5
Technical Data
TD150019EN
Effective January 2017
PXM4/6/8K Meter Advanced Color
Touchscreen Display Quick Start Guide
EATON www.eaton.com
Connection with Multiple Meters
Figure 15. Meter Web Server Configuration Screen Com 1 & 2
Setup.
In order to communicate with multiple meters, the primary meter
must be configured as Master Gateway. Any additional meters must
be configured as Slave Gateway. This can be set using the meter’s
web server configuration page for Com 1 & 2.
Additional (slave) meters can be connected to the display by daisy-
chaining the RS 485 ports between meters. This configuration also
requires that each meter in the chain have a unique base address.
This can be set with the rotary switch located on the bottom left
side of the meter. Please reference the PXM4000/6000/8000 User
and Installation Manual for full details.
Remote access to Ethernet enabled features for 4/6/8K requires LAN
connection to PXMCE-B.
Meter Firmware Requirements
The minimum meter firmware version required for compatibility is
13.3.6.5.
Technical Information
•
1024 x 768 pixel backlit LCD graphic touch screen display.
•
Power: 9–36 Vdc input.
•
Recommended power supplies: PSG60E (85-264 Vac input);
PSG60F (320-575 Vac input).
Display Measurements
•
Height: 9.65 in. (245 mm);
•
Width: 12.56 in. (319 mm);
•
Depth: 2.00 in. (52 mm);
•
Shipping weight: 2.1 lb (2.5 kg);
•
Cutout dimensions: 11.90 x 9.00 in. (303 x 229 mm).
Ratings
•
Front Bezel IP Rating: IP65;
•
Operating Temperature: 0 ~ 50° C (32 ~ 122° F);
•
Storage Temperature: -20 ~ 60° C (-4 ~ 140° F);
•
Storage Humidity: 10%~90%, non-condensing.