2. Installation
86-87050-00 A02 - Page 17
2.5 Communication Ports
MX RT
provides 4 communication methods.
1. The RS232 port provides communications using EATON Serial HID UPS transfer (SHUT) protocol. The SHUT
protocol is compatible with the power management applications available on the enclosed Solution-Pac 2
CD-Rom.
2. The Output contacts port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly
AS400) and more.
3. The USB port is compatible with the power management applications available on the enclosed Solution-Pac
2 CD-Rom.
4. The slot is compatible with the optional 66102 — Network Management Card (NMC) 2006 Edition and the
66103-Status Card.
Note
All communications options can be used simultaneously except for the SHUT RS232 and USB port. If both
the USB and SHUT ports are connected then the USB takes control.
Connection to the RS232 or USB communication port (42)
1 Connect the RS232 (42) or USB (44)
communication cable to the serial or USB
port on the computer equipment.
2. Connect the other end of the RS232 cable
(42) to the RS232 (7) communication port or
the USB cable (not included) to the USB port
(6) on the UPS.
The UPS can now communicate with various
EATON power management application
software.
Please note that Personal Solution-Pac can
be used to configure (personalize) the UPS
parameters such as voltage, frequency,
battery test, etc. See section 4.6 for more
details.
Connection to the communication port by relays (8)
8
w
Pin 1, 2: not used,
w
Pin 3: Remote Power Off signal (5 to 27 V DC,
10 m A max),
w
Pin 4: Operation on mains (not on battery),
w
Pin 5: User common,
w
Pin 6: Operation on automatic by-pass,
w
Pin 7: Low battery,
w
Pin 8: Load protected,
w
Pin 9: Operation on battery.
n.o: contact normally open.
n.c: contact normally closed.
When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.
Output relays specifications:
w
Voltage: 48 V DC max,
w
Current: 2 A max,
w
Power: 62.5 VA, 30 W.
Example: for 48 V DC, Imax=625 mA
Summary of Contents for Pulsar EX RT 5000
Page 2: ......
Page 4: ......
Page 10: ...86 87050 00 A02 Page 8 This page left blank intentionally...
Page 30: ...86 87050 00 A02 Page 28 This page left blank intentionally...
Page 34: ...86 87050 00 A02 Page 32 This page left blank intentionally...
Page 36: ...86 87050 00 A02 Page 34...
Page 38: ...86 87050 00 A02 Page 36...
Page 40: ...86 87050 00 A02 Page 38...
Page 42: ...Notes 86 87050 00 A02 Page 40...
Page 43: ...86 87050 00 A02...
Page 44: ...www eaton com 86 87050 00 A02...