Eaton SPD Series for Mounting External

to Electrical Distribution Equipment

Instruction Manual 

IM01005031E - Rev. 6

7.  Determine the wire length for the Ground and Neutral (where 

applicable) wires and cut these wires as needed. Again, keep 

these wires as short as possible to maximize SPD perfor-

mance.

8.  Standard and Standard with Surge Counter SPDs also provide 

wiring for Form C relay contacts. This connection can be used 

for remote monitoring of the SPD. The Form C contacts are 

rated at 150V AC or 125V DC at 1A. Make the remote moni-

toring connections per the Form C wiring diagram in Figure 8 

Follow all national, state and local electrical codes when mak-

ing these connections.

Figure 2. NEMA 1 (With Flushmount) (Suffix L)

4

IM01005031E

 Rev. 2

 

Effective November

 20

12

Eaton SPD Series

For Mounting External To

Electrical Distribution Equipment  

eaton corporation

 www.eaton.com

Determine the wire length for the Ground and Neutral   

7. 

(where applicable) wires and cut these wires as needed.   

Again, keep these wires as short as possible to maximize   

SPD performance.

Standard and Standard with Surge Counter SPDs also pro-

8. 

vide wiring for Form C relay contacts. This connection can be 

used for remote monitoring of the SPD. The Form C contacts are 

rated at 150V AC or 125V DC at 1A. Make the remote monitoring 

connections per the Form C wiring diagram in Figure 7. Follow 

all national, state and local electrical codes when making   

these connections.

NEMA 1 (With Flushmount) (Suffix L)

Figure 2. 

Summary of Contents for SPD050208Y1K

Page 1: ...Distribution Equipment Instruction Manual IM01005031E Effective November 2012 Rev 2 Table of Contents 1 0 Introduction 2 0 Installation 3 0 Operating Features 4 0 Troubleshooting 5 0 Specifications 6...

Page 2: ...nd are intended to be installed in applications with a degree of protection rated IP 20 1 3 Safety Precautions A licensed qualified electrician must complete all instructions in this manual in accorda...

Page 3: ...eck the facility grounding system All grounding bonding and earthing must meet the NEC and any other national state and local electrical codes 2 2 Installation Locations Eaton s SPD Series can be inst...

Page 4: ...tate and local electrical codes when mak ing these connections Figure 2 NEMA 1 With Flushmount Suffix L 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical...

Page 5: ...K Figure 4 NEMA 4 4X Suffix N P 5 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 Suffix K...

Page 6: ...v 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect Suffix M Figure 5 NEMA 4 4X With Disconne...

Page 7: ...al IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 7 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Figure 7 Flush Mount Plate For 50 200 kA Units In A NEMA 1...

Page 8: ...on Equipment Instruction Manual IM01005031E Rev 6 BLUE WHITE RED WHITE ORANGE WHITE COMMON NORMALLY OPEN NORMALLY CLOSED Figure 8 Sidemount Form C Wires Figure 9 Split Phase Units Figure 10 3 Phase De...

Page 9: ...t for each feature package Each display has both green and red light emitting diodes LEDs to indicate the status of the protection on each phase Green indicates the phase is fully protected Red indica...

Page 10: ...the display 3 Remove the two phillips head screws that hold the display 4 Rotate the display to the desired position Be careful not to overstress the display ribbon cable 5 Place the display back onto...

Page 11: ...Significant surge event Replace SPD Replace SPD with correct voltage model Check electrical system for TOV sources correct replace SPD Replace SPD One of the display Red LEDs is ON Audible Alarm is O...

Page 12: ...nd 480D Basic voltage codes 600Y and 600D voltage codes 0 6W 1 7W 2 1W Protection modes Single split phase L N L G N G L L Single phase L N L G N G Three phase delta L G L L Three phase Wye L N L G N...

Page 13: ...te Protection Status of the N G Mode on units with a Neutral Wire Audible alarm with Silence button Form C Relay Contact EMI RFI filtering Providing up to 50dB of Noise Attenuation from 10kHz to 100Mh...

Page 14: ...thin said term determined by Eaton to be defec tive The giving of or failure to give any advice or recommenda tions by Eaton shall not constitute any warranty by or impose any liability upon Eaton The...

Page 15: ...Instruction Manual IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 15 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Notes...

Page 16: ...nd conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLU...

Reviews: