Umsetzermodul PMINT—PROFIBUS-DP
— Installation und Verwendung
EATON CORPORATION
www.moeller.net/de/support
;Reaction_Delay_12M = 0 ; Bit Time
;End_Physical_Interface
;==============================================
; Slave-Specification
;==============================================
Freeze_Mode_supp = 1 ;1=Supported
Sync_Mode_supp = 1 ;1=Supported
Auto_Baud_supp = 1 ;1=Supported
Set_Slave_Add_supp = 0 ;0=NotSupported (INCOM address setting)
User_Prm_Data_Len = 3
User_Prm_Data = 0x00,0x00,0x00
Max_User_Prm_Data_Len = 3
;Ext_User_Prm_Data_Const(0) = 0x00,0x00,0x00
Min_Slave_Intervall = 1 ;Min interval between two slave list cycles
; Time base: 100us
Modular_Station = 1 ;0=Compact, 1=Modular device
Max_Module = 2 ;
Max_Input_Len = 32 ;Circuit Breaker Profile input, format 4
Max_Output_Len = 2 ;Circuit Breaker Profile output
Max_Data_Len = 34
Fail_Safe = 0 ;0=DataMsg with data=0 in CLEAR mode
Modul_Offset = 0 ;Slot number to appear in Cfg tool
Slave_Family = 2@CircuitBreaker@Digitrip
Diag_Update_Delay = 0
Fail_Safe_required = 0
;Info_Text = “ “ ;Optional additional info about device
Max_Diag_Data_Len = 14 ;6 Bytes Mandatory by PROFIBUS
Unit_Diag_Bit(0024) = “No Communications with DigiTrip”
Unit_Diag_Bit(0025) = “Data Object 1 invalid”
Unit_Diag_Bit(0026) = “Data Object 2 invalid”
Unit_Diag_Bit(0027) = “Data Object 3 invalid”
Unit_Diag_Bit(0028) = “Data Object 4 invalid”
Unit_Diag_Bit(0029) = “Data Object 5 invalid”
Unit_Diag_Bit(0030) = “Data Object 6 invalid”
Unit_Diag_Bit(0031) = “Data Object 7 invalid”
Unit_Diag_Bit(0032) = “Data Object 8 invalid”
Unit_Diag_Bit(0033) = “Data Object 9 invalid”
Unit_Diag_Bit(0034) = “Data Object 10 invalid”
Unit_Diag_Bit(0035) = “Data Object 11 invalid”
Unit_Diag_Bit(0036) = “Data Object 12 invalid”
Unit_Diag_Bit(0037) = “Data Object 13 invalid”
Unit_Diag_Bit(0038) = “Data Object 14 invalid”
Unit_Diag_Bit(0039) = “Remote Open/Closed Not Enabled”
Unit_Diag_Bit(0040) = “EEROM Error Alarm”
Unit_Diag_Bit(0041) = “RAM Error Alarm”
Unit_Diag_Bit(0042) = “Setpoints Error Alarm”
Unit_Diag_Bit(0043) = “Watchdog Alarm”
Unit_Diag_Bit(0044) = “Check Aux Switch Alarm”
Unit_Diag_Bit(0045) = “Breaker Mechanism Fault”
Unit_Diag_Bit(0046) = “Breaker Shunt Trip Problem”
Unit_Diag_Bit(0047) = “Operations Count Alarm”
Unit_Diag_Bit(0048) = “Earth Fault Alarm”
Unit_Diag_Bit(0049) = “Low Power Factor Alarm”
Unit_Diag_Bit(0050) = “Total Harmonic Distortion Alarm”
Unit_Diag_Bit(0051) = “Frequency Out Of Bounds Alarm”
Unit_Diag_Bit(0052) = “Historic Trip Occurred”
Unit_Diag_Bit(0053) = “Breaker In Maintenance Mode”
;******************************************************
;** Slave related Key Words for DP extensions **
;******************************************************
DPV1_Slave = 0
;C1_Read_Write_supp = 1
;C2_Read_Write_supp = 1
;C1_Max_Data_Len = 22
;C2_Max_Data_Len = 48
;C1_Response_Timeout = 50 ;in units of 10ms, optional
;C2_Response_Timeout = 50 ;in units of 10ms, optional
;C1_Read_Write_required = 0
;C2_Read_Write_required = 0
;C2_Max_Count_Channels = 1
;Max_Initiate_PDU_Length = 52
;Diagnostic_Alarm_supp = 0
;Process_Alarm_supp = 0
;Pull_Plug_Alarm_supp = 0
;Status_Alarm_supp = 0
;Update_Alarm_supp = 0
;Manufacturer_Specific_Alarm_supp = 0
;Extra_Alarm_SAP_supp = 0
;Alarm_Sequence_Mode_Count = 0
;Alarm_Type_Mode_supp = 0
;Diagnostic_Alarm_required = 0
;Process_Alarm_required = 0
;Pull_Plug_Alarm_required = 0
;Status_Alarm_required = 0
;Update_Alarm_required = 0
;Manufacturer_Specific_Alarm_required = 0
;DPV1_Data_Types = 0
;WD_Base_1ms_supp = 1
;Check_Cfg_Mode = 0
;Publisher_supp = 0