![background image](http://html1.mh-extra.com/html/eaton/nrx-digitrip-1150i/nrx-digitrip-1150i_instruction-leaflet_524886012.webp)
j
All event buffers and waveforms are stored in a serial sequence retaining the most recent data.
k
Data buffers from the event are retained independent of whether waveform data was or could be captured at the time of the event.
l
Data is approximate for most styles of CAM module. Consult the specific CAM module literature for more information.
m
Discrete logging data is not stored and not viewable in the display module.
n
Prime and Basic events share the same memory space. The maximum number stored will dependent upon the maximum number received of each event.
Table 9. Event Recording (continued)
Data
Number of
Events Saved
in Digitrip
Trip Unit
j
Number of
Events Saved
in CAM
Modules
jl
Data Captured
Voltage and
Current Waveforms
Captured in
Digitrip Trip Unit
j
Voltage and
Current Waveforms
Captured in CAM
Modules
jl
Alarm (Prime)
20
k
100 max
n
3
8
Long Delay Pick-up
Time Stamp
Status: Primary, Secondary and Cause
Currents: IA, IB, IC, IN, IB
Voltage: VAB, VBC, VCA, VAN, VBN, VCN
Power: Watts, VAR, VA
THD: IA, IB, IC
Demand: IA, IB, IC, IN, Watts, VAR, VA
Frequency
Operations Count
Temperature
Power Factor
IA, IB, IC, IN, IB,
VAB, VBC, VCA
6 cycles
IA, IB, IC, IN, IG,
VAB, VBC, VCA
6 cycles
Current Unbalance
Ground Fault
Incomplete Contact Close
High Load
Neutral Current
Phase Rotation
Over Voltage (Line to Line)
Under Voltage (Line to Line)
Voltage Unbalance (Line to Line)
Over Frequency
Under Frequency
Low Power Factor
Reverse Power
Apparent Power Demand
Power Demand
THD
Alarm (Basic)
Time Stamp
Status: Primary, Secondary and Cause
_
_
Calibration Alarm
Setpoint Fault
RAM Fault
ROM Fault
RTC Error
NV Memory Error
Watchdog Timer Operation
ADC Calibration Error
Long Delay Pick-up (test mode)
Ground Fault (test mode)
Trip Actuator Fault
Operations Count
Low Control Voltage
Trend Logging
0
m
50
Forward Active Energy
Reverse Active Energy
Apparent Energy
_
_
Energy Log
Time Adjustment
20
200
Previous Time
New Time
_
_
Real Time Clock Change
Effective September 2013
Instructional Leaflet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
12