Appendix D—Modbus Register Map
360
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
1045
Voltage Unbalance Trip
Delay
UINT16 RW NV
Default: 20
Range: 1 to 60
Units: seconds
Config CRC
Admin Lock
USB Lock
Backup Mem
Voltage Unbalance Trip Delay is the time delay following the trip level
being exceeded until a trip occurs.
1046
High Power Trip Level
SINT16 RW NV
Default: 110
Range: -200 to 200
Units: %
Config CRC
Admin Lock
USB Lock
Backup Mem
High Power Trip Level will trip the motor if the calculated KW Level
exceeds this threshold, following the High Power Trip Delay time.
1047
High Power Alarm Level
SINT16 RW NV
Default: 110
Range: -200 to 200
Units: %
Config CRC
Admin Lock
USB Lock
Backup Mem
High Power Alarm Level (based on KW) when exceeded and following the
Alarm Delay Time in the Protections/General category, will generate a
warning.
1048
High Power Trip Delay
UINT16 RW NV
Default: 20
Range: 1 to 60
Units: seconds
Config CRC
Admin Lock
USB Lock
Backup Mem
High Power Trip Delay is the time delay following the trip level being
exceeded until a trip occurs.
1049
Low Power Trip Level
SINT16 RW NV
Default: 50
Range: -200 to 200
Units: %
Config CRC
Admin Lock
USB Lock
Backup Mem
Low Power Trip Level will trip the motor if the calculated KW Level drops
below this threshold, following the Low Power Trip Delay time.
1050
Low Power Alarm Level
SINT16 RW NV
Default: 50
Range: -200 to 200
Units: %
Config CRC
Admin Lock
USB Lock
Backup Mem
Low Power Alarm Level when exceeded and following the Alarm Delay
Time in the Protections/General category, will generate a warning.
Table 128. C445 Modbus Register Map, continued