12
Eaton PDI JCOMM Enclosure Installation and Operation Manual P-164001107—Rev 01
Table 2. JCOMM Installation Kit Contents (Continued)
Option
Part Description
Additional Part Information or Quantity
(1) Main or
subdistribution circuit
cable kit
Main/subdistribution circuit CT cable harness:
connectorized cable Qty 4 for split-core CTs
(ABCN) and Qty 1 Ground split-core CT (G), in
lengths of 5, 10, 15, or 20 ft.
Main/subdistribution feed CT: split-core CT, 5A -
250A (ABCN)
4
Main/subdistribution feed CT: ground circuit,
split-core CT, 5A (G)
1
Voltage/Power Cables: 0-2 Voltage/Power Cables
Optional Eaton power/
voltage cable
Power/voltage cable, with inline 1A 1000V
cartridge fuses, in lengths of 5, 10, 15, or 20 ft.
44..22
IInnssttaallll tthhee JJC
CO
OM
MM
M EEnncclloossuurree
Severe or fatal injury can result from electrical shock during contact with high voltage conductors, monitoring
PCBs, or similar equipment.
Disconnect power before drilling holes, attaching conduit, and attaching JCOMMs to walls, PDUs, RPPs, or
other power distribution equipment.
Use Lock Out/Tag Out procedures.
Wear suitable personal protective clothing and use protective equipment for performing mechanical and
electrical installations.
Leave ample space for attaching and routing wires.
The customer provides attachment hardware for mounting JCOMMs.
Table 3. JCOMM Enclosure Installation Parts
JCOMM with WaveStar Color Monitor (various PNs depending on features)
JCOMM with no display (various PNs depending on features)
A JCOMM enclosure has four slots for mounting on a wall (
):
1.
Mark (4) mounting holes on wall nearby equipment using the enclosed Mylar template. Place a level
against the top of the drilling marks to make sure the holes are level.
2.
Drill ¼-inch bolt holes at the target location.
3.
Hang the enclosure to make sure the enclosure will be level and securely mounted.
4.
JCOMM has 1- and 2-inch knockouts on the top, bottom, and both sides of the unit for attaching conduit.
When mounting a JCOMM to the top of an RPP or PDU, use conduit and other hardware to anchor the
JCOMM to the unit.
Summary of Contents for PDI JCOMM
Page 1: ...p n P 164001107 Revision 01 Installation and Operation Manual Eaton PDI JCOMM Enclosure...
Page 4: ......
Page 12: ...2 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Safety...
Page 44: ...34 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Operation...
Page 46: ...36 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Service...
Page 48: ...38 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Bibliography...
Page 50: ...P 16400110701 P 164001107 01...