O&M Manual for 30-1000 Amperes

 Manual Transfer Switch

4.4 Vertical Design Load Lug Location

Transfer switch equipment is supplied as standard from the fac-

tory with its load terminal lugs at the top. If the load lugs are to be 

repositioned to the bottom, do it at this time before wiring the unit 

or making power cable connections.

With the solid steel shield removed, proceed with the following 

steps (Figure 4):

Step 1:

Disconnect the power panel from the rest of the transfer 

switch by unplugging the connector plugs (S1, S2 and 

S3) (Figure 15).

Step 2:

Remove the bolt that bonds the neutral strap to the rear 

of the enclosure, if it is in place.

Step 3:

Remove the four bolts that secure the power panel in the  

enclosure. Depending upon the size of the panel, it may 

be advisable to have assistance with the removal. Once 

the power panel is free, carefully move it to a solid work  

surface (Figure 6).

Figure 13. Vertical Design Load Lug Assembly Shown Mounted

Step 4:

Remove the operating mechanism from the front of the 

power panel by removing the six bolts holding the mech-

anism in position. The molded case switches or optional 

circuit breakers do not have to be removed (Figure 8).

Step 5:

The load lug assembly, just mentioned, is removed by 

first removing the six or eight bolts securing the pieces of 

insulated bus to the back of the power panel. The num-

ber of mounting bolts depends upon whether 3- or 4-pole 

devices are installed. Mounting bolts are accessed 

through holes in the load end of the molded case 

switches or optional circuit breakers.

Step 6:

Next, remove the 4 bolts holding the mounting bracket to 

the upper rear portion of the power panel. The load lug 

assembly can now be removed as one unit.

Note:

 There are grooves in the back of the power panel and in the mount-

ing bracket that keep the polyester phase barriers in their proper positions.

    

 

WARNING

IF THE LOAD LUG LOCATION IS BEING CHANGED ON ALREADY 

INSTALLED TRANSFER SWITCH EQUIPMENT, MAKE SURE THAT 

THE NORMAL, EMERGENCY AND OTHER POWER SOURCES CON-

NECTED TO THE EQUIPMENT ARE DE-ENERGIZED. HAZARDOUS 

VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH EQUIPMENT 

AND CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

  

NOTICE

AT THIS POINT, TAKE THE TIME TO REFER TO FIGURE 13 AND 

BECOME FAMILIAR WITH THE INSIDE REAR OF THE ENCLOSURE 

AND THE POWER PANEL MOUNTING PROVISIONS AVAILABLE FOR 

BOTH TOP AND BOTTOM ENTRY. IT WILL FACILITATE RE-INSTAL-

LATION OF THE POWER PANEL.

  

NOTICE

THE REAR MOUNTED LOAD LUGS, DIP INSULATED BUS BARS, 

STANDOFF INSULATORS, GLASS POLYESTER PHASE BARRIERS, 

AND METAL MOUNTING BRACKET ARE DESIGNED TO BE REMOVED 

AS ONE LOAD LUG ASSEMBLY (FIGURE 14).

Summary of Contents for MTVXKDA20225WRU

Page 1: ...m O M Manual for 30 1000 Amperes Manual Transfer Switch Instruction Booklet Description Page Introduction 2 Receiving Handling and Storage 5 Equipment Description 6 Installation and Wiring 10 Operatio...

Page 2: ...eding If further information is required by the purchaser regard ing a particular installation application or maintenance activity an Eaton representative should be contacted 1 1 1 Warranty and Liabil...

Page 3: ...rugged compact design utilizing molded case switches to effect the transfer of essential loads from one power source to another Figures 3 4 and 5 Molded case switches are interlocked to prevent both s...

Page 4: ...00 Amperes Manual Transfer Switch Table 2 Transfer Switch Catalog Number Explanation Figure 3 Vertical Design Automatic Transfer Switch Equipment with Deadfront Cover in Place Over Power Panel 225 100...

Page 5: ...affixed to the top of the shipping container which includes a variety of equipment and customer information such as General Order Number GO and Catalog Number Cat Make certain that this information ma...

Page 6: ...stance stack other equipment on top of a transfer switch equipment enclosure whether packaged or not Section 3 Equipment Description 3 1 General Eaton transfer switch equipment is available in four d...

Page 7: ...The switches incorporate pos itive quick make quick break toggle mechanisms and DE IONT arc chutes Vertically mounted switching devices are mechanically and electri cally interlocked to prevent the t...

Page 8: ...Both N E Selectable or Load line 2 DP 4000 Normal or Emergency or Both N E Selectable or Load line 3 Custom metering available contact Eaton 20A Rear Bus Connections Front connected solder less lugs...

Page 9: ...e and or C In legally required standby systems in accordance with article 701 of the National Electrical Code Since Eaton Transfer Switches utilize specially designed molded case switches and or molde...

Page 10: ...ting Procedure All transfer switch equipment enclosures are of the same design Only the overall physical dimensions change The enclosure is provided with four elongated mounting holes two in the top m...

Page 11: ...and set aside in a safe place until mounting is complete Step 2 Install required mounting bolt anchors and the two upper mounting bolts in the mounting surface Step 3 Gently lift the enclosure and gu...

Page 12: ...removed Figure 8 Step 5 The load lug assembly just mentioned is removed by first removing the six or eight bolts securing the pieces of insulated bus to the back of the power panel The num ber of mou...

Page 13: ...glass polyester phase barriers are in place and positioned properly in the grooves provided When making any bolted connection to the bus comply with the torque requirements as outlined in Table 4 Tab...

Page 14: ...holes in the power panel with the pre tapped inserts in the rear of the enclosure Step 10 With the power panel held securely against the back of the enclosure replace and tighten the four mounting bol...

Page 15: ...Step 6 Tighten cable lugs to the torque identified on the label affixed to the unit immediately adjacent to the lugs Step 7 Make necessary connections of options using wiring dia grams and Quick Start...

Page 16: ...600 Vac are provided Figure 9 A small disconnect plug is provided to change from one voltage to another Horizontal Design Voltage Selection Horizontal design transfer switches are furnished with an ad...

Page 17: ...of the handle to open and or close the main contacts Figure 19 The three switch positions Normal Neutral and Emergency are visually indicated on the indi cator wheel Figure 20 To manually operate the...

Page 18: ...individual representing company 6 Basic description of the situation as it exists 7 Any results of the problem solving steps taken and or read ings taken 6 2 1 Transfer Switch Appears In inoperative S...

Page 19: ...rol power is switched off by disconnecting all logic plugs b Inspect structure area for safety hazards or potential maintenance problems Inspect area especially where molded case switching devices are...

Page 20: ...N RECOMMENDATIONS AND DESCRIPTIONS CON TAINED HEREIN In no event will Eaton be responsible to the pur chaser or user in contract in tort including negligence strict liability or otherwise for any spec...

Reviews: