HARMONIC DISTORTION

What’s the Harm in Harmonics?

A concise report on the effects of harmonic distortion on computers

1. The adverse effects of harmonics on electrical power systems are well known. International 

standards exist to help manage the injection of harmonic currents into the power system.

2. A pure sine wave consists of a single fundamental frequency. Most waves are complex 

and can be broken down into a series of harmonics. For instance, the 3rd harmonic of the 
fundamental frequency 60 Hz is 180 Hz. The opposite end of the scale from a pure sine wave is 
a square wave, which contains all the odd harmonics of a fundamental frequency starting with 
the 3rd harmonic and extending to infinity.

3. Harmonic distortion is a measure of the ratio between the fundamental and the harmonics that 

are present in a wave-shape.

4. Distortion is caused by non-linear loads drawing non-sinusoidal currents.
5. Non-linear loads include such office equipment as computers (draw 3rd and 5th harmonics); 

lighting (ballasts produce 3rd and 5th), transformers (3rd component), power converters 
(variable speed drives, UPS, electronic ballasts produce 3rd, 5th, 7th, and 11th), and 
commercial appliances such as photocopiers and printers.

6. The harmonic currents in a distribution system have the following undesirable effects:

a. Significant effects on the performance of computer power supplies.
b. Heating of magnetic devices, which can cause premature insulation failure and 

breakdown.

c. Triple harmonics produce higher than expected neutral currents, potentially resulting in 

insulation damage and breakdown due to temperature rise.

d. High neutral currents cause additional voltage drops, reducing available voltage and 

introducing even more distortion at the load. The resulting neutral-to-ground voltage also 
causes parasitic ground currents.

e. Additional losses resulting in higher energy costs.
f.  Failure of power factor correction capacitors or increased resonance that leads to an 

even higher order of distortion.

g. High frequency fields that can introduce buzz into telephone lines and corrupt data in 

adjacent data lines.

h. Stray magnetic fields can introduce annoying interference patterns in VDTs.
i.  Undesirable ground currents may cause upstream GFI (ground fault interrupter) to trip, 

degrading power availability.

Computer loads

Computer power supplies are usually designed to operate over a range of AC input voltages. 
They produce a DC voltage that is affected by the wave shape of the AC waveform. Harmonic 
distortion has the effect of actually reducing the computer power supply’s operating voltage. 
That variation is compounded by the normal variation of 10%. The end result is that the computer 
supply may malfunction, hiccup, or fail to provide the required output logic voltages, resulting in 
potential bit errors. A further negative side-effect of effectively lowering the computer’s operating 
voltage range is the reduction of hold-up time, essential for the ability of the power supply to 
ride through power sags (caused by other equipments’ startups). The result is more potential bit 
errors. The simple fact is that the harmonic distortion prevalent in the modern office has a direct 
pathway to your computer power supplies, and once there it can cause data loss and other 
operating errors. 

This is a variety of harmonic frequencies 
superimposed on the desirable sine 
wave frequency passed back along the 
local power grid to other equipment 
throughout an entire office building 
or local neighborhood. The effect is 
measured by % VTHD, a measure of the 
amount of voltage variation within the 
waveform.

A Powerware Series 9 UPS is the 
best way to protect critical computer 
equipment from all potentially harmful 
power problems.

Summary of Contents for Powerware 5125

Page 1: ...Reference Guide Price Book Prices effective April 2008 500 VA 60 kVA ...

Page 2: ...fice Protection Systems to become the second largest single phase UPS manufacturer in the world The move resulted in an expanded product line and the addition of many new complementary offerings to our already aggressive product portfolio Moving forward in 2008 we are in the process of realizing a unified product roadmap that seeks to leverage the best of both product lines while targeting specifi...

Page 3: ...ingle phase Standby Powerware 3105 23 Series 5 Single phase Line interactive Powerware 5110 24 Powerware 5115 Tower 25 Powerware 5115 Rack 26 Powerware 5125 Tower 27 Powerware 5125 Rack Tower 1000 3000 VA 28 Powerware 5125 Rackmount 5000 6000 VA 30 Series 9 Single phase Online Powerware 9120 32 Powerware 9125 Rack Tower 700 3000 VA 33 Powerware 9125 Rack Tower 5000 6000 VA 36 Powerware Extended Po...

Page 4: ...e Plans 96 Powerware Three phase UPS Batteries 101 Input Plug and Output Receptacle Chart 102 Sales Returned Merchandise Authorization RMA Policy 103 Product Warranty Statements 104 Note Due to continuing product improvement programs all specifications and prices are subject to change without notice Note With the exception of batteries any UPS parts or parts kit pricing that is included in this pr...

Page 5: ... We will implement these changes in stages and will continuously send our partners rollout updates via e mail In addition the online version of the price book and reference guide on the UPS Salesweb will be continuously updated and will be the most accurate source for product numbers and prices Visit www powerware com for updated RoHS compliance information Easy onYour Wallet Better for the Enviro...

Page 6: ... for critical servers database servers networks and data centers Providing you with the most comprehensive level of protection we also recommend Series 9 for Network Area Storage NAS and Storage Area Network SAN systems IP telephony VoIP and rack applications POWER PROTECTION Risk Protection as Easy as 3 5 9 You ve invested thousands in the best equipment You consider your data a priceless commodi...

Page 7: ...ially damage hardware High frequency waveform Can be caused by either RFI or EMI caused by EMI interference interference generated by transmitters welding devices SCR driven printers lightning etc A change in frequency Resulting from generator or small stability co generation sites being loaded and unloaded Frequency variation can cause erratic operation data loss system crashes and equipment dama...

Page 8: ... Table 3 3 1 for systems operating at less than 69 kV less than 5 0 voltage total harmonic distortion THD and less than 3 0 individual harmonic voltage distortion Series 3 UPS The Series 3 UPS offers a low price solution to environments requiring minimal power protection Utility power is provided during normal operation Harmonic distortion present in the utility line passes through to the load Ser...

Page 9: ...r the battery All Batteries Will Eventually Fail The question isn t Will it happen but When will it happen Because UPS batteries are valve regulated sealed lead acid there has previously been no practical way to provide the user with any meaningful advance notice that batteries need to be replaced In the past the only way to know when the batteries were dead was when the power failed and took your...

Page 10: ...the load The resulting neutral to ground voltage also causes parasitic ground currents e Additional losses resulting in higher energy costs f Failure of power factor correction capacitors or increased resonance that leads to an even higher order of distortion g High frequency fields that can introduce buzz into telephone lines and corrupt data in adjacent data lines h Stray magnetic fields can int...

Page 11: ...overload or unsafe condition now but the owner needs to be on guard against this harmonic threat Effects of Harmonics High levels of harmonics result in erratic or subtle malfunctions of equipment that can have serious consequences Overheating could cause overvoltage damage and premature failure to computers and office equipment High harmonic levels can fool certain control circuits into erroneous...

Page 12: ...These reasons are so compelling that it s hardly worthwhile mentioning that all those features combined with our competitive pricing can lead to higher reseller margins Or is it Individual product warranty statements and the Load Protection Guarantee are located in the back of this publication 1 10 Year Pro Rated Warranty on Powerware 5115 5125 9120 9125 9140 9155 9170 and FERRUPS 2 5 Year Pro Rat...

Page 13: ... Shipping List Description Part Number Pkg of H x W x D inches H x W x D inches Weight lb Price 42U x 1050D Sidewalls pair Black PWENC9970941 80 0 x 1 x 42 80 0 x 4 0 x 42 0 105 0 275 Casters Uninstalled PWACC9970942 4 10 0 x 24 0 x 24 0 15 0 185 M6 Captive Nuts PWACC9970943 50 Bag Bag 40 M6 Phillips Screws PWACC9970944 100 Bag Bag 15 Baying Kit PWACC9970945 6 Bag Bag 2 0 25 Mounting Plate PWACC99...

