PMINT—PROFIBUS DP translator

module—installation and use

 

EATON CORPORATION

 www.moeller.net/en/support 

Table 15.  Cause-of-Status Code Definitions

Code

Definition

Code Definition

0

Unknown

40

Diagnostic failure #1

1

Normal operating mode

41

Low battery

2

External condition #1

42

Multiple causes

3

Instantaneous phase 

overcurrent

43

Diagnostic warning #2

4

Instantaneous ground 

overcurrent

44

Diagnostic warning #3

5

Instantaneous neutral 

overcurrent

45

Diagnostic warning #4

6

Instantaneous residual 

overcurrent

46

Diagnostic warning #5

7

Phase inverse-time 

overcurrent

47

Diagnostic warning #6

8

Ground inverse-time 

overcurrent

48

Diagnostic warning #7

9

Neutral inverse-time 

overcurrent

49

Diagnostic warning #8

10

Residual inverse-time 

overcurrent

50

Diagnostic warning #9

11

Overvoltage

51

Diagnostic warning #10

12

Undervoltage

52

Diagnostic failure #2

13

Auxiliary overvoltage

53

Diagnostic failure #3

14

Auxiliary undervoltage

54

Diagnostic failure #4

15

Underfrequency

55

Diagnostic failure #5

16

Overfrequency

56

Diagnostic failure #6

17

Current unbalance

57

Diagnostic failure #7

18

Voltage unbalance

58

Diagnostic failure #8

19

Apparent power factor

59

Diagnostic failure #9

20

Displacement power factor

60

Diagnostic failure #10

21

Zone interlock phase

61

Long delay phase overcurrent

22

Zone interlock ground

62

Short delay phase overcurrent

23

Watt

63

Fixed instantaneous phase overcurrent #1

24

VA

64

Bad/missing rating plug

25

VAR

65

Reverse power

26

Power demand

66

Fixed instantaneous phase overcurrent #2

27

VA demand

67

Reverse phase

28

Var demand

68

Reverse sequence

29

Current demand

69

Phase current loss

30

Total harmonic distortion

70

Phase voltage loss

31

Operations count

71

Alarm active

32

Contact maintenance

72

Bad frame

33

Control via communications

73

Phase currents near pickup

34

Contact disagreement

74

Lockout

35

Breaker failure

75

Making current release

36

Operation time exceeded

76

Fixed instantaneous phase overcurrent #3

37

Coil supervision

77

Set points error

38

Programmable logic

78

Overtemperature

39

Diagnostic warning #1

79

Accessory bus

Cause-of-Status Code Definitions (continued)

Code

Definition

Code Definition

80

Long delay neutral overcurrent

122

Failed to sync on voltage

81

External condition #2

123

Anti-backspin

82

Historical data

124

Zero speed

83

External condition #3

125

Time between starts

84

Ground fault (instantaneous or delay)

126

Source 1

85

Earth fault (instantaneous or delay)

127

Source 2

86

External condition #4

128

Start

87

External condition #5

129

Manual

88

External condition #6

130

Synchronizing

89

External condition #7

131

Starts per hour

90

External condition #8

132

Preferred source

91

External condition #9

133

Plant exerciser

92

Multiple external conditions

134

Neutral ground overvoltage

93

Motor bearing temperature

135

Safety interlock

94

Load bearing temperature

136

Real-time clock

95

Auxiliary temperature

137

High floating voltage

96

Winding temperature

138

Trip blocked

97

Local temperature

139

Incomplete sequence

98

External temperature

140

Cause N/A (none)

99

Rolled phase

141

Trip position

100

Per unit voltage

142

Voltage transient

101

Sensitive

143

Tamper

102

De-energize

144

RTD

103

Non sensitive

145

Differential

104

Time delayed sensitive

146

Frequency out of range

105

Breaker pumping

147

Sensor mismatch

106

Sub-network malfunction

148

Check aux. switch

107

Learning

149

Overcurrent

108

Offline

150

Time delayed Watt-VAR

109

Test

151

Overcurrent Watt-VAR

110

Jam

152

Power

111

Underload

153

Maintenance Mode

112

Delay ground overcurrent

154

Breaker mechanism fault

113

Calibration

155

Automatic reclose lockout

114

Emergency

156

Disconnect position

115

Torque limit

157

Shunt fault problem

116

Deceleration

Reserved 158 … 2043

117

Voltage sag

118

Voltage swell

2044

Product specific code 2044

119

Programming error

2045

Product specific code 2045

120

Failed to sync on phase

2046

Product specific code 2046

121

Failed to sync on frequency

2047

Product specific code 2047

Summary of Contents for PMINT

Page 1: ...ircuit breaker position switch connector TB2 4 PROFIBUS DP RS 485 connector 4 Section 5 Switches and indicator LEDs 4 PROFIBUS SYSFAULT LED red 4 PROFIBUS BUSFAULT LED red 4 INCOM connection Tx LED gr...

Page 2: ...le 4 PROFIBUS DP LED States 4 Table 5 Remote Enable Switch 5 Table 6 CFG Data Formats 5 Table 7 Cyclic Data Exchange Command Format 0 5 Table 8 Cyclic Data Exchange Monitoring Format 0 6 Table 9 Cycli...

Page 3: ...cover all of the details or variations of the equipment for its storage delivery installation checkout safe operation or maintenance When mounting the PMINT verify that a C Shape 32 mm or Standard 35...

