Eaton - Lighting Systems iLight Product Series - RI-2 73-897-00 IM8791 Iss 5 5
Earth
Neutral
Live
N
L
Mounting
Location and spacing
The RI-2 Interface should be installed in a dry
ventilated location, where ambient conditions
are maintained within the requirements of the
unit.
The unit has ventilation slots on its sides
to allow convection cooling and under no
circumstances should these be blocked.
Allow 50mm above and below the unit if
trunking with a depth greater than 50mm is
used.
Mounting Holes
The unit is provided with four 1/4in (6mm)
diameter fixing holes for wall mounting.
The mounting holes can be accessed by
undoing the four screws on the front cover and
removing it.
Supply Wiring
Connecting the Supply
This unit requires a nominal 240V single phase
supply (Live, Neutral, and Earth) with 1A
capability.
Keep the supply wiring segregated from the
relay connector cabling.
Ensure all supply connections are fully
tightened.
A knockout, suitable for a 3/4” (19mm) cable
gland, is provided for the supply entry point.
Wire Gauge for Supply Terminals
Terminals suitable for wire sizes from 22AWG
(0.34mm2) to 12AWG (4mm
2
).