6 Parameters
6.5 Parameter description
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
101
6.5.6.1 Control terminal and keypad
When the device is used together with an optional external keypad
(DXE-KEY-LED), the START and STOP buttons can be used to start and stop
the drive, and the speed and frequency reference value can be adjusted with
the two arrow keys.
figure 70: DX-KEY-LED optional keypad
P-12 = 1 (one operating direction)
Pressing the START button will start the drive in the operating direction
specified using control terminals DI1 (FWD) and DI2 (REV).
P-12 = 2 (two operating directions)
Pressing the START button will start the drive in the operating direction
specified using control terminals DI1 (FWD) and DI2 (REV). Pressing the
START button again will automatically reverse the operating direction.
→
In default the digital frequency reference value set with the
keypad will not be stored. It will be automatically reset to zero
with every stop command.
reference value reset mode”, page 105
figure 69: Optional DX-KEY-LED keypad and control terminals with P-15 = 0
(default setting, mode 0)
FF1
REV
FWD
0 V
4
3
2
1
+10 V