9 Accessory devices
9.8 DIL…mains contactors
156
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
9.8 DIL…mains contactors
Table 46: Assigned mains contactors
→
The mains contactors listed here are based on the DE1 variable
speed starter's rated input-side mains current I
LN
without a
mains choke. They need to be selected based on the thermal
current
→
I
th
= I
e
(AC-1) at the specified ambient temperature.
NOTICE
The inching operation is not permissible via the mains contactor
(Pause time
≧
30 s between switching off and on).
figure 91: Mains contactor at single-phase
connection
DILM12-XP1
P1DILEM
DILM
DILEM
DILM12-XP1
P1DILEM
2
3
5
4
6
A1
A2
1
13
14
Device Type
Rated operational
current
Input current
1)
mains contactor
I
e
I
LN
AC-1 to 55
°
C
AC-1 to 60
°
C
A
A
Part no.
Part no.
DE1-121D4…
1.4
3.6
DILEM-…+P1DILEM
DILM7-…+DILM12-XP1
DE1-122D3…
2.3
6.2
DILEM-…+P1DILEM
DILM7-…+DILM12-XP1
DE1-122D7…
2.7
7.3
DILEM-…+P1DILEM
DILM7-…+DILM12-XP1
DE1-124D3…
4.3
11.3
DILEM-…+P1DILEM
DILM7-…+DILM12-XP1
DE1-127D0…
7
17.4
DILEM-…+P1DILEM
DILM7-…+DILM12-XP1
DE1-129D6…
9.6
23.2
DILM7-…+DILM12-XP1
DILM7-…+DILM12-XP1
DE1-341D3…
1.3
1.7
DILEM-…
DILM7-…
DE1-342D1…
2.1
3.1
DILEM-…
DILM7-…
DE1-343D6…
3.6
4.9
DILEM-…
DILM7-…
DE1-345D0…
5
7
DILEM-…
DILM7-…
DE1-346D6…
6.6
8.5
DILEM-…
DILM7-…
DE1-348D5…
8.5
10
DILEM-…
DILM7-…
DE1-34011…
11
12
DILEM-…
DILM7-…
DE1-34016…
16
16.5
DILEM-…
DILM7-…
1) Phase current on mains side (without mains choke)
Technical data on the mains contactors can be found in the main catalog HPL, Contactors DILEM and DILM 7.