Eaton PMINT Installation And Use Manual Download Page 23

11

04/10 AWB1230-1621

Gültig ab April 2010

Umsetzermodul PMINT—PROFIBUS-DP

— Installation und Verwendung

 

EATON CORPORATION

 www.moeller.net/de/support 

Tabelle 15.  Ursache der Statusänderung

Code

Definition

Code Definition

0

Unbekannt

40

Diagnosefehler 1

1

Normaler Betriebsmodus

41

niedriger Batterie-Ladezustand

2

Externer Zustand 1

42

mehrere Ursachen

3

unverzögerter Überstrom in Phase

43

Diagnosewarnung 2

4

Unverzögerter Überstrom Masse

44

Diagnosewarnung 3

5

Unverzögerter Überstrom Neutral

45

Diagnosewarnung 4

6

Unverzögerter Rest-Überstrom

46

Diagnosewarnung 5

7

Phase stromabhängig Überstrom

47

Diagnosewarnung 6

8

Masse stromabhängig Überstrom

48

Diagnosewarnung 7

9

Neutral stromabhängig Überstrom

49

Diagnosewarnung 8

10

Reststrom stromabhängig Überstrom

50

Diagnosewarnung 9

11

Überspannung

51

Diagnosewarnung 10

12

Unterspannung

52

Diagnosefehler 2

13

Überspannung Hilfsspannung

53

Diagnosefehler 3

14

Unterspannung Hilfsspannung

54

Diagnosefehler 4

15

Unterfrequenz

55

Diagnosefehler 5

16

Überfrequenz

56

Diagnosefehler 6

17

Unsymmetrischer Strom

57

Diagnosefehler 7

18

Unsymmetrische Spannung

58

Diagnosefehler 8

19

Scheinleistungsfaktor

59

Diagnosefehler 9

20

Grundschwingungs-

Verschiebungsfaktor

60

Diagnosefehler 10

21

Logische Selektivität, Phase

61

lange Verzögerung bei Überstrom 

in Phase

22

Logische Selektivität, Masse

62

kurze Verzögerung bei Überstrom 

in Phase

23

Watt

63

fest unverzögert bei Überstrom in 

Phase, 1

24

VA

64

fehlerhaftes/fehlendes 

Bemessungsstrommodul

25

VAR

65

rückwärts, Energie

26

Energiebedarf

66

fest unverzögert bei Überstrom in 

Phase, 2

27

VA-Bedarf

67

rückwärts Phase

28

Var-Bedarf

68

rückwärts Sequenz

29

Langzeitmittelwert Strom

69

Stromverlust Phase

30

Klirrfaktor

70

Spannungsverlust Phase

31

Anzahl Schaltspiele

71

Alarm aktiv

32

Service kontaktieren

72

schlechter Rahmen

33

Steuerung über Kommunikation

73

Phasenstromwerte bei Ansprechen

34

Unstimmigkeit Kontakte

74

Wiedereinschaltsperre

35

Ausfall Leistungsschalter

75

Einschaltstromauslöser

36

Betriebszeit überschritten

76

fest unverzögert bei Überstrom in 

Phase, 3

37

Überwachung Spule

77

Sollwertfehler

38

Programmierbare Logik

78

Übertemperatur

39

Diagnosewarnung 1

79

Zubehörbus

Ursache der Statusänderung (Forts.)

Code

Definition

Code Definition

80

Lange Verzögerung neutral Überstrom

122

keine Synchr. bei Überspannung

81

Externer Zustand 2

123

Reversierschutz

82

Historiedaten

124

Nulldrehzahl

83

Externer Zustand 3

125

Zeit zwischen Starts

84

Erdschluss (unverzögert oder verzögert)

126

Quelle 1

85

Erdschluss (unverzögert oder verzögert)

127

Quelle 2

86

Externer Zustand 4

128

Start

87

Externer Zustand 5

129

manuell

88

Externer Zustand 6

130

Synchronisation

89

Externer Zustand 7

131

Starts/Stunde

90

Externer Zustand 8

132

bevorzugte Quelle

91

Externer Zustand 9

133

Plant exerciser

92

Mehrfache externe Zustände

134

Überspannung Neutral Masse

93

Temperatur Motorlager

135

Sicherheitsverriegelung

94

Temperatur Lastlager

136

Echtzeituhr

95

Hilfstemperatur

137

Hohe Schwebespannung

96

Temperatur Wicklung

138

Auslösung blockiert

97

Lokale Temperatur

139

unvollständige Sequenz

98

Externe Temperatur

140

Ursache: nicht zutreffend 

(keine)

99

Gerollte Phase

141

Auslöseposition

100

Pro Einheit Spannung

142

transiente Spannung

101

Empfindlich

143

manipulieren

102

Stromlos machen

144

Widerstands-Temperaturfühler

103

Unempfindlich

145

differenzierend

104

Zeitverzögert empfindlich

146

Frequenz außerhalb Bereich

105

LS flattert

147

Sensor-Fehlanpassung

106

Fehler im Subnetz

148

Hilfsschalter prüfen

107

Lernen

149

Überstrom

108

Offline

150

zeitverzögerte Watt-VAR

109

Test

151

Überstrom Watt-VAR

110

Stau

152

Leistung

111

Unterlast

153

Instandhaltungsmodus

112

Verzögerung Masse Überstrom

154

Fehler LS-Mechanismus

113

Kalibrierung

155

Automatische 

Wiedereinschaltsperre

114

Notfall

156

Getrennt-Stellung

115

Drehmomentgrenze

157

Netzkurzschluß

116

Verzögerung

Reserviert 158 … 2043

117

Spannungsabfall

118

Spannungsanstieg

2044

produktspezifischer Code 2044

119

Programmierfehler

2045

produktspezifischer Code 2045

120

keine Syhnchr. auf Phase

2046

produktspezifischer Code 2046

121

keine Synchr. auf Frequenz

2047

produktspezifischer Code 2047

Summary of Contents for PMINT

Page 1: ...ircuit breaker position switch connector TB2 4 PROFIBUS DP RS 485 connector 4 Section 5 Switches and indicator LEDs 4 PROFIBUS SYSFAULT LED red 4 PROFIBUS BUSFAULT LED red 4 INCOM connection Tx LED gr...

Page 2: ...le 4 PROFIBUS DP LED States 4 Table 5 Remote Enable Switch 5 Table 6 CFG Data Formats 5 Table 7 Cyclic Data Exchange Command Format 0 5 Table 8 Cyclic Data Exchange Monitoring Format 0 6 Table 9 Cycli...

Page 3: ...cover all of the details or variations of the equipment for its storage delivery installation checkout safe operation or maintenance When mounting the PMINT verify that a C Shape 32 mm or Standard 35...

Page 4: ...he RxD TxD data lines is critically important Refer to Table 3 Table 3 PROFIBUS DP RS 485 Connector Pin Outs Pin No Input Output Signal 1 Shield a 2 M24 ground for 24V output a 3 RxD TxD P B dataline...

Page 5: ...ed as bit 0 is bit 0 of byte 0 bit 8 is bit 0 of byte 1 Cyclic data exchange monitoring structure formats Monitoring structure Formats 0 4 for cyclic data exchange returned from the PMINT to the PROFI...

Page 6: ...unit not yet established 15 Load rejection 1 Primary status alarm cause 26 Table 8 Cyclic Data Exchange Monitoring Format 1 Byte s Data Type Description Resolution 0 Unsigned8 State 0 byte 0 of monito...

Page 7: ...r when the PMINT returns a high priority cyclic data exchange Table 12 DP V0 Unit Diagnostics Definitions Byte Bit s Value Description 7 08H Header device related diagnostics length 8 bytes 8 7 0 81H...

Page 8: ..._supp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 Bit Time MaxTsdr_19 2 60 Bit Time MaxTsdr_31 25 60 Bit Time MaxTsdr_45 45 60 Bit Time MaxTsdr_93 75 60 Bit Tim...

Page 9: ...it_Diag_Bit 0034 Data Object 10 invalid Unit_Diag_Bit 0035 Data Object 11 invalid Unit_Diag_Bit 0036 Data Object 12 invalid Unit_Diag_Bit 0037 Data Object 13 invalid Unit_Diag_Bit 0038 Data Object 14...

