Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
75
Figure 43. Distributed Bypass System CAN and Pull-Chain Simplified Interface Wiring
UPS 1
UPS 2
UPS 3
UPS 4
CAN
(If Installed)
(If Installed)
Pull Chain
NOTE
This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order.
Table 18. CAN Bridge Card Wiring Terminations
From UPS 1 CAN Bridge
Card
From UPS 2 CAN Bridge
Card
To UPS 3 CAN Bridge Card
(If Installed)
To UPS 4 CAN Bridge Card
(If Installed)
J3 8 (L)
J3 8 (L)
J3 8 (L)
J3 8 (L)
J3 9 (H)
J3 9 (H)
J3 9 (H)
J3 9 (H)
J3 10 (Shield)
J3 10 (Shield)
J3 10 (Shield)
J3 10 (Shield)
Table 19. Pull-Chain Wiring Terminations
From UPS 1
To UPS 2
To UPS 3 (If Installed)
To UPS 4 (If Installed)
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)
Summary of Contents for Power Xpert 9395C
Page 8: ......
Page 175: ...16400082106 164000821 06...