8
3. DNP Device Profile
PXM 4/6/8K DNP3 Ethernet Communications User Manual
MN150005EN January 2017 www.eaton.com
3. DNP Device Profile
DNP V3.0
DEVICE PROFILE DOCUMENT
This document must be accompanied by a table having the following headings:
Object Group Request Func
ti
on Codes Response Func
ti
on Codes
Object Varia
ti
on Request Quali
fi
ers Response Quali
fi
ers
Object Name (op
ti
onal)
Vendor Name:
Eaton
Device Name:
Power Expert Meter 4k/6k/8k
Highest DNP Level Supported:
For Requests :
Level 2
For Responses :
Level 2
Device Func
ti
on:
Master
Slave
Notable objects, func
ti
ons, and/or quali
fi
ers supported in addi
ti
on to the Highest DNP Levels Supported.
For sta
ti
c (non-change-event) object requests, request quali
fi
er codes 07 and 08 (limited quan
ti
ty), and 17
and 28 (index) are supported.
16-
16-bit and 32-bit Analog Change Events with Time are supported.
Floa
ti
ng Point Analog Output Status and Output Block Objects 40 are supported.
The read func
ti
on code for Object 50 (Time and Date), varia
ti
on 1, is supported.
Maximum Data Link Frame Size (octets):
Transmi
tt
ed:
292
Received :
292
Maximum Applica
ti
on Fragment Size (octets):
Transmi
tt
ed:
Con
fi
gurable up-to 2048
Received :
2048
Maximum Data Link Re-tries:
None
Fixed at ____
Con
fi
gurable from 0 to 15
Maximum Applica
ti
on Layer Re-tries:
None
Con
fi
gurable