Page 14: ...ions Shipping List Description Part Number Pkg of H x W x D inches H x W x D inches Weight lb Price Partition Wall for bayed enclosures PWACC9962621 1 77 0 x 40 0 80 0 x 42 0 x 4 0 10 0 300 Roof Mount Cable Manager PWACC9961554 1 24 0 x 8 0 x 6 0 26 0 x 10 0 x 8 0 8 0 100 Roof Mount Cable Manager Ladder Rack PWACC9961555 1 24 0 x 8 0 x 6 0 26 0 x 10 0 x 8 0 8 0 100 ...

Page 15: ...2 L5 20 BA 15 5 20 24 60x2 1x1 3 169 PW102BA0U022 2 1 92 L5 20 BA 15 5 20 8 16x2 1x1 3 89 PW102BA0U023 2 1 92 L5 20 BA 15 5 20 10 24x2 1x1 3 89 PW103BA0U032 2 2 88 L5 30 BA 15 5 20 24 60x2 1x1 3 299 PW103BA0U038 2 3 33 IEC320 C20 BA 6 IEC320 C13 8 15 5x1 6x1 6 129 PW103BA0U039 3 3 33 L6 20 BA 10 IEC320 C13 10 14x2 3x2 179 PW103BA0U120 3 3 33 L6 20 BA 10 IEC320 C13 24 29x2 3x2 249 PW103BA0U123 3 3 ...

Page 16: ...36 64x3 2x1 9 829 Horizontal Mount Models PW105ME1U048 2 4 99 L6 30 ME 10 IEC320 C19 4 1Ux19x4 3 399 PW105ME1U049 1 4 99 L6 30 ME 15 IEC320 C13 12 1Ux19x4 3 369 PW110ME1U083 2 9 98 IEC309 60 ME 10 IEC320 C19 6 1Ux19x11 8 679 PW317ME2U092 2 17 29 IEC309 60 ME 10 IEC320 C19 12 2Ux19x18 1 199 Monitored ePDUs Designed for high density mission critical server applications provides maximum power for bot...

Page 17: ...and a accessories port allows for temperature and humidity probes to manage local environmental conditions Vertical Mount 0U Models PW102SW0U150 2 1 92 L5 20 SW 9 5 15 8 42x1 89x2 779 PW102SW0U151 1 1 92 L5 20 SW 9 5 15 24 70x1 89x2 999 PW103SW0U152 2 2 88 L5 30 SW 9 5 15 16 70x1 89x2 949 PW103SW0U153 2 3 33 L6 20 SW 9 IEC320 C13 24 70x1 89x2 959 PW105SW0U154 1 4 99 L6 30 SW 9 IEC320 C13 16 70x1 8...

Page 18: ...05775 2 5 x 7 6 x 11 9 1 7 379 Environmental Rack Monitor C13 C14 100 250V AC 50 60Hz 3 pin power input 103005912 2 5 x 7 6 x 11 9 2 2 379 TH Module Black individual 103005822 2 4 x 6 3 x 8 8 0 7 79 Environmental Rack Monitor Water Leak Detector 3ft 103005780 0 6 x 7 9 x 8 2 0 3 129 Environmental Rack Monitor Water Leak Detector 12ft 103005894 0 6 x 11 2 x 11 4 0 5 229 Environmental Rack Monitor D...

Page 19: ... Customers connect directly to each panelboard main breaker Options List Price Input Connections Adders Direct Connection to Panelboard Main Breaker s Front Only Direct Connection to Panelboard Main Breaker s Front and Back Main Incoming Lugs Front Only 890 Main Incoming Lugs For 2 sided RPP 1 555 42 Circuit Cutler Hammer Panelboard Deduct 845 42 Circuit SqD Panelboard 1 950 Monitoring No meters i...

Page 20: ...rrier Plate Front to Back for two separate sources 505 Extra knock out plates 165 Panelboard Isolated Ground Bus per Panel 100 SERVICE PLANS For service plans please see the service section beginning on page 83 POWERWARE DATACENTER SOLUTIONS Powerware Remote Power Panel RPP continued ...

Page 21: ...208 15 1 2 Pole 3 12 awg 0 5 125 00 3 06 6 15R4 5662 208 15 1 2 Pole 3 12 awg 0 5 170 00 3 06 6 20R1 5465 208 20 1 2 Pole 3 12 awg 0 5 145 00 3 06 6 20R2 5462 208 20 1 2 Pole 3 12 awg 0 5 135 00 3 06 6 20R4 5462 208 20 1 2 Pole 3 12 awg 0 5 185 00 3 06 6 30R1 9330 208 30 1 2 Pole 3 10 awg 0 5 140 00 3 75 14 20R1 8410 120 208 20 1 2 Pole 4 12 awg 0 5 150 00 3 45 14 30R1 9430 120 208 30 1 2 Pole 4 1...

Page 22: ... 120 15 1 1 Pole 4 12 awg 0 5 140 00 3 45 L5 20R1 IG 2310 120 20 1 1 Pole 4 12 awg 0 5 135 00 3 45 L5 30R1 IG 2610 120 30 1 1 Pole 4 10 awg 0 5 155 00 4 20 L6 15R1 IG 4560 208 15 2 2 Pole 4 12 awg 0 5 140 00 3 45 L6 15R2 IG 4550 208 15 2 2 Pole 4 12 awg 0 5 135 00 3 45 L6 20R1 IG 2320 208 20 2 2 Pole 4 12 awg 0 5 135 00 3 45 L6 30R1 IG 2620 208 30 2 2 Pole 4 10 awg 0 5 165 00 4 20 L14 20R1 IG 2410...

Page 23: ...2 205 00 10 30 9C33UO 250 30 2 2 Pole 3 10 awg 0 5 625 00 4 15 9C54U2 C75 250 50 3 3 Pole 4 8 awg 0 75 1 080 00 8 60 HBL360C6W 250 60 2 2 Pole 3 6 awg 0 75 1 050 00 10 30 HBL460C9W 250 60 3 3 Pole 4 6 awg 0 75 945 00 14 30 HBL360R9W 250 60 3 3 Pole 4 6 awg 0 75 1 000 00 14 30 Notes 1 For the cables that have 0 5 conduit to go to 0 75 conduit please add 1 00 per foot to the above list price 2 For t...

Page 24: ... A 208 15 1 3 Pole 5 10 awg 0 5 365 00 4 75 FW360 N A 208 20 1 3 Pole 4 6 awg 0 75 140 00 13 15 FW360N N A 208 20 1 3 Pole 5 6 awg 1 00 270 00 15 30 FW3100 N A 208 20 1 3 Pole 4 3 awg 1 25 420 00 31 75 FW3100N N A 208 100 1 3 Pole 5 1 awg 1 50 280 00 42 90 Notes 1 For the cables that have 0 5 conduit to go to 0 75 conduit please add 1 00 per foot to the above list price 2 For the cables that have ...

Page 25: ... Dimensions Weight List Model Number VA Watt Connection Receptacles H x W x D inches lb Price PW3105 500 103004247 5592 500 300 1 8 meter 8 5 15R Outlets 11 0 x 7 0 x 4 4 7 94 79 PW3105 700 103004248 5592 700 420 Line cord 4 Battery Backup 11 0 x 7 0 x 4 4 9 70 97 with 90 5 15P 4 Surge Protection only POWERWARE 3105 INTERNATIONAL MODELS 230V 50 60 Hz Part Power Out Input Output Dimensions Weight L...

Page 26: ...t Dimensions Weight List Model Number VA Watt Connection Receptacles H x W x D inches lb Price PW5110 500 103004256 5591 500 300 1 8 meter 8 5 15R Outlets 10 6 x 3 4 x 10 2 12 1 120 PW5110 700 103004257 5591 700 420 Line cord 4 Battery Backup 10 6 x 3 4 x 10 2 15 2 150 PW5110 1000 103004258 5591 1000 600 with Surge Protection 10 6 x 3 4 x 15 1 28 0 212 PW5110 1500 103004259 5591 1440 900 90 deg 5 ...

Page 27: ...9 x 13 2 27 8 448 PW5115 1400 05146566 5591 1400 950 5 15P 6 5 15R 15 1 x 5 9 x 15 4 37 0 554 1 Bundled with Software Suite CD and communication cable DB9f to DB9m P N 60420064 002 POWERWARE 5115 INTERNATIONAL TOWER MODELS 230V 50 60 Hz1 Part Power Out Input Output Dimensions Weight List Model Number VA Watt Connection Receptacles H x W x D inches lb Price PW5115 500i 05146549 5591 500 320 IEC 320...

Page 28: ...ion for a comprehensive list of IT enclosure offerings SOFTWARE AND CONNECTIVITY OPTIONS Bundled with Software Suite CD and communication cable See the software and connectivity product section for more detail SERVICE PLANS For service plans please see the service section beginning on page 88 POWERWARE 5115 RACKMOUNT BATTERY BACKUP TIMES in minutes Load VA Watts PW5115 RM 500 PW5115 RM 750 PW5115 ...

Page 29: ...MODELS 230V 50 60 Hz includes 2 IEC interconnect cables Part Power Out Input Output Dimensions Weight List Model Number VA Watts Connection Receptacles H x W x D inches lb Price PW5125 1000i 05146630 5591 1000 700 IEC 320 C14 6 IEC 320 C13 9 45 x 6 38 x 15 79 34 3 481 PW5125 1500i 05146633 5591 1500 1050 IEC 320 C14 6 IEC 320 C13 9 84 x 6 38 x 18 39 50 7 634 PW5125 2200i 05146637 5591 2200 1600 IE...

Page 30: ...A Watt Connection Receptacle H x W x D inches lb Price PW5125 1000i RM 05146667 6591 1000 900 IEC 320 C14 6 IEC 320 C13 3 5 2U x 17 0 x 19 4 61 0 810 PW5125 1500i RM 05146670 6591 1500 1340 IEC 320 C14 6 IEC 320 C13 3 5 2U x 17 0 x 19 4 61 0 1 031 PW5125 2400i RM 05147565 6591 2400 2250 IEC 309 16A Plug 9 IEC 320 C13 3 5 2U x 17 3 x 24 5 89 0 1 430 12 attached 1 IEC 320 C19 PW5125 3000i RM 0514715...

Page 31: ... for more detail SERVICE PLANS For service plans please see the service section beginning on page 88 POWERWARE 5125 RACK TOWER BATTERY BACKUP TIMES in minutes full load half load Load VA Standard Internal Batteries 1 EBM 2 EBMs 3 EBMs 4 EBMs 1000 7 19 33 68 58 120 82 166 105 214 1500 5 13 23 57 49 161 73 172 96 205 2400 7 19 35 73 60 124 85 177 110 229 3000 5 15 25 61 49 103 69 146 90 190 Up to 4 ...

Page 32: ...W5125 6000 HW 103003610 5591 6000 5400 Hardwired Hardwired 5 25 3U x 17 50 x 26 0 161 0 3 258 4 C19 4 C13 PW5125 6000i 103003612 5591 6000 5400 IEC 309 32A IEC 309 32A on short cord 5 25 3U x 17 50 x 26 0 161 0 3 258 4 C19 4 C13 POWERWARE 5125 RACKMOUNT MODELS with Factory Installed ConnectUPS Web SNMP Card Part Power Out Input Output Dimensions Weight List Model Number VA Watt Connection Receptac...

Page 33: ...section for more detail SERVICE PLANS For service plans please see the service section beginning on page 88 POWERWARE 5125 RACKMOUNT BATTERY BACK UP TIMES in minutes Standard Load VA Watts Internal Batteries 1 EBM 2 EBMs 3 EBMs 4 EBMs 1000 900 59 169 303 452 612 2000 1800 26 79 138 204 274 2200 1980 21 65 112 164 223 2500 2250 19 61 106 156 210 2700 2430 17 52 89 132 180 3000 2700 15 49 85 125 168...

Page 34: ... 5592 9 6 x 6 2 x 16 2 31 0 489 PW9120 BATT 1000 05147367 5592 9 6 x 6 2 x 16 2 44 0 549 PW9120 BATT 1500 05147368 5592 10 8 x 6 7 x 17 5 57 0 689 PW9120 BATT 2000 3000 05147369 5592 14 2 x 8 6 x 18 6 110 0 999 SOFTWARE AND CONNECTIVITY OPTIONS Bundled with Software Suite CD and communication cable See the software and connectivity product section for more detail SERVICE PLANS For service plans pl...

Page 35: ...rdwired Hardwired 3 5 2U x 17 0 x 23 9 81 5 3 050 Notes Models do not include a rail kit Optional rail kits are available 1 Models fit in 19 inch rack enclosures 2 6 5 ft 2 meter line cord 3 L5 30R is located on a 12 inch attached cord 4 Use PowerPass for NEMA receptacles POWERWARE 9125 INTERNATIONAL MODELS 230V 50 60 Hz Part Power Out Input Output Dimensions Weight List Model Number VA Watts Conn...

Page 36: ...rom UPS as input to PowerPass except for hardwired units Note items 1 3 attach to the back of the unit they are not rackmounted POWERWARE 9125 OPTIONS Part Dimensions Weight List Description Number H x W x D inches lb Price 700 2000 VA Optional Mounting Hardware Mounting Rail Kit 2 post 2U 19 inch if not supplied with rack 05146726 5591 105 Mounting Rail Kit 4 post 2U 19 inch if not supplied with ...

Page 37: ... 68 88 3000 2100 5 25 38 54 70 Note Backup times are approximate and may vary with equipment configuration battery age temperature etc POWERWARE 9125 EBC BACKUP TIMES in minutes 1 Discharge Time EXTERNAL EBC 48 CABINETS For use with 1250 1500 2000 VA VA Watts 1 EBC 48 2 EBC 48s 3 EBC 48s 650 455 838 800 560 662 1000 700 506 1200 840 406 1250 875 387 1400 980 340 761 1500 1050 315 705 1600 1120 294...

Page 38: ...ction Receptacles H x W x D inches 1 lb Price PPDM L6 30 103003214 6501 208 240 208 240 120 L6 30P 1 L6 30R 8 5 15R 5 25 3U x 17 4 x 24 8 106 0 999 PPDM L6 20 103003214 6502 208 240 208 240 120 L6 30P 1 L6 20R 8 5 15R 5 25 3U x 17 4 x 24 8 106 0 999 PPDM L5 30 103003214 6503 208 240 208 240 120 L6 30P 1 L5 30R 8 5 15R 5 25 3U x 17 4 x 24 8 106 0 999 PPDM L14 30R 103003214 6504 208 240 208 240 120 ...

Page 39: ...etail SERVICE PLANS For service plans please see the service section beginning on page 88 POWERWARE 9125 5000 6000 VA BATTERY BACKUP TIMES in minutes 1 Load VA Watts Standard Internal Batteries 1 EBM 2 EBMs 3 EBMs 4 EBMs 1000 700 64 179 308 448 2000 1400 38 108 186 271 362 3000 2100 24 70 122 178 237 4000 2800 19 49 86 125 168 5000 3500 13 37 65 96 128 6000 4200 10 30 52 76 102 1 This table provid...

Page 40: ... 599 PDM304FFGGE L5 30P L5 20R L5 20R L5 30R L5 30R 599 PDM304GGGGE L5 30P L5 30R L5 30R L5 30R L5 30R 599 PDM304HHHHE L5 30P L5 15R 2 L5 15R 2 L5 15R 2 L5 15R 2 599 PDM304VVVVA L5 30P 1 5 50R 5 15R2 599 PDM304VVVVE L5 30P 1 5 50R 5 15R2 599 PDM305AAAAE L14 30P L14 30R L14 30R L14 30R L14 30R 599 PDM305AACCE L14 30P L14 30R L14 30R L6 30R L6 30R 599 PDM305AABCE L14 30P L14 30R L14 30R L6 20R L6 30...

Page 41: ...mber Connection Receptacles H x W x D inches lb Price PW9140 7500 HW 103005093 6591 Hardwired Hardwired 3 C19 2 C13 10 5 6U x 17 2 x 30 0 254 0 5 394 PW9140 10000 HW 103004728 6591 Hardwired Hardwired 3 C19 2 C13 10 5 6U x 17 2 x 30 0 254 0 6 344 PW9140 7500 103005094 6591 IEC309 60A cord IEC309 60A cord 4 C19 10 5 6U x 17 2 x 30 0 265 0 5 919 PW9140 10000 103004727 6591 IEC309 60A cord IEC309 60A...

Page 42: ...00 VA Line Cord Power Module Spare 2 799 106711171 004 PW9140 10 000 VA Power Module Spare 2 799 106711172 001 PW9140 Battery Module Spare 279 POWERWARE 9140 BATTERY BACKUP TIMES in minutes 1 Load VA Watts Standard Internal Batteries 1 EBM 2 EBMs 3 EBMs 4 EBMs 1250 1000 80 137 189 275 365 2500 2000 31 61 99 138 181 3750 3000 18 38 68 92 121 5000 4000 12 27 52 69 90 6250 5000 9 21 42 55 72 7500 600...

Page 43: ...al 32 2 x 12 x 33 7 352 0 9 965 PW9155 10 kVA 64 Battery 3 high K41012000000000 10 9 Hardwired Optional 47 8 x 12 x 33 7 590 0 11 985 PW9155 Model 10 kVA 32 Battery K41013000000000 10 9 Hardwired Optional 47 8 x 12 x 33 7 558 0 13 870 w Trans Mod 3 high PW9155 12 kVA 32 Battery 2 high K41211000000000 12 10 8 Hardwired Optional 32 2 x 12 x 33 7 352 0 10 825 PW9155 12 kVA 64 Battery 3 high K41212000...

Page 44: ... Systems 124100017 001 9155 Parallel Tie Cabinet 24 0 x 20 3 x 2 2 57 3 1 499 103004336 CAN Bridge Card 519 Note Up to 3 PW9155s can be paralled within the Parallel Tie Cabinet and each UPS must include a Powerware Hot Sync CAN Bridge Card installed in the 2nd X Slot Extended Battery Module 103004192 5501 PW9155 EBM 64 2 high Stack 32 2 x 12 0 x 30 2 480 0 4 425 103004193 5501 PW9155 EBM 96 3 high...

Page 45: ...6 92 0 136 0 12500 11250 6 1 28 8 54 0 81 6 111 0 17 6 54 0 96 2 142 0 12000 10800 6 5 30 2 56 5 85 5 116 0 18 6 56 5 101 0 149 0 11500 10350 6 9 31 6 59 3 89 7 122 0 19 2 59 3 106 0 156 0 11000 9900 7 3 33 3 62 4 94 4 129 0 20 2 62 4 111 0 164 0 10500 9450 7 8 35 1 65 9 99 6 136 0 21 4 65 9 117 0 174 0 10000 9000 8 4 37 2 69 8 106 0 144 0 22 6 69 8 124 0 184 0 9500 8550 9 1 39 6 74 2 112 0 153 0 ...

Page 46: ...0 120 240V In Out ASY 0567 4 23 x 14 12 x 15 25 17 0 2 029 Universal Power Module 208 240V In Out ASY 0528 4 23 x 14 12 x 15 25 17 0 1 929 Battery Module two required per slot string ASY 0529 4 23 x 7 012 x 14 75 30 0 310 Optional 20 Amp Charger Module same form factor as 3 kVA power modules ASY 0652 4 23 x 14 12 x 14 75 17 0 2 879 UPS Enclosures 3 slot enclosure 3 kVA max Hardwired Input Output 0...

Page 47: ... 0 x 25 5 155 0 4 583 Includes to 9 kVA N X 1 6 slot enclosure 1 power module 2 battery modules 1 caster kit PW6S6K 6 kVA expandable Hardwired Hardwired 33 3 x 17 0 x 25 5 232 0 6 997 Includes to 9 kVA N X 1 6 slot enclosure 2 power modules 4 battery modules 1 caster kit PW6S9K 9 kVA expandable Hardwired Hardwired 33 3 x 17 0 x 25 5 346 0 9 411 Includes to 9 kVA N X 1 6 slot enclosure 3 power modu...

Page 48: ... kVA N X 3 L6 30R 1 12 slot enclosure 12 5 20R 4 power modules 8 battery modules PW12S15K PD 15 kVA expandable Hardwired 3 L14 30R 60 7 x 24 0 x 28 5 581 0 15 121 Includes to 18 kVA N X 3 L6 30R 1 12 slot enclosure 12 5 20R 5 power modules 10 battery modules PW12S18K PD 18 kVA expandable Hardwired 3 L14 30R 60 7 x 24 0 x 28 5 658 0 17 535 Includes to 18 kVA N X 3 L6 30R 1 12 slot enclosure 12 5 20...

Page 49: ...battery modules occupy 1 slot 1 String 2 String 3 String 4 String 5 String 6 String 7 String 8 String 9 String 10 String 11 String 12 String 3 kVA 6 5 16 16 40 27 5 67 5 40 98 53 5 132 67 5 167 83 204 98 242 115 283 132 324 149 365 167 408 6 kVA 6 5 16 11 27 5 16 40 21 5 53 5 27 5 68 33 5 83 40 98 46 5 115 53 5 132 60 5 149 67 5 167 9 kVA 6 5 16 9 5 23 5 13 31 5 16 40 20 49 23 5 58 27 5 67 5 31 5 ...

Page 50: ...49 L5 30R twist lock Split Phase 1 L 59 L6 15R twist lock duplex All 1 M 79 L6 20R twist lock All 1 N 69 L6 30R twist lock All 1 O 69 Schuko Universal 1 P 69 L14 30R twist lock Split Phase 1 R 69 3 x 5 15R duplex Split Phase 2 W 69 3 x 5 20R duplex Split Phase 2 X 69 SERVICE PLANS For service plans please see the service section beginning on page 88 Maximum of 3 different types of receptacles per ...

Page 51: ... FE000BB3A0A0A0A 120V 120V 11 31 min 5 15P 6 5 15R 1 951 FE1 4kVA FE010BB3A0A0A0A 120V 120V 22 62 min 5 15P 6 5 15R 2 210 Model FE1 8 1 8 kVA 1 25 kW FE1 8kVA FF000CC3A0A0A0B 120V 120V 11 30 min 5 20P 6 5 20R 2 991 FE1 8kVA FF010AA0A0A0A0B 120V 120V 86 206 min Hardwire Hardwire 3 534 FE1 8KVA FF010CC3A0A0A0B 120V 120V 86 206 min 5 20P 6 5 20R 3 494 Model FE2 1 2 1k VA 1 5 kW FE2 1kVA FG000AA0A0A0A...

Page 52: ...6 min 2 430 BPE04MBB1A External maintenance bypass switch make before break 650 System List 11 800 Model FE12 5 12 5 kVA 10 kW FE12 5kVA FM140AA0A0A0A0B 208 208 120V External Hardwired Hardwired 9 312 Recommended system options EBPS12F Standard external battery pack 18 48 min 4 140 BPE04BBM1A External maintenance bypass switch break before make 550 System List 13 782 FE12 5kVA FM340AA0A0A0A0B 240 ...

Page 53: ...ONS Part List Description Number Price Serial CheckUPS Cable DB25M to DB9F INT 0035 48 BestLink Web SNMP Adapter External 116750225 001 370 Signal Splitter Box IPK 0022 249 Sensaphone 1104 FGD 1104 PW 499 Sensaphone 1104 Temperature Sensor FGD 1101 49 IBM AS 400 Kit Standard Cable Kit IPK 0001 95 AS 400 Bypass Switch Cable IPK 0001 120 Handheld Remote and Keypad FE FES FER models only RCK 0007 265...

