDARD)

9

DIA2

10

DIA3

Start Reverse

(programmable in STANDARD)

Start Reverse

(programmable in STANDARD)

Contact Closed = Start Reverse

Contact Closed = Start Forward

Contact Open = No Fault

Contact Closed = Fault

11

CMA

D1A1-D1A3 Common
Control Voltage Output

+24V
GND

DIB4

DIB5

Multi-Step Speed Select 1

Multi-Step Speed Select 2

I/O Ground

Connect to GND or +24V

12

Switch Voltage, etc. (0.1A max.)

13

Reference and Control Ground

Contact Open = No Action

Contact Closed = Fault Reset

14

15

open

closed

open

closed

D1B4

D1B5

Freq. Ref

open

open

closed

closed

Ref. V

in

(parameter 1.17=0)

Multi-Step Ref. 1
Multi-Step Ref. 2
Ref. I

in

(Terms. 4

&

5)

16

DIB6

Fault Reset

17

CMB

Common

Connect to GND or +24V

18

Output Frequency

Analog Output

Programmable in STANDARD (parameter 3.1)

(range 0-20mA/R

L

max. 500Ohm)

19

20

D01

Digital Output

READY

Programmable in STANDARD (parameter 3.6)

Open Collector (I

50mA, V

48V DC)

21

R01

Relay Output 1

RUN

Programmable in STANDARD (parameter 3.8)

Programmable in STANDARD (parameter 3.7)

22

R01

23

R01

24

R02

25

R02

26

R02

READY

FAULT

(50mA)

220V AC

Max.

2

Relay Output 2

FAULT

Connect CMA/CMB inputs to either logic high or logic low depending upon your application. Refer

to the SV9000 User Manual and SVReady Application Manual for additional information.

Reference Potentiometer

1-10 k

1

1

2

2

3

1

3

3

For the STANDARD Application, input signals at D1A1 and D1A2 are programmed as a pair using parameter 2.1.

2

1

Use the 

LEFT

 and 

RIGHT MENU

 buttons to enter the desired menu, then the 

UP

 and 

DOWN BROWSER

 button to access the desired 

item.

QUICK REFERENCE GUIDE

Shipped from the factory, the SV9000 drive has (7) SVReady 
Applications, with the drive’s default set to 

BASIC Application

. This 

guide is based on the use of the 

BASIC

 or 

STANDARD

 

Application

 

outlined in the User Manual and SVReady Application Manual.
For the 

BASIC Application

 – 

Control I/O signals are fixed and not programmable.
For the 

STANDARD Application

 – 

DIA1-DIA3, Control I/O signals as well as output signals R01-R02 are 
programmable. 
Other applications have different terminal block assignments and 
different parameter numbers or functions. These may be selected from 
System Parameter Group 0, parameter P0.1. Refer to the SV9000 User 
Manual for detailed information.

1

SVMulti-line™ CONTROL PANEL OPERATION

2

START-UP and I/O CONNECTIONS

• Go to menu screen M4.
• Press the 

UP/DOWN BROWSER

 button to go to application 

screen B2.

• Press the 

ENTER

 button to switch from remote control to panel 

control.

• Press the 

START

 button to start the drive.

• Go to menu screen M3.
• Press the 

RIGHT MENU

 button until R1 starts to blink.

• Press the 

UP BROWSER

 button to the desired motor frequency.

• Go to menu screen M1 and view the output motor frequency.

3

SCREEN DISPLAYS

Important:

 This guide is intended to provide a quick reference to 

the SV9000’s BASIC and STANDARD features for startup, 
programming and service. It does not replace the need to thoroughly 
read and understand the User Manual and SVReady™ Application 
Manual.

RUN lights when the motor is running.

shows the selected motor rotation.

STOP lights when the motor is not running.

READY lights when input voltage is present and the drive is ready.

FAULT lights when a drive fault occurs.

PANEL/REMOTE shows the active control source.

LEFT MENU moves forward in the menu.

RIGHT MENU moves backward in the menu.

RESET resets drive faults.

START starts the motor when the panel is the

current control source.

STOP stops the motor when the panel is the

current control source.

ENTER acknowledges changed values,

resets fault history, and is pressed to enter program

settings.

DOWN BROWSER

UP BROWSER

ENTER

RESET

UP

DOWN

•

Moves in the main menu.

•

Moves between pages inside the same submenu.

•

Changes values.

STOP

START

M2

Parameter
G 1-12

M1

Monitor
V 1-20

M3

Reference
R1

M4

Buttons
B 1-4

M5

Active Faults
F 1-9

M6

Fault History
F 1-9

M7

Contrast
15

Fault History Reset

G2 

Special Param.

G12

Scroll the Active Fault List

V2 Motor Speed
V3 Motor Current

V20 MotorTemp. Rise

G1

Basic Param.
P 1-15

R1

Freq. Reference
58.5 Hz

V1

Output Frequency
58.5 Hz

P1.1

Min. Frequency
12.34 Hz

P1.2

P12.x

P1.1

Min. Frequency
12.34 Hz

B2 Panel Control

B1

Reverse
1

B1

Reverse
0

R1

Freq. Reference
58.5 Hz

F1

1. Overcurrent

H1

2. Overvoltage

C1

Contrast
15

MENU SCREENS

SUB-MENU SCREENS

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

UP

DOWN

ENTER

ENTER

ENTER

Shipped from the factory the SV9000 is set to run forward from a contact closure at input DIA1, and to run in reverse from a contact closure at input 
DIA2. To Run from a Keypad Setting –

Reviews: