FIELD INSTALLED UPM INSTALLATION PLAN AND UNPACKING

Power Xpert 

9395P Field Installed UPM Mechanical Installation Manual  

S

  P-164000503 Rev 1

 

3-2

Table 3‐1. FI-UPM Cabinet Maximum Weight

Model

Maximum Weight 

kg (lb)

Shipping

Installed

Power Xpert 9395P FI-UPM

496 (1094)

471 (1037)

The FI-UPM cabinet uses forced air cooling to regulate internal component
temperature. Air inlets are in the front of the cabinet and outlets are in the top. Allow
clearance in front of and above each cabinet for proper air circulation. The clearances
required around the FI-UPM cabinet are shown in Table 3‐2. Dimensions are in
millimeters (inches).

Table 3‐2. FI-UPM Cabinet Clearances

From Top of Cabinet

457.2 mm (18

) minimum clearance for ventilation

From Front of Cabinet

914.4 mm (36

) working space

From Back of Cabinet

None Required

From Right Side of Cabinet

None Required

From Left Side of Cabinet

None Required

The basic environmental requirements for operation of the FI-UPM are:

S

Ambient Temperature Range:

0–40°C (32–104°F)

S

Recommended Operating Range: 20–25°C (68–77°F)

S

Maximum Relative Humidity:

95%, non-condensing

The FI-UPM ventilation requirements are shown in Table 3‐3.

Table 3‐3. FI-UPM Air Conditioning or Ventilation Requirements During Full Load Operation

Rating

Input/Output Voltage

Heat Rejection

kW (1000 BTU/hr)

Ventilation Required for

Cooling Air Exhaust

225 kVA

480/480

7.9 (27.1)

Approximately

950 liter/sec

(2000 CFM)

250 kVA

480/480

9.3 (31.9)

275 kVA

480/480

10.6 (36.1)

300 kVA

480/480

10.6 (36.1)

Summary of Contents for Power Xpert 9395P

Page 1: ...Eaton Power Xpert 9395 High Performance Field Installed UPM Mechanical Installation Manual Referenced throughout as 9395P...

Page 2: ......

Page 3: ...Eaton Power Xpert 9395 High Performance Field Installed UPM Mechanical Installation Manual Referenced throughout as 9395P...

Page 4: ...et conserver ce manuel afin de pouvoir vous y reporter ult rieurement WARNING This is a product for restricted sales distribution to informed partners EN IEC 62040 2 Installation restrictions or addit...

Page 5: ...2 Safety Warnings 2 1 3 Field Installed UPM Installation Plan and Unpacking 3 1 3 1 Creating an Installation Plan 3 1 3 2 Preparing the Site 3 1 3 3 Inspecting and Unpacking the FI UPM Cabinet 3 6 4...

Page 6: ...ew 3 4 Figure 3 3 FI UPM Cabinet Dimensions Top View 3 4 Figure 3 4 FI UPM Cabinet Dimensions Bottom View 3 5 Figure 3 5 FI UPM Cabinet Dimensions Bottom View with Mounting Brackets 3 5 Figure 3 6 FI...

Page 7: ...1 become void This service is offered as part of the sales contract for the FI UPM Contact an Eaton service representative in advance usually a two week notice is required to request service 1 1 Usin...

Page 8: ...INTRODUCTION Power Xpert 9395P Field Installed UPM Mechanical Installation Manual S P 164000503 Rev 1 1 2 Figure 1 1 Power Xpert 9395P Field Installed UPM...

Page 9: ...WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center 1 4 For More Information Refer to the following manuals for additional information S Eaton Power Xpe...

Page 10: ...he following S Scheduling initial startup S Regional locations and telephone numbers S A question about any of the information in this manual S A question this manual does not answer Please call the E...

Page 11: ...ontaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 maximum The system is not intended for outdoor use S Ensure all power is disconnected befo...

Page 12: ...er les portes de l onduleur ferm es et les panneaux avant en place pour garantir une circulation ad quate de l air de refroidissement et pour prot ger le personnel des tensions dangereuses dans l unit...

Page 13: ...procedures and illustrations in paragraph 3 2 and Chapter 4 to create a logical plan for installing the system 3 2 Preparing the Site For the FI UPM to operate at peak efficiency the installation sit...

Page 14: ...net Clearances From Top of Cabinet 457 2 mm 18 minimum clearance for ventilation From Front of Cabinet 914 4 mm 36 working space From Back of Cabinet None Required From Right Side of Cabinet None Requ...

Page 15: ...LLATION PLAN AND UNPACKING Power Xpert 9395P Field Installed UPM Mechanical Installation Manual S P 164000503 Rev 1 3 3 Dimensions are in millimeters inches 1880 74 0 735 9 29 0 Figure 3 1 FI UPM Cabi...

Page 16: ...al Installation Manual S P 164000503 Rev 1 3 4 871 34 3 831 5 32 7 39 5 1 6 192 4 7 6 149 2 5 9 Dimensions are in millimeters inches Figure 3 2 FI UPM Cabinet Dimensions Right Side View Front Dimensio...

Page 17: ...3 5 Front 602 8 23 7 213 8 4 Dimensions are in millimeters inches Figure 3 4 FI UPM Cabinet Dimensions Bottom View Front 12 7 0 5 X 15 8 0 62 Slot 6X 830 32 7 346 13 6 346 13 6 69 2 7 39 2 1 54 59 2...

Page 18: ...et is heavy see Table 3 1 on page 3 2 If unpacking and unloading instructions are not closely followed the cabinet may tip and cause serious injury AVERTISSEMENT Les sections de l onduleur sont lourde...

Page 19: ...ncliner les armoires FI UPM plus de 10 degr s de la verticale puisqu elles pourraient se renverser 3 Set the pallet on a firm level surface allowing a minimum clearance of 3m 10 ft on each side for re...

Page 20: ...INSTALLED UPM INSTALLATION PLAN AND UNPACKING Power Xpert 9395P Field Installed UPM Mechanical Installation Manual S P 164000503 Rev 1 3 8 Figure 3 7 Power Xpert 9395P FI UPM Cabinet as Shipped on Pa...

Page 21: ...r remove the shield before operating the UPS system Once the debris shield is removed do not place objects on the ventilation grill S A FI UPM is always designated as UPM 4 4 2 Unloading the FI UPM Ca...

Page 22: ...3 6 for the FI UPM cabinet center of gravity measurements 2 Remove the three bolts securing the left side shipping bracket to the cabinet and three bolts securing the bracket to the pallet see Figure...

Page 23: ...UPM 1 Remove the wire entry plate located on the bottom left side of the UPS cabinet see Figure 4 3 2 If not already removed remove the wire entry knockout located on the top left side of the UPS cab...

Page 24: ...the bracket with the screws from the hardware kit 8 Reinstall the FI UPM front panel removed in Step 6 and secure with the retained hardware 9 If permanently mounting the system proceed to Step 10 oth...

Page 25: ...ntract for the FI UPM Contact an Eaton service representative in advance usually a two week notice is required to reserve a preferred startup date 4 6 Completing the Installation Checklist The final s...

Page 26: ...the FI UPM to the UPS Air conditioning equipment is installed and operating correctly The area around the installed UPS system is clean and dust free It is recommended that the UPS be installed on a...

Page 27: ..._________________ _________________________________________________________________________ _________________________________________________________________________ __________________________________...

Page 28: ...FIELD INSTALLED UPM INSTALLATION Power Xpert 9395P Field Installed UPM Mechanical Installation Manual S P 164000503 Rev 1 4 8 This page intentionally left blank...

Page 29: ...new location by someone other than an authorized Eaton Customer Service Engineer in USA or Agent outside of USA or c if the Product s serial numbers have been removed or are illegible Any Warranted It...

Page 30: ...WARRANTY Power Xpert 9395P Field Installed UPM Mechanical Installation Manual S P 164000503 Rev 1 W 2 This page intentionally left blank...

Page 31: ......

Page 32: ...P 1640005031 P 164000503 1...

Reviews: