background image

2

Instruction Leaflet 

IL012348EN

Effective August 2020 

Instructions for LFD Current Limiter for Series C F-Frame and PD Frame 2. 

ELC Current Limiter for Series C F-Frame and PD Frame 2 MCPs. 

EATON 

www.eaton.com

 WARNING

DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON 

EQUIPMENT WHILE IT IS ENERGIZED.  DEATH, SEVERE PERSONAL INJURY, 

OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH 

ENERGIZED EQUIPMENT.  ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT 

BEFORE PROCEEDING WITH THE TASK AND ALWAYS FOLLOW GENERALLY 

ACCEPTED SAFETY PROCEDURES.  EATON IS NOT LIABLE FOR THE 

MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS. 

The User is cautioned to observe all recommendations,warnings, and 

cautions relating to the safety of personnel and equipment as well as 

all general and local health and safety laws, codes, and procedures.
The recommendations and information contained herein are based on 

Eaton experience and judgment, but should not be considered to be 

all-inclusive or covering every application or circumstance which may 

arise. If any questions arise, contact Eaton for further information or 

instructions.

Current limter circuit breaker or current limiter/MCP combinations are

designed for maximum protection and coordination, and should be

applied in accordance with the current limiter nameplate. For example,
the LFB3150R current limiter is for use only with thermal-magnetic 

F-Frame or PD2, whereas the ELC3030R current limiter is only to

be used with the 30A MCP.

This noninterchangeability feature is made possible by combinations

of molded projections and grooves and by several sizes of pierced and

2 .  INSTALLATION

1. INTRODUCTION

 WARNING

IF REMOVING A CIRCUIT BREAKER INSTALLED IN AN ELECTRICAL SYSTEM,

MAKE SURE THERCIRCUIT BREAKERS IS SWITCHED TO THE OFF POSITION 

AND THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PREFORMED.

SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS.

THE VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERS

PERSONAL INJURY.

threaded terminals. Standard terminals are provided with the current

limiter and are suitable for either copper or aluminum wire as shown

A circuit breaker that is mounted in an electrical system must be removed

to install the current limiter.

2-1. Remove terminals from load end of circuit breaker.

Note: During next step, molded projections of current limiter should

fit inside the molded grooves in the circuit breaker.

2-2. Position threaded terminals of current limiter under circuit breaker

terminals.

2-3. Secure current limiter to circuit breaker using the threee short screws

and lockwashers (Table 2-1) provided in the packing envelope. Torque load
screws (Table 2-1).

2-4. Secure current limiter to mounting panel using long #8-32 screws

provided in the packaging envelope.

2-5. Connect cables to current limiter. Table 1-1 shows available connector

types.

in Table 1-1.

For this publication, the term circuit breaker shall also include motor

Type ELC

Current Limiter

Max.Amps.

Terminal wire connectors areUL listed for standard wire sizes as

UL 486A or 486B 
Optional on special order for copper cable only 

Standard Aluminum

Terminals

Nonstandard Terminals

(Steel)

Wire Range

AWG          (mm²)

50

100

150

#14-2

#1-410

#1-410

(2.5-35)

(50-95)

(50-95)

#14-2 

²

(2.5-35)

Wire Range

AWG          (mm²)

circuit protector.

Table 1-1 Current Limiter Terminals Wire Sizes 

Table 2-1 Clamping Screw Torque Values and Usage.

Note :  Before attempting to Install the current limiter, check that
the catalog number is correct and that the rating of the accessory
satisfies job requirements.

Current Limiter

Amperes

Clamping Screw

Torque value

lb-in

(N•m)

25-70

100-150 (also LFD3150R)

#12-24

1/4-20

20 to 40

60 to 80

(2.26 to 4.52)

(6.78 to 9.4)

1

²

Eaton assumes no responsiblity for malfunctioning accessories
installed by the customer.

A circuit breaker that is mounted in an electrical system must be removed
to install the current limiter.

Reviews: