UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual P-164000821—Rev 01
www.eaton.com/powerquality
3-3
The UPS ventilation requirements are shown in Table 3-3.
Figure 3-1. UPS Cabinet Dimensions – (Front View)
NOTE
Eaton battery cabinets are located in the same room as the UPS, the battery cabinet
environmental requirements supersede the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life
and performance, and will reduce or void the battery warranty. Refer to
Eaton's
Terms and Conditions of Sale with Battery Replacement Coverage and the Battery
Replacement Price Book
for more information. These documents can be found at
www.eaton.com/powerquality or contact an Eaton service representative for
information on how to obtain copies.
Table 3-3. 480V Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395C
1000 kW
1000 kVA
480/480
37.3 (128)
Approximately 4250 liter/sec (9000 CFM)
1000 kW
1100 kVA
480/480
37.3 (128)
1100 kW
1100 kVA
480/480
42.3 (144)
Dimensions are in millimeters [inches].
1964
[77.3]
3731
[146.9]