Racks and Power Distribution
Racks and Power Distribution
UPS ProdUctS and acceSSorieS
Power
Rack Space
Configuration
Parts
Qty
Description
Required
12kW
ZC1224010100000 1 Powerware BladeUPS
6U
12 kW 400V w/60A 5W
in/ RPM ONLY w/WEB/
SNMP/4.8 min battery
For additional
battery
103005747-6591 1 Battery increase to 12 minutes 3U
runtime
2 Battery increase to 20 minutes 6U
3 Battery increase to 27 minutes 9U
4 Battery increase to 34 minutes 12U
* Each UPS requires same number of external batteries
two (2) rackS @ 6 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
PW107BA0UC08
2
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
1
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052737
1
42U Enclosure (Rack) Split Rear &
-
Casters & Sides
1052754
1
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
75U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
one (1) rack @ 12 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000
1
Powerware Rack Power Module
3U
(RPM), 12 kW, (2 x L21-30R),
(6 x C19), BladeUPS Plug, 10 ft
PW107BA0UC08
2
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052737
1
42U Enclosure (Rack) Split Rear &
-
Casters & Sides
Total U space remaining for IT equipment
33U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
Racks and Power Distribution
UPS ProdUctS and acceSSorieS
Power
Rack Space
Configuration
Parts
Qty
Description
Required
12kW N+1 ZC122P060100000 2 Powerware BladeUPS
12U
12 kW 400V w/parallel cord,
13 min battery @ 12 kW
103005913
1 Powerware 42U enclosure
6U
with BladeBar and
Bottom WW
116750221-001
1 ConnectUPS-X WEB/SNMP
-
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1
24U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591
2 Battery increase to 30 minutes 6U
battery runtime*
4 Battery increase to 44 minutes 12U
6 Battery increase to 59 minutes 18U
8 Battery increase to 76 minutes 24U
* Each UPS requires same number of external batteries
UPS ProdUctS and acceSSorieS
Power
Rack Space
Configuration
Parts
Qty
Description
Required
24kW N+1 ZC122P060100000 3 Powerware BladeUPS
18U
12 kW 400V w/parallel
cord, 9 min battery @ 24 kW
103005913
1 Powerware 42U enclosure
6U
with BladeBar and
Bottom WW
116750221-001
1 ConnectUPS-X WEB/SNMP
-
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1
18U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591
3 Battery increase to 21 minutes 9U
battery runtime*
6 Battery increase to 32 minutes 18U
9 Battery increase to 43 minutes 27U
12 Battery increase to 54 minutes 36U
* Each UPS requires same number of external batteries
two (2) rackS @ 6 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
PW107BA0UC08
2
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
2
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052754
1
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
81U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
one (1) rack @ 12 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000
1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08
2
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
1
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
Total U space remaining for IT equipment
39U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
FoUr (4) rackS @ 6 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000
1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 1
Powerware Rack Power Module (RPM), 3U
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08
4
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
4
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052754
3
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
162U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
two (2) rackS @ 12 kw Per rack
Rack Space
Parts
Qty
Description
Required
Y032420CD100000 1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 1
Powerware Rack Power Module
3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08
4
Vertical (0U) ePDU 7 kW, 16A 230V
0U
(24 x C13) / (8 x C19)
1052736
2
42U Enclosure (Rack) Split Rear &
-
Casters no Sides
1052754
1
Powerware Baying Kit,
-
to attach two racks together
Total U space remaining for IT equipment
78U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
Powerware
®
BladeUPS
™
configuration Guide
Quick configurations for 12 kW single UPS solutions up to 60 kW N+1
redundant systems.
Step 1
Select UPS based on power configuration.
Step 2
Select desired rack and power configuration.
Step 3
Select appropriate startup and service support.
Note: Typical rack configurations. Other configurations available.