Page 54: ... 705 40 m 1 h 42 m 27 m 1 h 14 m 2FE 3 790 1 h 11 m 2 h 51 m 49 m 2 h 10 m 34 m 1 h 28 m 3FE 4 200 1 h 49 m 4 h 05 m 1 h 12 m 3 h 08 m 48 m 2 h 13 m 4FE2 5 600 2h 06 m 4 h 46 m 1 h 27 m 3 h 39 m 60 m 2 h 33 m 5FE2 6 845 3 h 04 m 6 h 46 m 2 h 13 m 5 h 11 m 1 h 32 m 3 h 41 m 6FE3 8 240 4 h 27 m 9 h 39 m 3 h 08 m 7 h 22 m 2 h 16 m 5 h 14 m 7FE3 11 380 7 h 12 m 15 h 56 m 5 h 10 m 12 h 10 m 3 h 45 m 8 ...

Page 55: ... Charger SPK FILV 10A SPK FIHV 10A 1 449 FE4 3kVA 60 Hz Tower with 20 Amp Battery Charger SPK FILV 20A SPK FIHV 20A 1 799 FE5 3kVA 60 Hz Tower with 5 Amp Battery Charger SPK FJLV 5A SPK FJHV 5A 1 199 FE5 3kVA 60 Hz Tower with 10 Amp Battery Charger SPK FJLV 10A SPK FJHV 10A 1 449 FE5 3kVA 60 Hz Tower with 20 Amp Battery Charger SPK FJLV 20A SPK FJHV 20A 1 799 FE7kVA 60 Hz Tower with 5 Amp Battery ...

Page 56: ...S 12kW 208V w 60A 5W ZC1212010100000 12 kVA 12kW 208 208 10 5 x 17 3 x 28 0 321 0 12 150 in RPM ONLY w SNMP PWBladeUPS 208V w parallel cord ZC121P060100000 12 kVA 12kW 208 208 10 5 x 17 3 x 28 0 311 0 12 075 PWBladeUPS 208V w parallel cord w SNMP ZC121P061100000 12 kVA 12kW 208 208 10 5 x 17 3 x 28 0 311 0 12 400 1 All weights are installed weight add 80lbs to determine shipping weight POWERWARE B...

Page 57: ...U RPM can be deployed in the same rack with the UPS and IT equipment there s no need for a dedicated infrastructure rack The resulting architecture has fewer cables to manage fewer distribution points to monitor and greater flexibility for IT personnel make changes without an electrician Provides plug and play primary distribution of power from threephase input source to secondary power distributi...

Page 58: ...r 400V 2 Select input connector option 3 Select input cord length corded units only 4 Select first receptacle plate option 5 Select second receptacle plate option 6 Select metering option 7 Select TVSS option Example of configured model part number Y03111022300000 SERVICE PLANS For service plans please see the service section beginning on page 81 POWERWARE BladeUPS BATTERY BACKUP TIMES in minutes ...

Page 59: ...ith 32 Battery 2 high KA1511100000010 15 kVA 13 5kW 208 208 4 32 2 x 12 0 x 33 7 373 0 15 500 PW9355 15 kVA with 64 Battery 3 high KA1512100000010 15 kVA 13 5kW 208 208 13 47 8 x 12 0 x 33 7 609 0 17 230 PW9355 15 kVA with 32 Battery 2 high KA1511200000010 15 kVA 13 5kW 220 2202 4 32 2 x 12 0 x 33 7 373 0 15 500 PW9355 15 kVA with 64 Battery 3 high KA1512200000010 15 kVA 13 5kW 220 2202 13 47 8 x ...

Page 60: ...12 220 B 2 5 20R UL 9 10 11 12 220 D 2 6 15R 9 10 11 12 220 E 2 6 20R 9 10 11 12 220 F 2 L5 15R 9 10 11 12 220 G 1 L5 20R 9 10 11 12 220 H 1 L5 30R 9 10 11 12 220 I 2 L6 15R 9 10 11 12 220 J 1 L6 20R 9 10 11 12 220 K 1 L6 30R 9 10 11 12 220 L 1 L14 20R 9 10 11 12 220 M 1 L14 30R 9 10 11 12 220 X Blank Panel 9 10 11 12 20 N 2 IEC 320 C13 120V 9 10 11 12 220 P 2 IEC 320 C19 120V 9 10 11 12 220 Note ...

Page 61: ...136 0 21 4 65 9 117 0 174 0 10000 9000 8 4 37 2 69 8 106 0 144 0 22 6 69 8 124 0 184 0 9500 8550 9 1 39 6 74 2 112 0 153 0 24 1 74 2 132 0 196 0 9000 8100 9 9 42 3 79 4 120 0 163 0 25 7 79 4 141 0 209 0 8500 7650 10 8 45 5 85 2 129 0 175 0 27 6 85 2 152 0 225 0 8000 7200 11 9 49 1 91 9 139 0 189 0 29 8 91 9 164 0 242 0 7500 6750 13 1 53 2 99 7 151 0 205 0 32 3 99 7 178 0 263 0 7000 6300 14 6 58 0 ...

Page 62: ...net PW9355 20 kVA Dual Feed KB2013100000010 480 208 18 66 0 x 60 0 x 34 1 2230 0 KBT002200000010 30 375 with Options Cabinets Internal Batteries 2 Opt Cabs KBT001200000010 PW9355 20 kVA Single Feed KB2013100000010 600 208 18 66 0 x 40 0 x 34 1 1695 0 KBT001300000010 25 375 with Options Cabinets Internal Batteries PW9355 20 kVA Dual Feed KB2013100000010 600 208 18 66 0 x 60 0 x 34 1 2230 0 KBT00130...

Page 63: ...79 Zone 4 Seismic Kit 103004896 Zone 4 Kit 1 799 Remote Monitor Panel requires Industrial Relay X Slot Card part See Page 69 for Connectivity Options Pricing CAN Bridge Parallel Card 103004336 Spare Parts Kit See Service Section Upgrade 9355 20 kVA to 9355 30 kVA See Service Section Upgrade a standard UPS to a parallel UPS module See Service Section Note Up to 3 EBMs can be added to each UPS for e...

Page 64: ...4300 12 38 62 95 114 26000 23400 13 40 65 98 118 25000 22500 14 43 68 101 124 24000 21600 14 46 71 103 129 23000 20700 15 48 74 106 134 22000 19800 16 51 76 109 144 21000 18900 17 53 79 111 152 20000 18000 18 56 82 114 160 19000 17100 19 58 85 117 175 18000 16200 20 62 88 120 189 17000 15300 22 66 92 130 204 16000 14400 24 71 96 142 219 15000 13500 26 75 101 154 234 14000 12600 28 79 105 166 249 1...

Page 65: ...stamping anti aliasing ITIC analysis and automatic trigger settings open field upgradeable firmware memory expandable to 1 GB and optional digital relay I O card Comprehensive power and power quality measurements for 138 standard data points logged Embedded Web Server see and analyze waveforms trends harmonics directly in your web browser meter display High speed 6 Mhz impulsive transient detectio...

Page 66: ... w VAUX PX6251A5AA 7 654 PX 6000 Meter AC w VAUX Com Exp Card PX6251A5BA 8 808 PX 6000 Meter AC w VAUX I O Card PX6251A5AB 8 283 PX 6000 Meter AC w VAUX Com Exp I O Cards PX6251A5BB 9 437 PX 6000 Meter AC w VAUX 1GB CF PX6251A6AA 8 178 PX 6000 Meter AC w VAUX 1GB CF Com Exp Card PX6251A6BA 9 332 PX 6000 Meter AC w VAUX 1GB CF I O Card PX6251A6AB 8 807 PX 6000 Meter AC w VAUX 1GB CF Com Exp I O Car...

Page 67: ... 1 PX8251A5BB PX 8000 Meter w VAUX Std pwr 512MB CF Com Exp I O Cards Example 2 PX6251A6BA PX 6000 Meter w VAUX Std pwr 1GB CF Com Exp Card POWER XPERT 4000 6000 8000 METERS Power Quality Metering Products continued Model Series 4 4000 Standard Power Quality 6 6000 Enhanced Power Quality 8 8000 Premium PQ w Transient Capture Voltage Input Configuration 0 Standard V1 V2 V3 V4 2 Standard plus auxili...