Page 4: ...he RxD TxD data lines is critically important Refer to Table 3 Table 3 PROFIBUS DP RS 485 Connector Pin Outs Pin No Input Output Signal 1 Shield a 2 M24 ground for 24V output a 3 RxD TxD P B dataline...

Page 5: ...ed as bit 0 is bit 0 of byte 0 bit 8 is bit 0 of byte 1 Cyclic data exchange monitoring structure formats Monitoring structure Formats 0 4 for cyclic data exchange returned from the PMINT to the PROFI...

Page 6: ...unit not yet established 15 Load rejection 1 Primary status alarm cause 26 Table 8 Cyclic Data Exchange Monitoring Format 1 Byte s Data Type Description Resolution 0 Unsigned8 State 0 byte 0 of monito...

Page 7: ...r when the PMINT returns a high priority cyclic data exchange Table 12 DP V0 Unit Diagnostics Definitions Byte Bit s Value Description 7 08H Header device related diagnostics length 8 bytes 8 7 0 81H...

Page 8: ..._supp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 Bit Time MaxTsdr_19 2 60 Bit Time MaxTsdr_31 25 60 Bit Time MaxTsdr_45 45 60 Bit Time MaxTsdr_93 75 60 Bit Tim...

Page 9: ...it_Diag_Bit 0034 Data Object 10 invalid Unit_Diag_Bit 0035 Data Object 11 invalid Unit_Diag_Bit 0036 Data Object 12 invalid Unit_Diag_Bit 0037 Data Object 13 invalid Unit_Diag_Bit 0038 Data Object 14...

Page 10: ...isted in Table 14 The definition of the cause of status word pertaining to the primary status is listed in Table 15 Table 13 Primary Status Code Definitions Code Definition Code Definition 0 Unknown 1...

Page 11: ...5 Making current release 36 Operation time exceeded 76 Fixed instantaneous phase overcurrent 3 37 Coil supervision 77 Set points error 38 Programmable logic 78 Overtemperature 39 Diagnostic warning 1...

Page 12: ...installation and use Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH nderungen vorbehalten Subject to alterations 04 10 AWB1230 1621 Z8896 Moon Doku Heng Printed in USA 04 10 04...

Page 13: ...ung TB1 4 INCOM Schalterposition Steckverbinder Positionsschalter TB2 4 PROFIBUS DP RS 485 Stecker 4 Abschnitt 5 Schalter und Anzeigen 4 PROFIBUS SYSFAULT LED rot 4 PROFIBUS BUSFAULT LED rot 4 Leuchte...

Page 14: ...abelle 4 Leuchte PROFIBUS DP 4 Tabelle 5 Schalter Fernaktivierung 5 Tabelle 6 Formate der Konfigurationsdaten 5 Tabelle 7 Befehl Zyklischer Datenaustausch Format 0 5 Tabelle 8 Kontrolle Zyklischer Dat...

Page 15: ...altung auftreten k nnen oder alle Details und Variationen der beschriebenen Betriebsmittel ab Das PMINT Modul kann auf einer C Schiene 32 mm oder einer Standard DIN Hutschiene 35 7 5 mm montiert werde...

Page 16: ...Klemme Nr Ein Ausgangssignal 1 INCOM Datennetz 2 INCOM Datennetz 3 INCOM Schirm 4 Positionsschalter 1 Leistungsschalter 5 Positionsschalter 2 Leistungsschalter 6 Positionsschalter GND Masse Leistungss...

Page 17: ...giewert wird aber mit einer h heren Aufl sung geliefert Befehlsstruktur Format 0 f r den zyklischen Datenaustausch Die von dem PMINT Modul unterst tzte Befehlsstruktur Format 0 f r den zyklischen Date...

Page 18: ...tion zu Ausl seeinheit noch nicht aufgebaut 15 Lastabwurf 1 Zustand prim r Alarm Ursache 26 Tabelle 8 Kontrolle Zyklischer Datenaustausch Format 1 Byte Datentyp Beschreibung Aufl sung 0 vorzeichenlos8...

Page 19: ...m PROFIBUS Master vermittelt wenn das PMINT Modul einen zyklischen Datenaustausch mit hoher Priorit t zur ck meldet Tabelle 12 Diagnosebits der DP V0 Einheit Byte Bit s Wert Beschreibung 7 08H Header...

Page 20: ...upp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 Bit Time MaxTsdr_19 2 60 Bit Time MaxTsdr_31 25 60 Bit Time MaxTsdr_45 45 60 Bit Time MaxTsdr_93 75 60 Bit Time...

Page 21: ...Unit_Diag_Bit 0034 Data Object 10 invalid Unit_Diag_Bit 0035 Data Object 11 invalid Unit_Diag_Bit 0036 Data Object 12 invalid Unit_Diag_Bit 0037 Data Object 13 invalid Unit_Diag_Bit 0038 Data Object 1...

Page 22: ...ng des Worts das die Ursache f r den prim ren Status beschreibt ist in Tabelle 15 aufgef hrt Tabelle 13 Statuscodes prim rseitig Code Definition Code Definition 0 Unbekannt 19 Alarm Phase A 1 ffnen 20...

Page 23: ...schaltstromausl ser 36 Betriebszeit berschritten 76 fest unverz gert bei berstrom in Phase 3 37 berwachung Spule 77 Sollwertfehler 38 Programmierbare Logik 78 bertemperatur 39 Diagnosewarnung 1 79 Zub...

Page 24: ...lation und Verwendung Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH nderungen vorbehalten Subject to alterations 04 10 AWB1230 1621 Z8896 Moon Doku Heng Printed in USA 04 10 04...

Reviews: