Instructional Literature 

IL0104001E 

Effective January 2017

Withstand test results

The high-potential withstand tests provide information on the 
dielectric condition of the recloser and the vacuum integrity of the 
interrupters.

If the recloser passes the closed-contacts tests (Tests 1 and 2), but 
fails the open-contacts test (Test 3), the cause is likely to be in the 
interrupter assembly. Retest each phase individually to determine 
the failed phase or phases.

If the recloser does not pass Tests 1, 2, or 3, contact an authorized 
service center or your Cooper Power Systems representative.

Test results for NOVA i reclosers equipped with the internal 
voltage sensing option will be influenced by the source-to-ground 
connected sensing resistor, especially if dc high-potential testing is 
performed.

Inspection of nova i module

If the NOVA i module was exposed to an external flashover, an 
inspection process is recommended to assure proper operation of 
the recloser. Should the NOVA i exhibit external flashover 
attributes (carbon tracking or discoloration), the following proce-
dure is recommended to restore the encapsulation back to its 
original condition:

1. 

Bypass and remove the recloser from service as described 

in this manual.

2. 

Inspect module for damage to the terminals. Remove any 

damaged terminals and replace.

3. 

Inspect module for damage to the module rods. If there is 

damage to the module rods, the conductor module must be 
replaced.

4. 

Verify through careful inspection that there is no damage to 

the housing that could inhibit proper operation. Check the 
integrity of the lifting lugs.

5. 

Clean the damaged module with isopropyl alcohol and a 

scratch-free, nylon scouring pad to remove any carbon 
deposit.

6. 

Confirm the dielectric strength of the module by performing 

high-potential withstand testing. Confirm both 
phase-to-ground and phase-to-phase conditions. See the 
High-Potential Withstand Testing section of this manual.

Troubleshooting

If the NOVA i recloser does not perform as described in the 
OPERATION section of this manual, the following information may 
assist in troubleshooting:

Unit will not close

•  Make sure the yellow manual open handle is completely up.

•  Check all cables for proper connection.

•  Verify that the control has power.

•  Upon loss of ac power, check recloser control battery level.

•  Check the fusing on the dc-to-dc converter board located in the 

control cabinet.

Unit will not open electrically

•  Check all cables for proper connection.

•  Verify that the control has power.

•  Check the fusing on the dc-to-dc converter board located in the 

control cabinet.

 

Summary of Contents for NOVA 15i

Page 1: ...Installation Form 6 FXD control settings Accessories Auxiliary switch Terminals Pole mounting hanger Arrester mounting brackets Substation mounting frame Service information Service requirements Freq...

Page 2: ...s situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury CAUTION Indicat...

Page 3: ...oser and inspect it thoroughly for damage incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the...

Page 4: ...100 9 4 kV 50 kV 45 kV 125 kV 100 16 4 kV 60 kV 50 kV 170 kV 100 23 0 kV 70 kV 60 kV Table 2 Current ratings A Description 15 kV 27 kV 38 kV Rated continuous current Short circuit current Symmetrical...

Page 5: ...Terminal to terminal 1180 79 Lower terminal to ground earth 671 45 NOVA 27i Terminal to terminal 1473 55 Lower terminal to ground earth 951 35 NOVA 38i Terminal to terminal 1763 46 Lower terminal to g...

Page 6: ...1E Effective January 2017 Figure 3 NOVA 15i recloser dimensions with 3 integrated voltage sensor option in load side Note All dimensions are mm Dimensions shown are approximate Terminal connectors Ter...

Page 7: ...converter board also houses voltage monitoring and conditioning circuits that protect the battery from failure and provide trip close operations without ac power In the absence of ac power to the ele...

Page 8: ...ices when making hitches and lifting the equipment Lift the unit smoothly and do not allow the unit to shift This equipment is not intended to protect human life Follow all locally approved procedures...

Page 9: ...ded on both sides Hazardous voltage Solidly ground all equipment Failure to comply can result in death severe personal injury and equipment damage WARNING Equipment Damage Do not adjust or rotate bush...

Page 10: ...of a grounding mat may be required depending upon the local safety regulations defining the permissible step and touch potential levels Consult local regulations for proper grounding procedures In pol...

Page 11: ...the equipment It is recommended to use a minimum of 50 sq mm copper wire for the pole ground connection to the recloser 2 Any ground wire of the equipment is not allowed to be connected to the neutra...

Page 12: ...quipment It is recommended to use a minimum of 50 sq mm copper wire for the pole ground connection to the recloser IMPORTANT All external inputs to the control must be routed within 203 mm of their co...

Page 13: ...his equipment is not intended to protect human life Follow all locally approved procedures and safety practices when installing or operating this equipment Failure to comply can result in death severe...

Page 14: ...tor located on the mechanism housing Provide a good electrical ground connection to the control cabinet ground Note Painted surfaces of the mechanism housing may prevent a ground connection to the rec...

Page 15: ...voltage sensor Energize recloser and confirm the voltage outputs in the control When the recloser is energized the output of the voltage sensor in 6 V based upon the Form 6 FXD control s input impeda...

Page 16: ...for a Wye connection Also the Phantom Phase feature must be disabled Refer to Service Information S280 70 4 for more information on programming the Form 6 FXD control Figure 16 Form 6 FXD control syst...

Page 17: ...tion to copper wires to optimize the electrical connection Anti oxide coatings for temporary protection of wire brushed aluminum cable connections to flat pad terminals must be maintained at intervals...

Page 18: ...ing brackets The arrester mounting bracket accessory see Figure 18 can be bolted to the recloser frame and pole mounting hanger for the addition of inboard and outboard arresters The arresters are not...

Page 19: ...vailable for substation mounting applications Figure 19 Dimensions of NOVA i recloser with substation mounting frame accessory Terminal options A Eyebolt 1 0 500 mcm 89 Cable range 630 A maximum Eyebo...

Page 20: ...gs settings and interface options on the recloser nameplate see Figure 6 are correct for the planned testing 2 Test electrical open and close operation Close and open the recloser contacts using the m...

Page 21: ...0 seconds TEST 2 1 Close the recloser contacts 2 Ground the recloser 3 Ground Phase A terminal 2 and Phase C terminal 6 4 Apply proper test voltage to Phase B terminal 3 5 The recloser should withstan...

Page 22: ...k to its original condition 1 Bypass and remove the recloser from service as described in this manual 2 Inspect module for damage to the terminals Remove any damaged terminals and replace 3 Inspect mo...

Page 23: ...S3 COM N O R1 C Open COM N C 52a MS1 R1 A VTC Pull Up 2 R1 E Close COM N O 52b MS2 R1 B VTC Pull Up 1 H2 H1 R1 U R1 V LEGEND SYMBOL DESCRIPTIO N AB Actuator Circuit Board AS Auxiliary Switch 3 Stage C...