Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
45
44..33
FFiieelldd IInnssttaalllleedd U
UP
PM
M IInnssttaallllaattiioonn
If installing a FI-UPM, install the FI-UPM using the instructions in the
Eaton 9395 Field Installed UPM
Mechanical Installation Manual
, listed in
. After the FI-UPM is installed, proceed to
if installing a battery system; otherwise, proceed to
Distributed Bypass Tie Cabinet Installation
.
44..44
B
Baatttteerryy S
Syysstteem
m IInnssttaallllaattiioonn
If installing an Eaton battery cabinet, refer to the
Eaton 9395 Integrated Battery Cabinet (Model IBC-L)
Installation Manual
, listed in
.
If installing a customer-supplied battery system, install the battery system according to the battery and battery
system manufacturer's instructions and all applicable codes and regulations, including the NEC, Article 480.
After the battery system is installed, proceed to
Distributed Bypass Tie Cabinet Installation
if installing a
distributed bypass tie cabinet; otherwise, proceed to
Installing UPS External and Battery Power Wiring
to
complete the wiring of the UPS.
44..55
D
Diissttrriibbuutteedd B
Byyppaassss TTiiee C
Caabbiinneett IInnssttaallllaattiioonn
NOTE
The tie cabinet must contain Module Output Breakers (MOBs) with dual auxiliary
contacts for control of the system. Without dual auxiliary MOBs, UPMs are not allowed
to go to bypass individually during servicing. All UPMs will go to bypass instead of the
just the UPM needing service, decreasing critical load protection. With dual auxiliary
MOBs, one UPM can be bypassed while the remaining UPMs support the load as long
as the remaining UPMs have the capacity to do so.
If installing a distributed bypass system, install the customer-supplied tie cabinet or distribution panel according
to the tie cabinet or distribution panel manufacturer's instructions and all applicable codes and regulations,
including the NEC, Article 480. After the tie cabinet is installed, proceed to
Installing UPS External and Battery Power Wiring
to complete the wiring of the UPS.
In the case of parallel Distributed Bypass configurations, wiring for the common system neutral reference will
also be connected to E12 of each module and this common system neutral reference wiring will be routed to
the output switchgear cabinet and connected to an isolated / ungrounded bus which is common with the wiring
from the E12 terminal of all other paralleled modules of the Distributed Bypass system.
44..66
IInnssttaalllliinngg U
UP
PS
S EExxtteerrnnaall aanndd B
Baatttteerryy P
Poow
weerr W
Wiirriinngg
NOTE 1
The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of
the unit (see
). Do not remove the debris shield until installation is complete.
However, remove the shield before operating the UPS. Once the debris shield is
removed, do not place objects on the ventilation grill.
NOTE 2
Remove the UPS cabinet top or bottom conduit landing plate to drill or punch conduit
holes (see
NOTE 3
If the load requires a neutral, a bypass source neutral must be provided.
NOTE 4
DO NOT install both a source neutral and a bonding jumper. See
for neutral
bonding jumper wire sizes. Bonding jumper must be copper wire.