OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide
S
164201594 Rev D
www.eaton.com/powerquality
91
Configuring the UPS for EBMs
To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1.
Press any button on the front panel display to activate the menu
options.
2.
Using the button, scroll to the Settings menu.
3.
Press the
button twice to select the User Settings menu.
4.
Using the button, scroll to the Number of Battery Strings option
and press the
button.
5.
Use the or buttons to select the number of strings according to
your UPS configuration:
All 2-High UPS and EBM Cabinets*
Number of Strings
UPS + 1 EBM
6
UPS + 2 EBMs
10
UPS + 3 EBMs
14
UPS + 4 EBMs
18
All 3-High UPS and EBM Cabinets*
Number of Strings
UPS + 1 EBM
10
UPS + 2 EBMs
16
UPS + 3 EBMs
22
* UPS-32 models contain 2 strings; EBM-64 models contain 4 strings.
UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.
6.
Press the
button to save the setting.
7.
Press the
ESC
button until the Eaton logo appears.