3.2.2 Standard Feature Package 

The Eaton SPD Series Standard Feature Package display is 

shown in Figure 16

Figure 16. Standard Feature Package Display

The Standard Feature Package has the following features:

• 

All features of the Basic Feature Package.

• 

One Form C relay contact rated at 150Vac or 125Vdc @1A.

• 

Normal operating conditions. N.O. = OPEN. N.C = 

CLOSED.

• 

Loss of protection on any phase or loss of power. N.O. = 

CLOSED. N.C. = OPEN.

• 

Audible alarm with Reset push button.

• 

EMI/RFI filtering. 

3.2.3 Standard With Surge Counter Feature Package

The Eaton SPD Series Standard With Surge Counter Feature 

Package display is shown in Figure 17. 

Figure 17. Standard With Surge Counter Feature Package 

Display

The Standard With Surge Counter Feature Package has the fol-

lowing features:

• 

All features of the Standard Feature Package. 

• 

LCD screen that displays surge count. 

• 

Reset button to RESET the surge counter to zero.

3.2.4 SPD Display Rotation

The SPD display can be rotated on the SPD enclosure, up to 360 

degrees. This allows you to position the display for the best vis-

ibility regardless of the position in which the SPD is installed.  
Rotations are at 90, 180, and 270 degrees. 
Reposition the SPD display as follows:

1.  Remove power from the unit. 
2.  Remove and discard the perforated overlay material at the  

  two opposite corners of the display. 
3.  Remove the two phillips head screws that hold the display.
4.  Rotate the display to the desired position. Be careful not to  

  overstress the display ribbon cable.
5.  Place the display back onto the SPD enclosure. Again, be  

  careful not to overstress or crimp the ribbon cable. 
6.  Replace the two phillips head screws. Tighten screws to  

  1.35 Nm (12 in-lbs).
7.  Restore power to the unit. 

3.3 IEC Approved Models

Eaton’s One-Port low-voltage Surge Protective Device Delta 

Models SPD120480D3M, SPD160480D3M and SPD200480D3M 

meet the requirements of IEC 61643-11 / EN 61643-11, Part 11: 

Test Class II, and are intended to be installed in applications with 

a degree of protection rated IP 20.
The Delta Models are intended for use with a 3 Phase TN-S 

System with PE and Neutral Distribution, 5 conductor with a 

minimum 10 AWG or 6 mm2.  The Delta models are also intend-

ed for use with a 3 Phase TN-C System with PEN Distribution, 

4 conductor with a minimum 10 AWG or 6 mm2.  Screws used 

for connection to ground shall be #10-32 x 3/8” and shall not be 

zinc or aluminum.  This product is not serviceable and contains 

no replacement parts.
Additional product information and ratings for IEC Applications:

• 

The SPD contains internal disconnects with a short circuit cur-

rent rating I

SCCR

 of 200kA.

• 

Residual Current IPE for this product is 5 mA.

• 

Operating temperature is Normal -5°C to 40°C (23°F to 

104°F).

• 

Humidity range is 5% through 95% non-condensing.

• 

The SPD may be mounted directly to earthed conductive sur-

face, installed as per this manual.

• 

Temporary overvoltage rating UT = 402.6V.

• 

Withstand or safe failure mode, t

T

 = 120 minutes, U

T

 = 526V.

• 

Modes of protection as marked on a Delta SPD = L - L,  

L -G(PE).

Summary of Contents for SPD050208Y1K

Page 1: ...Distribution Equipment Instruction Manual IM01005031E Effective November 2012 Rev 2 Table of Contents 1 0 Introduction 2 0 Installation 3 0 Operating Features 4 0 Troubleshooting 5 0 Specifications 6...

Page 2: ...nd are intended to be installed in applications with a degree of protection rated IP 20 1 3 Safety Precautions A licensed qualified electrician must complete all instructions in this manual in accorda...

Page 3: ...eck the facility grounding system All grounding bonding and earthing must meet the NEC and any other national state and local electrical codes 2 2 Installation Locations Eaton s SPD Series can be inst...

Page 4: ...tate and local electrical codes when mak ing these connections Figure 2 NEMA 1 With Flushmount Suffix L 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical...

Page 5: ...K Figure 4 NEMA 4 4X Suffix N P 5 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 Suffix K...

Page 6: ...v 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect Suffix M Figure 5 NEMA 4 4X With Disconne...

Page 7: ...al IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 7 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Figure 7 Flush Mount Plate For 50 200 kA Units In A NEMA 1...

Page 8: ...on Equipment Instruction Manual IM01005031E Rev 6 BLUE WHITE RED WHITE ORANGE WHITE COMMON NORMALLY OPEN NORMALLY CLOSED Figure 8 Sidemount Form C Wires Figure 9 Split Phase Units Figure 10 3 Phase De...

Page 9: ...t for each feature package Each display has both green and red light emitting diodes LEDs to indicate the status of the protection on each phase Green indicates the phase is fully protected Red indica...

Page 10: ...the display 3 Remove the two phillips head screws that hold the display 4 Rotate the display to the desired position Be careful not to overstress the display ribbon cable 5 Place the display back onto...

Page 11: ...Significant surge event Replace SPD Replace SPD with correct voltage model Check electrical system for TOV sources correct replace SPD Replace SPD One of the display Red LEDs is ON Audible Alarm is O...

Page 12: ...nd 480D Basic voltage codes 600Y and 600D voltage codes 0 6W 1 7W 2 1W Protection modes Single split phase L N L G N G L L Single phase L N L G N G Three phase delta L G L L Three phase Wye L N L G N...

Page 13: ...te Protection Status of the N G Mode on units with a Neutral Wire Audible alarm with Silence button Form C Relay Contact EMI RFI filtering Providing up to 50dB of Noise Attenuation from 10kHz to 100Mh...

Page 14: ...thin said term determined by Eaton to be defec tive The giving of or failure to give any advice or recommenda tions by Eaton shall not constitute any warranty by or impose any liability upon Eaton The...

Page 15: ...Instruction Manual IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 15 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Notes...

Page 16: ...nd conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLU...

Reviews: