86-87050-00 A02 - Page 24
3.5 Return to Normal AC Source
After an outage, the UPS restarts automatically when Normal AC source is restored (unless this function has been
disabled via UPS personalization) and the load is supplied again.
3.6 UPS Shutdown When AC Present
Before shutdown, please read ALL instructions below:
3.7 UPS Shutdown When on Battery
Before shutdown, please read ALL instructions below:
1. Press and hold the «0” (off) button
(28)
for 3
seconds. The buzzer beeps once.
2. The display asks for confirmation.
3. Press the scroll button
(25)
to select yes.
4. Press confirm button
(27)
.
The UPS is now fully shut down.
1. Press and hold the «0” (off) button
(28)
for 3
seconds. The buzzer beeps once.
The load is no longer protected by the UPS.
It is
powered via the Normal AC source (bypass).
If
the UPS is set in frequency converter mode, the
equipment will not be powered.
If the Normal AC
source is out of tolerance, the UPS will generate a
10ms output calibrated break.
LEDs
(22)
is ON, LEDs
(33)
and
(34)
are green.
For a full shutdown of UPS and connected load, the
upstream circuit breaker (not included) should be set
to the off position or remove the Normal AC source.
25
28
27
NO
YES
33
34
28
22
ON AUTO BYPASS
3. Operation
Summary of Contents for Pulsar EX RT 5000
Page 2: ......
Page 4: ......
Page 10: ...86 87050 00 A02 Page 8 This page left blank intentionally...
Page 30: ...86 87050 00 A02 Page 28 This page left blank intentionally...
Page 34: ...86 87050 00 A02 Page 32 This page left blank intentionally...
Page 36: ...86 87050 00 A02 Page 34...
Page 38: ...86 87050 00 A02 Page 36...
Page 40: ...86 87050 00 A02 Page 38...
Page 42: ...Notes 86 87050 00 A02 Page 40...
Page 43: ...86 87050 00 A02...
Page 44: ...www eaton com 86 87050 00 A02...