SPECIFICATIONS
EATON
Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide
S
164201393 Rev C
www.powerware.com
101
Table 16. Split-Phase Model Specifications (ASY-0673) Continued
9 kVA, 7500 Watts
Voltage
Input Current*
Output Current
Input Service*
Heat Dissipation
Normal Mode
200
48A
45A
220
45A
42A
208
42A
43.5A
60A
860W (2 93 kBTU/h )
220
39A
42A
60A
860W (2.93 kBTU/hr)
230
43.5A
39A
240
42A
37.5A
12 kVA, 10000 Watts
Voltage
Input Current*
Output Current
Input Service*
Heat Dissipation
Normal Mode
200
64A
60A
220
60A
56A
208
56A
58A
80A
1145W (3 90 kBTU/h )
220
52A
56A
80A
1145W (3.90 kBTU/hr)
230
58A
52A
240
56A
50A
15 kVA, 12500 Watts
Voltage
Input Current*
Output Current
Input Service*
Heat Dissipation
Normal Mode
200
80A
75A
220
75A
70A
208
70A
72.5A
100A
1430W (4 88 kBTU/h )
220
65A
70A
100A
1430W (4.88 kBTU/hr)
230
72.5A
65A
240
70A
62.5A
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.