Effective January 2019
12
Eaton
Eaton SPD Series for Mounting External
to Electrical Distribution Equipment
Instruction Manual
IM01005031E - Rev. 6
Description
Specification
Surge current capacity per phase
50, 80, 100, 120, 160, 200, 250, 300, 400 kA ratings available
Nominal discharge current (I
n
)
20kA
Short circuit current rating (SCCR)
200kA
SPD Type
Basic feature package = Type 1 (can also be used in Type 2 applications)
Standard and Standard with Surge Counter feature packages = Type 2
Enclosure Types
NEMA 1, NEMA 4, NEMA 4X (304 SST)
Standard split phase voltages available
120/240
Single phase
230
Three phase wye system voltages available
120/208, 127/220, 230/400, 277/480, 347/600
Three phase delta system voltages
240, 480, 600
Three phase high leg delta system voltages
120/240
Phase wire length
48” of 10AWG extend beyond the conduit hub
Relay wire length (optional)
48” of 14AWG extend beyond the conduit hub
RoHS Compliant
Yes
Internal Disconnect (optional)
Eaton 30 Amp FDC Circuit Breaker, Type MCCB
Input Power Frequency
50/60 Hz
Power consumption (Basic units)
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes
400Y and 480Y and 480D voltage codes
600Y and 600D voltage codes
0.5W
1.1W
1.3W
Power consumption (Standard and Standard with Surge Counter units)
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes
400Y, 480Y, and 480D Basic voltage codes
600Y and 600D voltage codes
0.6W
1.7W
2.1W
Protection modes
Single split phase ...L-N, L-G, N-G, L-L Single phase... L-N, L-G, N-G Three phase delta...L-G, L-L
Three phase Wye.....L-N, L-G, N-G, L-L Three phase high leg delta....L-N, L-G, N-G, L-L
Maximum continuous operating voltage (MCOV)
208Y, 220Y, 240S, 240D, and 240H voltage codes
150 L-N,150 L-G, 150 N-G, 300 L-L
230L, 400Y and 480Y voltage codes
320 L-N, 320 L-G, 320 N-G, 640 L-L
600Y voltage code
420 L-N, 420 L-G, 420 N-G, 840 L-L
240 D voltage code
320 L-G, 320 L-L
480 D voltage code
640L- L-G, 640 L-L
600D voltage code
840 L-G, 840 L-L
Ports
1
Operating temperature
-40F to 122F (-40C to 50C)
Operating humidity
5% through 95%, non-condensing
Weight
Reference Figures 2, 3, 4, 5, and 6 on pages 4, 5 and 6
Form C relay contact ratings
150 Vac or 125 Vdc, 1A maximum
Form C relay contact loogic
Power on, normal state - NO contact = OPEN, NC contact = CLOSED
Power off, fault state, - NO contact = CLOSED, NC contact = OPEN
EMI/RFI filtering attenuation (Standard and Standard With Surge Counter
Up to 50 dB from 10 kHz to 100 MHz
Agency certifications and approvals
UL1449 4th Edition listed, CSA (excludes 230L voltage code), UL1283 7th Edition (Type 2 SPDs only)
IEC 61643-11/EN 61643-11, Part 11: Test Class II. See Section 6.0 Ordering Guidelines for specific models.
Warranty
10 Years, 15 Years if you register on www.eaton.com/spd and click the warranty registration icon.
ROHS Compliant
Yes
Wire Length and AWG
Factory prewired with 48 inches of 10 AWG wire.
5.0 Specifications
Table 3. Specifications