5 Parameters
5.3 “Extended” parameter group
DB1 Variable Frequency Drives
09/17 MN040034EN
www.eaton.com
41
P-47
AI2 signal range
0
6
Configures the Analog input 2 for the selected
signal source type.
0: 0 - 10V
1: 0 - 20 mA
2: t 4 - 20 mA (Trips in case of wire breakage)
3: r 4 -20 mA (Ramps to f-fix1 (P-20) in case of wire
break)
4: t 20 - 4 mA (Trips in case of wire break)
5: r 20 - 4 mA (Ramps to f-fix1 (P-20) in case of wire
break)
6: Ptc-th (connection of a thermistor for motor
protection)
0
P-48
t-Standby
0.0 s
25.0 s
Time after which the drive changes to standby
mode (inverter output disabled) when the motor is
running at min. speed (f-min).
0: Standby Mode disabled
not equal to zero: The device will switch to standby
mode after the time specified here.
Operation automatically resumes as soon as the
speed set point increases above P-02.
0.0 s
P-49
PID1 WakeUpLevel
0.00%
100.00%
Wake-up level controller 1
Sets an error level (difference between the PID
reference and feedback values) above which the
PID controller will wake from Standby mode.
Sets an error level (difference between PI set point
and feedback values) above which the PI controller
will wake from standby mode.
0.00%
P-50
CAN0 Baudrate
0
3
CANopen
Baudrate
Sets the Baudrate in case CANopen is used
0: 125 kbit/s
1: 250 kbit/s
2: 500 kbit/s
3: 1MBit/s
4: 50 kbit/s
5: 20 kbit/s
2
P-51
T-Memory Enable
0
1
If this function is enabled, the computed thermal
model for the motor will be automatically saved
when the supply voltage is switched off.
The stored values will then be used when it is
switched back on. If this function is disabled, the
motor thermal history is reset to zero on every
power up.
0: Thermal memory disabled
1: Thermal memory enabled
0
Parameter
Name
min. value
max. value
Description
DS