Appendix D—Modbus Register Map
310
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
314
Active Inhibit
UINT16 RO
Enum
Current Active Inhibit, continued
315
Configuration Inhibit
Reason
UINT8 RO
Enum
The reason for an active inhibit due to an incorrect or out-of-range
configuration parameter.
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
Value
Description
1040
Logic User Inhibit 41
1041
Logic User Inhibit 42
1042
Logic User Inhibit 43
1043
Logic User Inhibit 44
1044
Logic User Inhibit 45
1045
Logic User Inhibit 46
1046
Logic User Inhibit 47
1047
Logic User Inhibit 48
1048
Logic User Inhibit 49
1049
Logic User Inhibit 50
Value
Description
0
No active inhibits
1
Local and Remote motor control sources both point to
Fieldwire
2
Local motor control source is set to User Interface but the
User Interface type does not match
3
One or more enabled protection features requires a voltage
option card in the Measurement Module
4
One or more enabled protection features requires a PTC
(Temperature) option card in the Measurement Module
5
Selected operational mode is incompatible with 3wire cfg
fieldwire as local control
6
Cannot choose fieldwire as the feedback source when the
fieldwire is used as a local / remote source with the
selected starter
7
UI Custom Overlay - Multiple buttons assigned to same
function
8
UI Custom Overlay - Multiple button LEDs assigned to the
same function
9
UI Custom Overlay - Multiple status LEDs assigned to the
same function
10
Selected operational mode is incompatible with the
connected UI
11
The General Purpose I/O operational mode does not use
fieldwire as a control source
12
Q3 configured for both latching relay and shunt trip output