Page 68: ... version of PowerVision software Features and Benefits Stealth Mode Operation Cost Savings Calculator Animated UPS PowerScope View History Calendar and ControlRoom Views Separate views for single and three phase UPSs Event History Summary Battery replacement warning Power On Off scheduling via calendar UPS Load Segment receptacle Control Local Remote UPS Power On Off Automatic graceful shut down w...

Page 69: ...des simultaneous monitoring of multiple ConnectUPS and BD cards from a single console Powerware Extensions for IBM Director Network Management System integration software The extensions for IBM Director considerably simplify network management tasks for UPSs by allowing system administrators to monitor diagnose configure set alarms schedule self tests check battery gather inventory information and...

Page 70: ...otal package includes Server Core Layout Manager Quality Manager Modbus PXSTOTALPK 21 000 TCP Connector and SNMP Connector PowerVision v4 x Software Products Part Number List Price PowerVision Network Edition License includes built in multiple server OS shutdown unlimited 165200132 661 Available Options Include Environmental Monitoring Probe 116750224 001 220 Secure Web Server Option License 16520...

Page 71: ... Mbps power connected network connections with no additional expense Alarm notification through any combination of e mail SNMP traps or network message speeds corrective action Integrated NetWatch Client software provides graceful unattended shutdown of computer operating systems in the event of an extended power failure Powerware MultiView software provides simultaneous UPS monitoring through mul...

Page 72: ...s with any Powerware UPS with any ConnectUPS Web SNMP card Can be located up to 20 meters 65 6 feet from the UPS Measures ambient temperatures between 20ºC and 80ºC Measures relatively humidity between 10 and 90 percent Displays status on Web page IP phone or PDA or network management system Auto sends alarms via e mail PCS phone or pager Warranty US and Canada 2 year limited warranty option for e...

Page 73: ... options Note You can have up to two optional connectivity cards installed CONNECTIVITY Connectivity Products continued Other Connectivity Products continued Serial Cards Integration Products ConnectUPS X Environmental Multi Server Card Web SNMP Card Modbus Card Probe1 Part Number 05146447 5502 116750221 001 103002510 5501 116750224 001 Powerware 5115 1U RM Powerware 5125 Powerware 9120 Powerware ...

Page 74: ...146 Relay Card X Slot AS 400 Compatible 1018460 146 AS 400 cables for relay cards 1014018 and 1018460 AS 400 model 9406 DB15 DB9 25 ft 103004349 5501 62 DB15 DB9 75 ft 103004347 5501 104 Industrial Relay and Display Drive Card 5A 250V 103003055 335 Provides 4 Form C Relay contacts for integrating UPS alarms into security and alarm systems Also provides signal information for the Remote Monitor Dis...

Page 75: ...ppliances 185 Max Series CHSPMAX 1500 75 000 Amps 50 000 Amps Standard surge protection for major appliances and home electronics 319 Ultra Series CHSPULTRA 3500 175 000 Amps 75 000 Amps Ultimate surge protection for major appliances home electronics computers home office and entertainment systems 590 3 Way Series CHSPCHSR4P 3500 175 000 Amps 75 000 Amps Standard 3 way protection ac power phone ca...

Page 76: ...dem 132 SGXMAXTV 975 90 000 Amps 7 Outlet 5 15R 6 power Mid level protection for ac cord Transformer spacing Power Cable TV 137 SGXMAXAC 975 90 000 Amps 7 Outlet 5 15R 6 power Mid level protection for ac cord Transformer spacing power only 104 Ultra Series SGXULTNET 1575 105 000 Amps 8 Outlet 5 15R 6 power Advanced protection for ac cord transformer spacing Power Telephone Modem 207 SGXULTTV 1575 ...

Page 77: ...ircuit breaker protection protects generator circuits from overload 7000 Watt Portable Generator 12 250 Starting Watts Extended run time per tank of fuel Push button electronic start Fold down handle for compact storage and transportation 10 pneumatic wheels for all terrain mobility Full power locking outlet provides secure connection while delivering maximum power Lo Tone muffler keeps noise leve...

Page 78: ...Wye Three phase 4W G PXL120208YSK 16 0 x 11 0 x 4 0 21 1 315 PXL120208YSM 25 0 x 14 0 x 8 0 40 1 715 120 240 Single Split phase 3W G PXL120240SSK 16 0 x 11 0 x 4 0 21 1 445 PXL120240SSM 25 0 x 14 0 x 8 0 40 1 845 240 Delta 3W G PXL120240DSK 16 0 x 11 0 x 4 0 21 1 580 PXL120240DSM 25 0 x 14 0 x 8 0 40 1 980 480 Delta 3W G PXL120480DSK 16 0 x 11 0 x 4 0 21 1 580 PXL120480DSM 25 0 x 14 0 x 8 0 40 1 9...

Page 79: ... option Integral Disconnect 208 120 Wye Three phase 4W G PXL300208YPK 18 0 x 13 0 x 4 0 24 3 515 PXL300208YPM 25 0 x 14 0 x 8 0 40 4 315 120 240 Single Split phase 3W G PXL300240SPK 18 0 x 13 0 x 4 0 24 3 845 PXL300240SPM 25 0 x 14 0 x 8 0 40 4 645 240 Delta 3W G PXL300240DPK 18 0 x 13 0 x 4 0 24 4 175 PXL300240DPM 25 0 x 14 0 x 8 0 40 4 975 480 Delta 3W G PXL300480DPK 18 0 x 13 0 x 4 0 24 4 175 P...

Page 80: ... 25 0 x 14 0 x 8 0 40 7 705 480 Delta 3W G PXL500480DPK 18 0 x 13 0 x 4 0 24 6 805 PXL500480DPM 25 0 x 14 0 x 8 0 40 7 705 480 277 Wye Three phase 4W G PXL500480YPK 18 0 x 13 0 x 4 0 24 6 805 PXL500480YPM 25 0 x 14 0 x 8 0 40 7 705 Standard Diagnostics K option No Integral Disconnect M option Integral Disconnect 208 120 Wye Three phase 4W G PXL500208YSK 18 0 x 13 0 x 4 0 24 5 485 PXL500208YSM 25 0...

Page 81: ... PVL100240DK 11 55 x 5 0 x 2 6 5 1 010 480 Delta 3W G PVL100480DK 11 55 x 5 0 x 2 6 5 1 010 480 277 Wye Three phase 4W G PVL100480YK 11 55 x 5 0 x 2 6 5 1 010 PVL 120 120kA phase surge rating 208 120 Wye Three phase 4W G PVL120208YK 11 55 x 5 0 x 2 6 5 1 035 120 240 Single Split phase 3W G PVL120240SK 11 55 x 5 0 x 2 6 5 1 140 240 Delta 3W G PVL120240DK 11 55 x 5 0 x 2 6 5 1 245 480 Delta 3W G PVL...

Page 82: ...res RJ21 M F PDDP25B 1 25 x 3 3 x 6 63 0 78 232 25 Pairs 50 wires RJ21 M F PDDP25E 1 25 x 3 3 x 6 63 0 7 232 25 Pairs 50 wires RJ21 M F PDDP25G 1 25 x 3 3 x 6 63 0 78 232 25 Pairs 50 wires RJ21 M F PDDP25T 1 25 x 3 3 x 6 63 0 7 232 50 Pairs 100 wires 2 RJ21 M F PDDP50A 2 5 x 3 3 x 6 63 1 35 423 50 Pairs 100 wires 2 RJ21 M F PDDP50B 2 5 x 3 3 x 6 63 1 5 423 50 Pairs 100 wires 2 RJ21 M F PDDP50E 2 5...

