Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
155
Figure 101. UPS Control Panel
3
1
2
PRESS ANY KEY TO CONTINUE
The control panel consists of:
•
A liquid crystal display (LCD) (
1
)
•
A horizontal row of pushbutton switches (
2
)
•
A vertical column of status indicators (
3
). See paragraph
The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph
for use of the operational controls.
When the unit powers up, the screen displays the Eaton logo as shown in
. To advance to the Main
Menu and Mimic screen, press any control panel pushbutton once.
77..22..11
S
Sttaattuuss IInnddiiccaattoorrss
The four symbols on the right side of the control panel are status indicators. These colored light emitting diode
(LED) lamps work with the alarm horn to let you know the operating status of the UPS.
describes the status indicators.
Table 31. Status Indicators
Indicator
Status
Description
Green
On
The UPS is in Online mode, operating normally. The power module is supplying power
to the critical load.
Off
The UPS is turned off.
Yellow
On
The UPS is in Battery mode. Because Battery mode is a normal condition of the UPS,
the Online indicator also remains illuminated.