SPECIFICATIONS
EATON
Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide
S
164201393 Rev C
www.powerware.com
104
Table 17. Universal Model Specifications (ASY-0674) Continued
15 kVA, 10500 Watts
Voltage
Input Current*
Output Current
Input Service*
Heat Dissipation
Normal Mode
200
70A
75A
208
67.5A
72.5A
220
65A
70A
100A
1430W (4.88 kBTU/hr)
230
62.5A
65A
(
/ )
240
60A
62.5A
18 kVA, 12600 Watts
Voltage
Input Current*
Output Current
Input Service*
Heat Dissipation
Normal Mode
200
84A
90A
208
81A
87A
220
78A
84A
125A
1720W (5.85 kBTU/hr)
230
75A
78A
(
/ )
240
72A
75A
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.