Page 83: ...3 x 1 47 x 120 0 0 40 101 Low Voltage Fused RJ45 Pins 1 2 4 5 PMTJT1 0 93 x 1 47 x 3 6 0 19 51 PPCH Series Category 5 12 Ports 110 IDC RJ45 PPCH12C5 1 75 x 19 0 x 1 28 1 2 428 12 Port 110 IDC RJ45 4 Center Wires Fused PPCH12RJ45B 1 75 x 19 0 x 1 28 1 2 702 12 Port 110 IDC RJ45 Telco 4 Center Wires Fused PPCH12RJ45G 1 75 x 19 0 x 1 28 1 2 768 Category 5 24 Ports 110 IDC RJ45 PPCH24C5 3 5 x 19 0 x 1...

Page 84: ...rminal Block PTSP2BG 0 93 x 1 47 x 3 6 0 16 51 2 2 Center Wire Quick Connect Terminal Block PTSP2BT 0 93 x 1 47 x 3 6 0 16 51 2 2 Center Wire Quick Connect Terminal Block PTSP32BA 1 25 x 13 35 x 5 3 1 76 387 2 2 Center Wire Quick Connect Terminal Block PTSP32BB 1 25 x 13 35 x 5 3 1 84 387 32 32 Center Wire Quick Connect Terminal Block PTSP32BE 1 25 x 13 35 x 5 3 1 76 387 2 2 Center Wire Quick Conn...

Page 85: ...clusive to contract customers they cannot be purchased without a corrective contract Additionally contracts are value priced compared to a single PM and an average emergency Time Materials T M event a single rectifier board can exceed 5 000 plus labor to replace Offerings Complete line of Power Systems Maintenance Plans Remote monitoring services to support maximum uptime Battery maintenance and u...

Page 86: ...g for site personnel Comprehensive coverage for the entire UPS including standard batteries Toll free number for Gold Plan Plus technical support Replacement UPS or module delivered to your location by overnight carrier Original UPS or module picked up from your locations All freight paid by Eaton See applicable Powerware limited warranty for details The Powerware Gold Plan Plus is ideal for modul...

Page 87: ...m responsiveness with up to five years of bumper to bumper on site service system startup plus performance checks The On Site Gold Plan Plus delivers complete care of your UPS from the moment it begins protecting your mission critical systems and beyond with Eaton s prompt 24 hour response for any on site corrective maintenance needs Enhanced on site UPS maintenance coverage and startup Enhance yo...

Page 88: ...x8 for Series 5 products 7x24 for Series 9 products and Ferrups 2 Unit must be within 100 miles of Eaton established service location to qualify for 24 hr response 3 Initial start up serves as the annual PM service for the first year of operation Subsequent PM services are schedule on request from customer beginning in the second year of operation SERVICES SUMMARY Summary of Eaton Service Plans fo...

Page 89: ...ling 100 Domestic 250 International plus freight 3 Minimum Billing UPS and Power System UPS and Power System Equipment below 200kVA Equipment 200kVA and above or Multi Module A Five day or less response 4 hour minimum charge 6 hour minimum charge B Two day or less response Not applicable 8 hour minimum charge 4 Calculation of Charges Portal to Portal travel time and mileage 5 Travel Transportation...

Page 90: ...ice Series 5 0STUP5100XALLC5 695 Series 9 0STUP9100XALLC5 695 Series Ferro 0STUPFERRXALLC5 695 Product Part Number List Price On Site Preventive Maintenance 5 x 8 service Series 5 0XXPM5100XALLC5 695 Series 9 0XXPM9100XALLC5 695 Series Ferro 0XXPMFERRXALLC5 695 Product Part Number List Price On Site Startup 7 x 24 service Series 5 0STUP5100XALLC7 895 Series 9 0STUP9100XALLC7 895 Series Ferro 0STUP...

Page 91: ...1252400XX 1 395 5 YR 5XXGX51253000CX 504 5OSGX51253000CX 1 256 5OSGP51252400XX 2 355 Base Unit 7 x 24 Service Adders Contract On Site Gold Plan On Site Gold Plan Plus Product Duration Part Number List Price Part Number List Price 7x24 Base 2 YR 2OSGX5100BASEC7 292 2OSGP5100BASEC7 477 Adder 3 YR 3OSGX5100BASEC7 328 3OSGP5100BASEC7 697 5 YR 5OSGX5100BASEC7 379 5OSGP5100BASEC7 1 081 External Battery ...

Page 92: ...covers standard internal batteries POWERWARE 9120 SERVICE PLANS On site service is 7 x 24 Contract Gold Plan On Site Gold Plan On Site Gold Plan Plus Product Duration Part Number List Price Part Number List Price Part Number List Price 700 1500 VA 2 YR 2XXGX91201500CX 46 2OSGX91201500CX 887 2OSGP91201500CX 1 515 3 YR 3XXGX91201500CX 163 3OSGX91201500CX 1 020 3OSGP91201500CX 1 661 5 YR 5XXGX9120150...

Page 93: ...1 670 3OPGP91253000CX 2 427 5 YR 5XPGX91253000CX 1 038 5OPGX91253000CX 2 239 5OPGP91253000CX 3 198 5000 6000 2 YR 2XPGX91256000CX 515 2OPGX91256000CX 1 389 2OPGP91256000CX 1 958 3 YR 3XPGX91256000CX 1 056 3OPGX91256000CX 2 108 3OPGP91256000CX 3 245 5 YR 5XPGX91256000CX 2 095 5OPGX91256000CX 3 500 5OPGP91256000CX 5 775 Extended Battery Module Adder Service Plans On Site Service is 7 x 24 Contract G...

Page 94: ...e Part Number List Price 7 5 kVA 2 YR 2XPGX91400750CX 935 2XPGP91400750CX 1 485 2OPGX91400750CX 1 835 2OPGP91400750CX 2 711 3 YR 3XPGX91400750CX 1 636 3XPGP91400750CX 2 186 3OPGX91400750CX 2 598 3OPGP91400750CX 3 564 5 YR 5XPGX91400750CX 3 082 5XPGP91400750CX 3 632 5OPGX91400750CX 4 141 5OPGP91400750CX 5 228 10 kVA 2 YR 2XPGX91401000CX 965 2XPGP91401000CX 1 515 2OPGX91401000CX 1 865 2OPGP91401000C...

Page 95: ...mber List Price 8 10 kVA 2 YR 2OPGX915510KVCX 1 070 2OPGP915510KVCX 1 960 3 YR 3OPGX915510KVCX 1 897 3OPGP915510KVCX 3 710 5 YR 5OPGX915510KVCX 3 584 5OPGP915510KVCX 6 295 8 10 kVA 2 YR 2OPGX915510P2CX 1 924 2OPGP915510P2CX 3 600 2 Unit Parallel 3 YR 3OPGX915510P2CX 3 281 3OPGP915510P2CX 6 667 5 YR 5OPGX915510P2CX 5 994 5OPGP915510P2CX 11 028 8 10 kVA 2 YR 2OPGX915510P3CX 2 405 2OPGP915510P3CX 4 5...

Page 96: ...0B9SLCX 355 2OSGP9170B9SLCX 391 9 Slot External 3 YR 3XXGP9170B9SLCX 1 528 3OSGX9170B9SLCX 1 601 3OSGP9170B9SLCX 1 697 Battery Cabinet 5 YR 5XXGP9170B9SLCX 2 920 5OSGX9170B9SLCX 3 053 5OSGP9170B9SLCX 3 213 9170 2 YR 2XXGP9170B12SCX 382 2OSGX9170B12SCX 434 2OSGP9170B12SCX 470 12 Slot External 3 YR 3XXGP9170B12SCX 2 048 3OSGX9170B12SCX 2 121 3OSGP9170B12SCX 2 217 Battery Cabinet 5 YR 5XXGP9170B12SCX...

Page 97: ... 5XXGXFERRXBG2CX 946 5XXGPFERRXBG2CX 978 5OSGXFERRXBG2CX 1 140 5OSGPFERRXBG2CX 1 345 25ME 1re GROUP 3 2FE 9FE 2 YR 2XXGXFERRXBG3CX 79 2XXGPFERRXBG3CX 112 2OSGXFERRXBG3CX 177 2OSGPFERRXBG3CX 261 16FE 2re 3 YR 3XXGXFERRXBG3CX 599 3XXGPFERRXBG3CX 646 3OSGXFERRXBG3CX 746 3OSGPFERRXBG3CX 873 1rd 5 YR 5XXGXFERRXBG3CX 1 311 5XXGPFERRXBG3CX 1 344 5OSGXFERRXBG3CX 1 560 5OSGPFERRXBG3CX 1 765 GROUP 4 EBPS12 ...

