Page 47
s
The
s
segment transducer block will adjust the
following PreAlert limits (Alert limits are not modified by the wizard):
o
low- and high-limits of the fieldbus segment power supply
o
high limit for the noise levels (there is no low limit)
o
low- and high-limits for device signal amplitudes.
It also allows the user to select whether a removed or added device creates an alarm
or not.
The wizard is executed in 3 steps:
o
Step 1: select the fieldbus segment power supply
Select the model of fieldbus power supply in use. If you are using a model
the limits according to the datasheet of the fieldbus power supply in use.
Default values are as shown in the following table: