DG1 Series Overview
8
PowerXL DG1 Series Option Cards
MN040007EN—April 2014 www.eaton.com
Installing DG1 Option Board
Remove Utility line and control power from the PowerXL
DG1 series drive. Install the option board in one of the slots
available on the control board. To insert and remove the
board, hold it in a horizontally straight position to avoid
twisting the connector pins.
CAUTION
To prevent board damage, option cards and fieldbus boards
must not be installed, removed or replaced while utility line
or control power is applied to the PowerXL Drive.
Verify the board fits tightly in the metal clamp and plastic
groove. If the board seems to be difficult to install in the slot,
you should confirm that you are using one of the allowed
slots for the option board.
Note:
Check that the DIP switch settings on the board
correspond to your need.
Control Wiring
Digital I/O and 24 Vdc can use Stranded Cu or Solid Cu wire
as specified below. Analog signal PT100 must use shielded
cables.
Table 3
shows the wire sizes available. I/O terminals
allow for 5.00 mm connectors.
Table 3. Wire Sizes
Wire Type
Wire Size
Terminal Torque
Solid Cu –90°C
12–28 AWG (0.2~2.5 mm
2
)
4.5 in-lb (0.5 Nm)
Stranded Cu –90°C
12–30 AWG (0.2~2.5 mm
2
)
4.5 in-lb (0.5 Nm)
Summary of Contents for Power XL DG1 Series