Page 10: ...isted in Table 14 The definition of the cause of status word pertaining to the primary status is listed in Table 15 Table 13 Primary Status Code Definitions Code Definition Code Definition 0 Unknown 1...

Page 11: ...5 Making current release 36 Operation time exceeded 76 Fixed instantaneous phase overcurrent 3 37 Coil supervision 77 Set points error 38 Programmable logic 78 Overtemperature 39 Diagnostic warning 1...

Page 12: ...installation and use Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH nderungen vorbehalten Subject to alterations 04 10 AWB1230 1621 Z8896 Moon Doku Heng Printed in USA 04 10 04...

Page 13: ...ung TB1 4 INCOM Schalterposition Steckverbinder Positionsschalter TB2 4 PROFIBUS DP RS 485 Stecker 4 Abschnitt 5 Schalter und Anzeigen 4 PROFIBUS SYSFAULT LED rot 4 PROFIBUS BUSFAULT LED rot 4 Leuchte...

Page 14: ...abelle 4 Leuchte PROFIBUS DP 4 Tabelle 5 Schalter Fernaktivierung 5 Tabelle 6 Formate der Konfigurationsdaten 5 Tabelle 7 Befehl Zyklischer Datenaustausch Format 0 5 Tabelle 8 Kontrolle Zyklischer Dat...

Page 15: ...altung auftreten k nnen oder alle Details und Variationen der beschriebenen Betriebsmittel ab Das PMINT Modul kann auf einer C Schiene 32 mm oder einer Standard DIN Hutschiene 35 7 5 mm montiert werde...

Page 16: ...Klemme Nr Ein Ausgangssignal 1 INCOM Datennetz 2 INCOM Datennetz 3 INCOM Schirm 4 Positionsschalter 1 Leistungsschalter 5 Positionsschalter 2 Leistungsschalter 6 Positionsschalter GND Masse Leistungss...

Page 17: ...giewert wird aber mit einer h heren Aufl sung geliefert Befehlsstruktur Format 0 f r den zyklischen Datenaustausch Die von dem PMINT Modul unterst tzte Befehlsstruktur Format 0 f r den zyklischen Date...

Page 18: ...tion zu Ausl seeinheit noch nicht aufgebaut 15 Lastabwurf 1 Zustand prim r Alarm Ursache 26 Tabelle 8 Kontrolle Zyklischer Datenaustausch Format 1 Byte Datentyp Beschreibung Aufl sung 0 vorzeichenlos8...

Page 19: ...m PROFIBUS Master vermittelt wenn das PMINT Modul einen zyklischen Datenaustausch mit hoher Priorit t zur ck meldet Tabelle 12 Diagnosebits der DP V0 Einheit Byte Bit s Wert Beschreibung 7 08H Header...

Page 20: ...upp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 Bit Time MaxTsdr_19 2 60 Bit Time MaxTsdr_31 25 60 Bit Time MaxTsdr_45 45 60 Bit Time MaxTsdr_93 75 60 Bit Time...

Page 21: ...Unit_Diag_Bit 0034 Data Object 10 invalid Unit_Diag_Bit 0035 Data Object 11 invalid Unit_Diag_Bit 0036 Data Object 12 invalid Unit_Diag_Bit 0037 Data Object 13 invalid Unit_Diag_Bit 0038 Data Object 1...

Page 22: ...ng des Worts das die Ursache f r den prim ren Status beschreibt ist in Tabelle 15 aufgef hrt Tabelle 13 Statuscodes prim rseitig Code Definition Code Definition 0 Unbekannt 19 Alarm Phase A 1 ffnen 20...

Page 23: ...schaltstromausl ser 36 Betriebszeit berschritten 76 fest unverz gert bei berstrom in Phase 3 37 berwachung Spule 77 Sollwertfehler 38 Programmierbare Logik 78 bertemperatur 39 Diagnosewarnung 1 79 Zub...

Page 24: ...lation und Verwendung Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH nderungen vorbehalten Subject to alterations 04 10 AWB1230 1621 Z8896 Moon Doku Heng Printed in USA 04 10 04...