background image

16

Effective January 2017

NOVA

®

 15i, NOVA 27i, and NOVA 38i; Three-phase

microprocessor-controlled; installation and operation
instructions (S280-43-1)

Instructional Literature 

IL0104001E

Accessories

Auxiliary switch

A three-stage auxiliary switch can be provided as an accessory. 
Each stage has two independent contacts that permit any desired 
combination of “a” (follow state of recloser contacts) and “b” 
(opposite recloser contacts) positions. The switch contacts are 
insulated for 600 V and have a continuous current rating of 10 A. 
Their interrupting ratings are shown in Table 7.

Terminals

The standard terminal is a 2-hole flat-pad terminal rated 630 A. An 
eyebolt, 1/0–500 mcm (630 A), eyebolt 4/0–1000 mcm (800 A), and 
4-hole flat-pad terminals, are available as an accessory (see Figure 
17).

The eyebolt and fixed-pad terminals are made of copper alloys. 
Cooper Power Systems recommends terminal connection to 
copper wires to optimize the electrical connection.

Anti-oxide coatings for temporary protection of wire-brushed 
aluminum cable connections to flat-pad terminals must be 
maintained at intervals determined by the customer based on load 
current, climate, and other installation conditions.

Eyebolt terminals are recommended for copper conductors only.

Pole-mounting hanger

A pole-mounting hanger (see Figure 17), which bolts directly to the 
recloser frame, is available for pole-mounting installation.

 

 

Note: 

All dimensions are mm. 

Dimensions shown are approximate.

637

POLE

617  

Min.

B

290

POLE

779

POLE

1085

Terminal options 

A

Eyebolt, 1/0 - 500 mcm 

89

Cable range (630 A max.) 

 Eyebolt, 4/0 - 1000 mcm 

111

Cable range (800 A max.) 

Flat Pad, 2-hole  

119

(630 A max.) 

 Flat Pad, 4-hole  

121

(800 A max.) 

Table 7

Auxiliary switch interrupting ratings

Inductive

Non-Inductive

Non-Inductive

Inductive

ac
(A)  

ac dc 

dc

Volts

(A) (A) 

(A) 

24 – 

15.0 

48 – 

7.5 

120 80 

– 

125 – 

1.5 

240 60 

– 

250 

– 

– 

60 

– 

30 

– – 

0.45 

20.0

10.0

2.0

0.5

Figure 17.

 

Dimensions of NOVA i recloser with pole-mounting hanger accessory.

B

NOVA 15i

809

NOVA 27i

908

NOVA 38i

1007

A

Summary of Contents for NOVA 15i

Page 1: ...Installation Form 6 FXD control settings Accessories Auxiliary switch Terminals Pole mounting hanger Arrester mounting brackets Substation mounting frame Service information Service requirements Freq...

Page 2: ...s situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury CAUTION Indicat...

Page 3: ...oser and inspect it thoroughly for damage incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the...

Page 4: ...100 9 4 kV 50 kV 45 kV 125 kV 100 16 4 kV 60 kV 50 kV 170 kV 100 23 0 kV 70 kV 60 kV Table 2 Current ratings A Description 15 kV 27 kV 38 kV Rated continuous current Short circuit current Symmetrical...

Page 5: ...Terminal to terminal 1180 79 Lower terminal to ground earth 671 45 NOVA 27i Terminal to terminal 1473 55 Lower terminal to ground earth 951 35 NOVA 38i Terminal to terminal 1763 46 Lower terminal to g...

Page 6: ...1E Effective January 2017 Figure 3 NOVA 15i recloser dimensions with 3 integrated voltage sensor option in load side Note All dimensions are mm Dimensions shown are approximate Terminal connectors Ter...

Page 7: ...converter board also houses voltage monitoring and conditioning circuits that protect the battery from failure and provide trip close operations without ac power In the absence of ac power to the ele...

Page 8: ...ices when making hitches and lifting the equipment Lift the unit smoothly and do not allow the unit to shift This equipment is not intended to protect human life Follow all locally approved procedures...

Page 9: ...ded on both sides Hazardous voltage Solidly ground all equipment Failure to comply can result in death severe personal injury and equipment damage WARNING Equipment Damage Do not adjust or rotate bush...

Page 10: ...of a grounding mat may be required depending upon the local safety regulations defining the permissible step and touch potential levels Consult local regulations for proper grounding procedures In pol...

Page 11: ...the equipment It is recommended to use a minimum of 50 sq mm copper wire for the pole ground connection to the recloser 2 Any ground wire of the equipment is not allowed to be connected to the neutra...

Page 12: ...quipment It is recommended to use a minimum of 50 sq mm copper wire for the pole ground connection to the recloser IMPORTANT All external inputs to the control must be routed within 203 mm of their co...

Page 13: ...his equipment is not intended to protect human life Follow all locally approved procedures and safety practices when installing or operating this equipment Failure to comply can result in death severe...

Page 14: ...tor located on the mechanism housing Provide a good electrical ground connection to the control cabinet ground Note Painted surfaces of the mechanism housing may prevent a ground connection to the rec...

Page 15: ...voltage sensor Energize recloser and confirm the voltage outputs in the control When the recloser is energized the output of the voltage sensor in 6 V based upon the Form 6 FXD control s input impeda...

Page 16: ...for a Wye connection Also the Phantom Phase feature must be disabled Refer to Service Information S280 70 4 for more information on programming the Form 6 FXD control Figure 16 Form 6 FXD control syst...

Page 17: ...tion to copper wires to optimize the electrical connection Anti oxide coatings for temporary protection of wire brushed aluminum cable connections to flat pad terminals must be maintained at intervals...

Page 18: ...ing brackets The arrester mounting bracket accessory see Figure 18 can be bolted to the recloser frame and pole mounting hanger for the addition of inboard and outboard arresters The arresters are not...

Page 19: ...vailable for substation mounting applications Figure 19 Dimensions of NOVA i recloser with substation mounting frame accessory Terminal options A Eyebolt 1 0 500 mcm 89 Cable range 630 A maximum Eyebo...

Page 20: ...gs settings and interface options on the recloser nameplate see Figure 6 are correct for the planned testing 2 Test electrical open and close operation Close and open the recloser contacts using the m...

Page 21: ...0 seconds TEST 2 1 Close the recloser contacts 2 Ground the recloser 3 Ground Phase A terminal 2 and Phase C terminal 6 4 Apply proper test voltage to Phase B terminal 3 5 The recloser should withstan...

Page 22: ...k to its original condition 1 Bypass and remove the recloser from service as described in this manual 2 Inspect module for damage to the terminals Remove any damaged terminals and replace 3 Inspect mo...

Page 23: ...S3 COM N O R1 C Open COM N C 52a MS1 R1 A VTC Pull Up 2 R1 E Close COM N O 52b MS2 R1 B VTC Pull Up 1 H2 H1 R1 U R1 V LEGEND SYMBOL DESCRIPTIO N AB Actuator Circuit Board AS Auxiliary Switch 3 Stage C...