To use the REPO switch:
1.
Firmly push the red pushbutton until it locks into place. The switch latches into the activated state (see
The battery breaker or disconnect is tripped and the power module is turned off immediately without
asking for verification.
Do not attempt to restart the system after using the REPO until the cause of the shutdown has been identified
and cleared.
Ne pas tenter de redémarrer le système après le déclenchement du circuit d’arrêt d’urgence à distance avant
d’avoir déterminé la raison du déclenchement.
2.
To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases (see
). To remove the key, rotate the key back to
the vertical position.
3.
Restart the UPS by following the procedure in paragraph
UPS Operation using the Color Touchscreen Control Panel
.
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
L’intérieur de l’armoire de l’onduleur est alimenté jusqu’à ce que le disjoncteur du circuit d’alimentation en
amont soit activé.