5 Parameters
5.3 “Extended” parameter group
DB1 Variable Frequency Drives
09/17 MN040034EN
www.eaton.com
39
P-36
RS485-0 Address
1
63
1
RS485-0 Baudrate
0
6
Baud Rate
2: 9.6 kbit/s
3: 19.2 kbit/s
4: 38.4 kbit/s
5: 57.6 kbit/s
6: 115.2 kbit/s
6
Comm Timeout Modbus
RTU
0
8
Comm Timeout Modbus RTU
Time between a communication loss and the
resulting action.
Setting “0” disables the action after
communications trip.
t: Indicates that the drive will trip if time is
exceeded
r: Indicates that the drive will ramp to stop if time
is exceeded
0: no action
1: t 30 ms
2: t 100 ms
3: t 1000 ms
4: t 3000 ms
5: r 30 ms
6: r 100 ms
7: r 1000 ms
8: r 3000 ms
4
P-37
Password Level2
0
9999
Defines the password which is used to get access
to extended parameter set (Level 2).
In addition, it also defines the password needed to
get access to the advanced parameter set (P-37 +
100).
Access via P-14.
101
P-38
Parameter lock
0
1
Determines whether to lock the parameters
0: OFF. All parameters can be changed.
1: ON. Parameter values can be displayed, but
cannot be changed. If a remote keypad is
connected, parameters cannot be accessed by the
remote keypad if they are locked.
0
P-39
AI1 Offset
-500.00%
500.00%
Offset Analog Input 1
Resolution 0.1 %
0.00%
Parameter
Name
min. value
max. value
Description
DS