8 Technical Data
8.3 Rating data
138
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
Power section
Rated operation
current
I
e
A
6.6
8.5
11
16
Overload current,
1.5 x I
e
, cyclically for
60 s every 600 s
I
2-150
A
9.9
12.75
16.5
24
Overload current,
max. 2 x I
e
every
600 s
I
2max
A
13.2
17
22
32
Output voltage at U
e
U
2
V
400/480, 3-phase
400/480, 3-phase
400/480, 3-phase
400/480, 3-phase
Output Frequency
f2
Hz
0 - 50/60
(max.300)
0 - 50/60
(max. 300)
0 - 50/60
(max. 300)
0 - 50/60
(max. 300)
Frequency resolution
(reference value)
Δ
f
%
0.025
0.025
0.025
0.025
Pulse frequency
(audible)
f
PWM
kHz
16 (10/12/14/16/
18/20)
16 (10/12/14/16/
18/20)
16 (10/12/14/16/
18/20)
16 (10/12/14/16/
18/20)
Derating between 50 °C
and 60 °C
None
None
• None if
f
PWM
≦
16 kHz
• None if
I
e
≦
10.6 A and
f
PWM
≦
20 kHz
• None up to a
max. of 57 °C
• None if
f
PWM
≦
14 kHz
up to a max. of
50 °C
• None if
f
PWM
≦
16 kHz
up to a max. of
46 °C
• None if
I
e
≦
14.9 A and
f
PWM
≦
10 kHz
• None if
I
e
≦
10.6 A and
f
PWM
≦
20 kHz
Max. leakage current to
earth (PE)
I
PE
mA
< 3.5 AC/< 10 DC
< 3.5 AC/< 10 DC
< 3.5 AC/< 10 DC
< 3.5 AC/< 10 DC
DC braking
0 - 100 % U
e
, 0 - 10 s, parameterizable
Heat dissipation
Speed/torque
100/100
P
v
W
90
120
159
240
90/100
P
v
W
87
116
154
233
100/50
P
v
W
51
73
82
143
90/100
P
v
W
50
71
89
138
50/100
P
v
W
80
93
136
218
50/50
P
v
W
50
70
67
147
50/25
P
v
W
48
52
64
86
0/100
P
v
W
79
93
129
190
0/50
P
v
W
41
58
74
121
0/25
P
v
W
38
48
60
81
Symbol
Unit
DE1-346D6…
DE1-348D5…
DE1-34011…
DE1-34016…