Page 98: ...or 7x24 8 HR 1 YR depot Powerware Three phase UPS Models Powerware BladeUPS1 Optional Powerware 9355 UPS Optional Optional 5 Powerware PDU RPP Optional included with start up 1 Powerware BladeUPS warranty and service plans coverage includes both electronics and batteries 2 4 and 2 hour response is limited availability major markets call 800 843 9433 to verify 3 PMs preventive maintenance are per y...

Page 99: ...ing eNotify remote UPS and battery monitoring SOW R 28 Extended Battery Module Replacement Depot 475 475 Coverage per EBM P N BRO9C BLADEBM BRO9C BLADEBM Adds replacement coverage for EBM 3U On Site 650 650 cabinets and batteries requires a P N BR07C BLADEBM BR07C BLADEBM PowerTrust contract shipping is ground UPS and Battery Preventive Maintenance Special BladeUPS combined 5x8 900 1 350 UPS and b...

Page 100: ...T Board 106711205 4 234 106711205 4 234 106711205 4 234 C Spares Kit 106711207 2 066 106711207 2 066 106711207 2 066 1 Start up purchase required to activate PDU warranty and Service Protection Plan coverage 2 Prices apply only to PDU and RPP products purchased after January 2006 non Eaton made PDU product use MVS pricing 3 Standard Warranty and Service Protection Plan for Powerware PDU includes 1...

Page 101: ...55015 2 175 PVN3C 9355030 2 327 2 Year Battery Labor Coverage adder1 adds labor and freight to 2YR battery parts warranty Per Cabinet Pricing BL07C 9355015 300 BL07C 9355030 300 Part numbers P N are based on services sold concurrently with product purchase if service is sold non concurrently change digit 5 to N 1 Requires a new Eaton Powerware branded battery installed at factory or replacement pr...

Page 102: ...711169 8 240 106711170 8 680 B Spares Kit 106711181 6 120 106711182 6 595 C Spares Kit 106711183 1 815 106711184 2 271 Full Battery Coverage FBC Powerware 9355 Full Battery Coverage Pricing Battery Configuration Per Year Per Year Price Price HR12 34 QTY 32 FB07C32 9355015 477 HR12 34 QTY 64 FB07C64 9355015 692 HR12 34 QTY 96 FB07C96 9355015 890 HR12 34 QTY 108 FB07C108 9355030 990 HR12 120 QTY 36 ...

Page 103: ... our products to verify that they meet or exceed manufacturer specifications and supply maximum runtime Using Eaton qualified batteries gives your customers confidence that their batteries will perform as expected and keep their applications running Batteries are the number one cause of UPS load loss One bad battery can ruin an entire string Eaton qualified batteries are backed by a service networ...

Page 104: ...hart 5 15R 5 15P 5 20R 5 20P L5 30R L5 30P 6 15R 6 15P L6 20R L6 20P 14 50R 14 50P L14 30R L14 30P IEC 320 C13 female IEC 320 C14 male L6 15R L6 15P IEC 320 C19 female IEC 320 C20 male L6 30R L6 30P IEC 309 16A IEC 309 32A R indicates receptacle P indicates plug L indicates locking plug or receptacle ...

Page 105: ...special custom or configured products will be a minimum of 50 The buyer is responsible for both inbound and outbound freight charges Note Charges may be waived by mutual agreement between buyer and seller Proper approval and authorization must be obtained and documented in writing before the transaction is initiated Erroneous Shipments Sales RMAs necessary as a result of shipping order entry error...

Page 106: ...ny Customer Service Engineer or Agent or f use of the Product under other than normal operating conditions or in a manner inconsistent with the Product s labels or instructions This Guaranty is not valid a unless the End User returns to Company the Warranty Registration Card within thirty 30 days of purchase or b if the Product s serial numbers have been removed or are illegible Company shall not ...

Page 107: ... packaging as the replacement Warranted Item received by the End user or as otherwise instructed by Company If Company does not receive the defective Warranted Item Company will either charge the End user s credit card or send the End user an invoice which the End user agrees to pay for the value of the replacement product If the Warranted Item is to be replaced by Company but the End user is unwi...

Page 108: ... Company hereunder whether the claims are based in contract including indemnity in tort including negligence or strict liability or otherwise shall not exceed the price of the Product on which such liability is based Company shall not be responsible for failure to provide service or parts due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of t...

Page 109: ...nt and at no cost to the End user the replacement Warranted Item to the End user within one 1 business day after Company receives notice of the warranty claim In such case the End user must return at Company s expense the defective Warranted Item to Company in the same packaging as the replacement Warranted Item received by the End user or as otherwise instructed by Company If Company does not rec...

Page 110: ...eunder whether the claims are based in contract including indemnity in tort including negligence or strict liability or otherwise shall not exceed the price of the Product on which such liability is based Company shall not be responsible for failure to provide service or parts due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Warranty...

Page 111: ...agrees to pay for the value of the replacement Product If the Warranted Item is to be replaced by Company but the End User is unwilling or unable to supply a credit card number or purchase order for the value of the replacement Product Company will use commercially reasonable business efforts to ship via standard ground shipment and at no cost to the End User the replacement Warranted Item to the ...

Page 112: ... which such liability is based Company shall not be responsible for failure to provide service or parts due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Warranty the End User must register the product warranty via mail or online at www powerware com warranty registration use the Product in a normal way follow the Product s user s gui...

Page 113: ...tem is to be replaced by Company but the End User is unwilling or unable to supply a credit card number or purchase order for the value of the replacement Product Company will use commercially reasonable business efforts to ship via standard ground shipment and at no cost to the End User the replacement Warranted Item to the End User within one 1 business day after Company receives the defective P...

Page 114: ...or otherwise shall not exceed the price of the Product on which such liability is based Company shall not be responsible for failure to provide service or parts due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Warranty the End User must use the Product in a normal way follow the Product s user s guide and protect against further dama...

Page 115: ...f the Warranted Item is to be replaced by Company but the End User is unwilling or unable to supply a credit card number or purchase order for the value of the replacement Product Company will use commercially reasonable business efforts to ship via standard ground shipment and at no cost to the End User the replacement Warranted Item to the End User within one 1 business day after Company receive...

Page 116: ...ue to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Warranty the End User must use the Product in a normal way follow the Product s user s guide and protect against further damage to the Product if there is a covered defect OTHER LIMITATIONS Company s obligations under this Warranty are expressly conditioned upon receipt by Company of al...

Page 117: ...Product b if the Product is moved to a new location by someone other than an authorized Eaton Customer Service Engineer in USA or Agent outside of USA or c if the Product s serial numbers have been removed or are illegible Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof Labor wa...

Page 118: ... months from date of Product shipment whichever occurs first for the refurbishment replacement of parts The period covered by this Warranty for Product installed and currently located outside of the fifty 50 United States and the District of Columbia is twelve 12 months from the date of Product purchase or eighteen 18 months from date of Product shipment whichever occurs first for the refurbishmen...

Page 119: ...expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts COSTS NOT RELATED TO WARRANTY The End User shall be invoiced for and shall pay for all services not expressly provided for by the terms of this Warranty including without limitation site calls involving an inspection that determines no corrective maintenance is required Any costs for replacement equipme...

Page 120: ... PowerTrust PowerTrust Preferred LanSafe X Slot Status AGlance Powerware Hot Sync PowerVision and PowerChain Management are trade names trademarks and or service marks of Eaton Corporation or its subsidiaries and affiliates All other trademarks are property of their respective owners 2008 Eaton Corporation All Rights Reserved Printed in USA SLT02LTA April 11 2008 ...

Reviews: