5 Technical data
5.6 Mains chokes
DB1 variable frequency drive
11/20 MN040031EN
Eaton.com
103
5.6 Mains chokes
DX-LN1-…
Figure 53: DEX-LN1… mains chokes (single-phase)
Table 19: Assigned mains chokes (single-phase)
For more information and technical data on DX-LN1...
and DX-LN3... mains chokes, please refer to installation
leaflet IL00906003Z.
Device type
Input
current
Mains choke, single-phase
(U
LN
max. 260 V +10 %, 50/60 Hz ±10 %)
I
LN
Type
I
e
Type
I
e
A
(max. 50
o
C)
A
(max. 40
o
C)
A
Voltage class: 115 V
Mains voltage: (50/60 Hz), U
LN
: 110 (-10 %) - 115 (+10 %) V
U
e
: 115 V AC, single-phase / U
2
: 400 V AC, three-phase
DB1-1D3D2FN-N2CC
11.4
DX-LN1-013
11.7
DX-LN3-016
13
Voltage class: 115 - 230 V
Mains voltage: (50/60 Hz), U
LN
: 110 (-20 %) - 230 (+10 %) V
U
e
: 115 - 230 V AC, single-phase / U
2
: 230 V AC, three-phase
DB1-1M4D3FN-N2CC-PFC
at
110 V
10.92
DX-LN1-013
11.7
DX-LN1-013
13
DB1-1M4D3FN-N2CC-PFC
at
230 V
5.1
DX-LN1-006
5.5
DX-LN1-006
6
Voltage class: 230 V
Mains voltage: (50/60 Hz) U
LN
: 200 (-10 %) - 240 (+10 %) V
U
e
: 230 V AC, single-phase / U
2
: 230 V AC, three-phase
DB1-122D3…
4.5
DX-LN1-006
5.5
DX-LN1-006
6
DB1-124D3…
9.1
DX-LN1-013
11.7
DX-LN1-013
13
DB1-127D0…
15.5
DX-LN1-018
16.4
DX-LN1-018
18
DB1-127D0FN-N2CC-PFC
8.7
DX-LN1-013
11.7
DX-LN1-009
9
a