Bypass Mode
In the event of a UPS overload or internal failure, the UPS transfers your
equipment to utility power. Battery mode is not available; however, the
utility power continues to be passively filtered by the UPS. The
indicator illuminates. The UPS transfers to Bypass mode when:
S
The UPS has an overtemperature condition.
S
The UPS has an overload condition of 101 to 150% for 30 seconds.
S
The UPS detects a fault in the battery or UPS electronics.
Standby Mode
When the UPS is turned off and remains plugged into a power outlet,
the UPS is in Standby mode. The
μ
indicator flashes and the bar graph
indicators are off, indicating that power is not available to your
equipment. The battery recharges when necessary.
NOTE
For 220–240V models, the output receptacles may remain electrically live (up to
110–120V). Unplug the UPS to ensure power is not available to the output receptacles.