5 Technical data
5.1 General rated data
DB1 variable frequency drive
11/20 MN040031EN
Eaton.com
87
5 Technical data
5.1 General rated data
Technical data
Symbol
Unit
Value
General
Standards
General requirements: EN 61800-2
EMC: EN 61800-3:
Safety: EN 61800-5-1
Certifications and manufacturer's declarations on conformity
CE, UL, cUL
Production quality
RoHS, ISO 9001
Climate resistance
ρ
w
%
< 95 %, mean relative humidity (RH),
non-condensing, non-corrosive,
no dripping water (EN 61800-2)
Ambient temperature range
Operation
ϑ
°C
-10 – +60 – depending on the cooling system
Storage
ϑ
°C
-40 - +60 (frost-free and condensation-free)
Vibration level (not evaluated during operation)
Shock test
Pulse shape
Half sine
Peak acceleration
15 g
Duration
11 ms
Vibration test
Frequency range
f
Hz
10 - 150
10 - 57.55: 0.075 mm peak-peak shift
57.55 - 150: 1 g peak acceleration
Vibration measurement
1 octave/minute
Electrostatic discharge (ESD, EN 61000-4-2:2009
U
kV
±4, contact discharge
±8, air discharge
Fast transient burst (EFT/B, EN 61000-4-4: 2004)
U
kV
±1, at 5 kHz, control signal terminal
±2, at 5 kHz, motor connection terminals,
Single-phase mains connection terminals
±2, at 5 kHz, three-phase mains connection terminals