Common Alarm Parameters
The following parameters are common to multiple alarms.
Parameter
Description
Where to find:
Enable Audible
Alarm Indication
Enable or disable the audible alarm indicator.
SC200: Alarms > Alarm
Settings > Global Settings
DCTools/Web: Alarms >
Alarm Configuration
Alarm Recognition
Period
All alarms (except those listed below) are
activated only after the alarm condition is
present for this period.
These alarms have individual recognition
periods: AC Fail, System Overload,
Generator Fail.
These alarms do not have recognition
periods: Battery Test Fail, Configuration
Error, Missing Hardware, Standby
Mode, String Fail, Unknown Hardware,
Unmapped IOB Found, and all LVD
alarms.