High limit: 65 °C
High-high limit: 65 °C
Minimum value
0 °C
Maximum value
32767 °C (Note: module
operates up to 70 °C)
Alarm hysteresis (no alarm
→
alarm
→
no alarm)
1 °C
Latching Alarm Acknowledge (If Alarm Acknowledge is required, see
further below)
Click this button to acknowledge all active alarms in this transducer block.
Reset Measurement Processor
Reset measurement processor to recover from fault state. Warning! Resetting
measurement processor will delete device and segment tag data. Ensure this is backed
up and download these parameters after reset.
Set Monitored Segments
The default value is to monitor all 8 segments. If any segments are not in use these
may be omitted from the scan. It is recommended to set non-scanning segments to
display null values. Whilst investigating an issue on a segment, select only that segment
number to scan only that segment. After resolving the issue scanning should be reset
to all active segments.
Set Non-scanning Segment Values to Null
The default is to display the last measured values for the segment. If any segments are
not in use it is recommended to set to display null values and disable scanning on
these segments.
Set Alarms to Latch
Set if alarm acknowledgement is required. Default is alarms do not require
acknowledgement.