Fixed capacitor banks (Unipump, Unipak, and Unipak
detuned filter) low voltage (600 V and below), NEMA 1
NEMA 3R (outdoor) enclosed versions
EATON
www.eaton.com
Table 7. Rated current values in amperes
kVAR
240 Vac
480 Vac
600 Vac
1
2.4
—
—
1.5
3.6
1.8
—
2
4.8
2.4
—
2.5
6
3
—
3
7.2
3.6
—
4
9.6
4.8
—
5
12
6
4.9
6
14.4
7.2
—
7.5
18
9
7.4
8
19.2
9.6
—
9
—
10.8
—
10
24
12
9.8
12.5
30
15
12
15
36
18
15
17.5
42
21
17
20
48
24
20
22.5
54
27
22
25
60
30
25
27.5
—
33
27
30
72
36
29
32.5
78
39
32
35
84
42
34
37.5
90
45
37
40
96
48
39
42.5
102
51
42
45
108
54
44
50
120
60
49
55
—
66
54
60
144
72
59
65
—
78
64
70
168
84
69
75
180
90
74
80
192
96
78
85
—
102
83
90
216
108
88
100
240
120
98
120
288
144
118
125
—
150
123
140
336
168
137
150
360
180
147
160
384
192
157
180
432
216
176
200
480
240
196
225
—
270
221
250
—
300
245
300
—
360
294
350
—
420
343
400
—
480
392
Operating features
During normal operation, cleared fuse indicator lamps will
not illuminate. When a fuse clears on an energized unit, the
associated lamp will glow.
Unipak detuned filters are equipped with a self-resetting reactor
over-temperature indicator lamp . Thermal overload indicating light
activates when reactor temperature reaches 180 °C .
Reactor cabinet thermal overload and cleared fuse indicator lamps
Maintenance
The following maintenance items require the capacitor to
be energized and should be performed only by trained and
qualified personnel .
m
WARNING
ONLY QUALIFIED ELECTRICIANS SHOULD HANDLE THE INSTALLATION AND
MAINTENANCE OF THIS CAPACITOR BANK; OTHERWISE, ELECTRIC SHOCK,
ARC FLASH, OR FIRE MAY OCCUR.
Retorque
Before handling the capacitor, disconnect all and any electrical
power supply from the circuit into which the capacitor bank is being
installed . Extreme caution must be taken to prevent accidental
contact with the terminals of the capacitor during installation,
operation, and service of this equipment . Accidental contact with
the capacitor, if not properly discharged, can result in personal injury
or death .
After five minutes of removing all power from the capacitor bank,
the capacitors inside the enclosure can be accessed by shorting all
terminals and then grounding the leads using an insulated shorting
jumper wire . Using a DC voltmeter, confirm that the capacitor has
entirely discharged as evidenced by zero voltage present between
the capacitor terminals prior to performing installation, operation,
or service of the capacitor bank . Accidental contact with energized
parts may cause personal injury or death .
Generally, power factor capacitor banks are considered to be
maintenance free . Over time, the capacitance value may decrease,
especially when self-healing occurs .