Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
119
Table 31. Display Menu Operation (Continued)
Function
Subfunction
Operation
Output Current –
UPS
Output Current –
UPM
The Output Current screen displays a real time bar graph of the output current of
the UPS. The graph shows the current for each phase.
Output Power –
UPM
The Output Power screen displays the power in kW and kVA for each UPM.
System Level 0
Setup
Function Selection
This screen can be used to set the screen contrast, show the firmware versions
installed, identify the unit type, change the display language, set up Energy Saver
functions, set up Advanced Power Management functions, and enter a password to
access Level 1 functions. Press the
SETUP
pushbutton on the main menu bar to
display the System Setup Level 0 Screen. No password is necessary to access
Level 0 functions. Use the up or down arrow pushbutton to highlight the setup
function screen desired, then press the
SELECT
pushbutton to display the function
screen.
Contrast Adjust
Select
CONTRAST
from the System Setup Level 0 menu to display the Contrast
Adjust screen. Use the left or right arrow pushbutton to adjust the contrast for the
LCD. When the contrast adjustment is complete, press the
SAVE
pushbutton. Once
the setting is saved, the System Setup screen displays. To return to the System
Setup screen without saving the setting, press the
ESC
pushbutton.
Firmware Versions
The Versions screen provides the firmware version numbers installed on the UPS.
Select
VERSIONS
from the System Setup Level 0 menu to display the Versions
screen. To scroll through the firmware types, press the up or down arrow
pushbutton on the menu bar. To return to the System Setup screen, press the
ESC
pushbutton.
Identification
The Unit Type screen provides the model, CTO, and serial numbers of the UPS unit.
Select
UNIT TYPE
from the System Setup Level 0 menu to display the Unit Type
screen. To return to the System Setup screen, press the
ESC
pushbutton.
Language
The Language Setup screen allows the display menu language to be set. Select
LANGUAGE SETUP
from the System Setup Level 0 menu to display the Language
Setup screen. Use the up or down arrow pushbutton to highlight the desired
language, then press the
SELECT
pushbutton. To return to the System Setup
screen, press the
ESC
pushbutton.
Energy Saver
System
The Energy Saver System Setup screen allows the Energy Saver function to be
configured. Select
ENERGY SAVER SYSTEM SETUP
from the System Setup
Level 0 menu to display the Energy Saver System Setup screen. Use the up or down
arrow pushbutton to highlight the desired function, then press the
SELECT
pushbutton. To return to the System Setup screen, press the
ESC
pushbutton.
Storm Detection
Counter
The Storm Detection Counter screen sets the number of power line disturbances
that can occur before the UPS locks into Online mode. Select
STORM DETECTION
COUNTER
from the Energy Saver System Setup screen to display the Storm
Detection Counter screen. Use the up or down arrow pushbutton to set the counter.
Press
SAVE
or
ABORT
. Once the action is completed, the Energy Saver System
Setup screen is displayed.
Storm Detection
Timer
The Storm Detection Timer screen sets the length of time that power line
disturbances are monitored. The time can be set in 10 minute increments from 0 to
990 minutes. Select
STORM DETECTION TIMER
from the Energy Saver System
Setup screen to display the Storm Detection Timer screen. Use the up or down